Page 1: ...CONTENTS To the owner Congratulations on receiving your GPI 4 20 mA Out with Display We are pleased to provide you with a product designed to give you maximum reliability and efficiency Our business i...
Page 2: ...in indoor or outdoor applications where occasional exposure to moisture is common The 4 20 mA Out with Display is available in two ver sions One indicates flowrate in units minute and one in units ho...
Page 3: ...her liquids occasional low pressure splashing will not harm unit if cable entry points are well sealed subject to 5g shock loading facing the sun directly for long periods of time close to high voltag...
Page 4: ...m ONLY Local Com HL HF IN R See note EDM Power INPUTS OUTPUTS 4 20 mA Out with Display Loop Loop current current Min V 8 5 Max V 35 Customer Equipment Minimum signal amplitude required for normal oper...
Page 5: ...Max V 35 Customer Equipment Loop Power Supply Typ 12 24 VDC Loop Input Loop Input NOTE 1 Loop power supply electrically isolated from customer equipment NOTE 2 Actual value of loop current mA is disre...
Page 6: ...Frequency Generating Input Device INPUTS OUTPUTS 4 20 mA Out with Display Loop Loop current current Customer Equipment Loop Power Supply Typ 12 24 VDC Open Collector Pulse In Pulse In Return Pulse Ou...
Page 7: ...that the enclosure sealisnotcrimpedortwisted Donotover tightencornerscrews hand tighten only Faceplate can be rotated 90 W I R I N G D I A G R A M 8 4 20 mA or 0 20 mA Output Customer Equipment Witho...
Page 8: ...4 20 mA and Pulse Output option available only with Reed Switch input W I R I N G D I A G R A M 1 0 4 20 mA or 0 20 mA Output and Pulse Output Customer Equipment With Built in Power Supply Input Reed...
Page 9: ...button for 3 seconds to reset the Batch Total to zero When fluid is flowing through the meter a small propeller icon is highlighted Flowrate Feature Tousethisfeature pressandreleaseDISPLAYuntilFLOWRA...
Page 10: ...ser to tweak the factory calibration by a percent that represents application fluid or plumbing differences 1 To calibrate press and hold the CALIBRATE and DISPLAY buttonsforabout3secondsuntilyouseeFL...
Page 11: ...the transmitter If signal is being received deactivate it by one of the following methods Stop the flow through the line that is being recorded Disconnect the output device on the flowmeter Locking U...
Page 12: ...presently operating temporarily disable its external power supply Be sure to allow at least 30 seconds to elapse with unit unpowered 2 Press and hold the 4 button While holding watch the indicator li...
Page 13: ...signal input connections for intermittent open or short circuits F LOOP OUTPUT 1 Output response time setting too long Select a shorter response time setting STABLE BUT especially for fast input sign...
Page 14: ...14 DIMENSION DRAWINGS...
Page 15: ...Tapping GM001 GM002 and GM003 2 9 120058 01 Bracket 1 10 904005 13 Screw 6 32 x 1 2 in 4 Item No No Part No Description Req d 11 904002 44 Screw 8 32 x 5 16 in 2 12 125066 20 Cable 20 ft 1 125066 3 C...
Page 16: ...linearity plus span any input loop current output 0 C to 70 C loop voltage supply 12 VDC to 24 VDC 0 5 of span plus possible resolution uncertainty Max Conversion Resolution Uncertainty Loop current o...
Page 17: ...gital Pulse Out Open Collector square wave Will switch up to 60 V and up to 200 mA Closed circuit voltage drop typically 0 1 V guaranteed less than 0 5 V at any in range current Configuration 2 Totals...
Page 18: ...Please contact GPI before returning any part It may be possible to diagnose the trouble and find a solution with a telephone call GPI can also inform you of any special require ments you will need to...
Page 19: ......
Page 20: ...rranty shall not apply if A the product has been altered or modified outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has bee...