MAVOWATT 210
Gossen Metrawatt GmbH
37
8.2.2
Connecting Voltage Measurement Cables to the Circuit to be Measured
Direct connection of all voltage measurement inputs are rated at 600 VRMS
max. When measuring voltages greater than 600 VRMS, potential transform-
ers (PTs) or other transducers must be used.
Voltage probes are connected to the individual source or load lines and are ref-
erenced to the return (common).
The instrument is powered off.
1. Connect the alligator clips of the instrument to the circuit to be measured.
8.2.3
Connecting AC Current Probes to MAVOWATT 210
The instrument is powered off.
1. Plug the probe output cable of the current probe to the current input of the
instrument.
8.2.4
Connecting AC Current Probes to the Circuit to be Measured
Attention!
!
DO NOT use other probe types, including probes that use uninsulated
connectors.
Attention!
!
DO NOT USE non-insulated current probe cores around a non-insulated
wire. Probes of this type are designed for use around insulated wires
only. Use only completely insulated probe cores with no exposed con-
ductive areas of the core around non-insulated wires.
Attention!
!
DO NOT attempt to measure current in any circuit in which the circuit to
ground voltage exceeds the insulation rating of the current probe (exam-
ple: 600 VRMS max).
Attention!
!
Make sure the current probes are tightly closed. Keep mating surfaces
clean and free from foreign matter.