Before installation:
-.Carefully.check.for.mechanical.damage.on.the.surface.of.the.terminal’s.palm.scanner,.circuit.
board.and.housing;
-.In.order.to.avoid.short.circuits,.the.protected.ends.of.cables.used.to.connect.the.terminal.must.
not.exceed.5.mm.
Cab. no.
Cable connection
Max. length
Type
1
Ethernet.(IEEE.802.3).–.terminal
100.m
Four.twisted.pair.cables.of.no.lower.than.
category.five.with.a.wire.size.of.no.less.
than.0.2.mm
2
2
Power.source.–.terminal.power
2.m
Duplex.cable.with.a.wire.size.of.no
less.than.0.75.mm
2
.(for.example,.3192Y)
3
Terminal.–.lock,.BCR.-.lock
2.m
Duplex.cable.with.a.wire.size.of.no
less.than.0.75.mm
2
.(for.example,.3192Y)
4
Terminal.–.BioSmart.BCR
2.m
Four.twisted.pair.cables.of.no.lower.than.
category.five.with.a.wire.size.of.no.less.
than.0.2.mm
2
5
IN,.IN+.terminal.contacts.–.external.devices
2.m
CQR-6.or.RAMCRO-6.cable
6
WO0,.WO1.terminal.contacts.–.external.
devices
2.m
Four.twisted.pair.cables.of.no.lower.than.
category.five.with.a.wire.size.of.no.less.
than.0.2.mm
2
Table.2...Types.of.cables.used:
8.2.Installation.procedure
The.terminal.must.be.installed.using.the.following.procedure:
1..Open.the.box.and.verify.that.all.the.terminal’s.parts.are.present.
2..Decide.where.you.will.install.the.terminal.
3..Unscrew.the.screws.located.in.the.lower.part.of.the.terminal.housing.which.secure.the.housing.
to.the.rear.panel..Remove.the.rear.panel.
4..Place.the.rear.panel.of.the.terminal.on.the.wall.and.mark.out.the.fixture.points.for.the.terminal.
(fig..4).
5..Lay.and.feed.through.all.the.required.cables..The.cables.used.must.correspond.to.table.2,.or.
have.similar.technical.characteristics..Ensure.that.there.are.no.tears,.breaks.or.mechanical.defects.in.
the.cables..Ensure.that.the.power.is.off.before.connecting.any.cables...
6..Feed.the.cables.through.the.hole.for.cable.insertion.in.the.terminal’s.rear.panel..