Water-to-water Heat Pump

 

 

 

 

28

 

9.

 

Connection to Power Supply 

The heat pump must be connected to the power supply grid. Connection to the grid must be made 

by an expert in compliance with applicable legislation and local regulations. The heat pump has a 

separate power supply line and controls supply line.  

Power Supply Line  

The installation technician must assure proper electric protection of the heat pump power supply 

line. A 3p/16A/C circuit breaker should be used.  

The three-phase power line must be made with a 5G2.5 cable cord. The cable cord should be 

installed in the heat pump from the rear side via the M25x1.5 cable entry in order to prevent 

moving and falling out of the cable cord from the terminal pins located on the electronics holder. 

The cable cord should be connected to the DOVOD 3x400 VAC-1X1 terminal pins.  

In case of an incorrect sequence of phases, the controller will report the error: 'Electric lock E6'

Be careful – make sure the phase sequence is correct! 

Do not forget to connect the PE earth conduit! 

 

Controls Supply Line 

The installation technician must assure proper electric protection of the control line of the pump. A 

1p/6A/C circuit breaker should be used.  

A single-phase power line must be made with a 3G1.5 cable cord. The cable cord should be 

installed in the heat pump from the rear side via the M20x1.5 cable entry in order to prevent 

moving and falling out of the cable cord from the terminal pins located on the electronics holder. 

The cable cord should be connected to the DOVOD 230 VAC-1X3 terminal pins. 

In case of an incorrect sequence of phases, the controller will report the error: 'Electric lock E6'

 

Do not forget to connect the PE earth conduit! 

Summary of Contents for HPWW12

Page 1: ...1 gorenje Heat Pump WATER TO WATER Instructions for Installation and Start up...

Page 2: ...Water to water Heat Pump 2 1 INDEX...

Page 3: ...nstallation of the water to water heat pump They include a description of the start up procedure that should be carried out by a competent expert authorised by the manufacturer Use the following Conte...

Page 4: ...quirements for water pureness With power supply connection observe the correct rotation field and the proper diameters of the cable cords used The first start up must be carried out by an authorised s...

Page 5: ...heat pump may be connected to a heat source heating system or electric power supply in compliance with applicable regulations Electric connection must be fixed via a circuit breaker switch that cuts o...

Page 6: ...e heat pump is transferred to the refrigerant cooling down the underground water by 2 to 4 C the cooled water is then returned to underground some 15 m away from the point of collection in the directi...

Page 7: ...f the unit is used for connection to the electricity supply and for connection of the circulating pump temperature probes and mixing valves The unit cooling circuit is filled with R407C refrigerant Th...

Page 8: ...3 Measuring point return line heating 4 Heat exchanger 5 Pressure switch low pressure 6 Compressor 7 Compressor power supply terminal 8 Compressor return pipe suction 9 Sight glass fitting for contro...

Page 9: ...vicing connection refrigerant pressure at compressor inlet 3 Mechanical expansion valve 4 Servicing connection refrigerant pressure at evaporator inlet 5 Heat exchanger evaporator 6 Flow rate switch m...

Page 10: ...re copper AISI316 Pure copper AISI316 Pure copper AISI316 Pure copper AISI316 Refrigerant volume I 1 13 1 24 1 80 2 36 3 15 Water volume I 1 24 1 35 1 92 2 48 3 27 EVAPORATOR Material Steel 1 4404 316...

Page 11: ...0 pri W10 W35 8 4 5 4 11 6 5 4 14 2 5 4 17 7 5 6 pri W10 W45 8 0 4 1 11 1 4 1 13 7 4 2 16 8 4 3 pri W10 W55 7 7 3 1 10 6 3 1 13 0 3 1 16 0 3 3 Sound power level dB A Heating water flow rate at interna...

Page 12: ...upply Rated voltage circuit breaker allowed deviation V A 10 400 10 400 10 400 10 400 16 400 16 Rated electric power W10 W35 kW 1 21 1 56 2 15 2 63 3 16 Rated current A 2 18 2 81 3 88 4 75 5 70 Other...

Page 13: ...g and the air humidity is not too high Place the heat pump horizontally on a firm floor with adequate load bearing capacity The lower part of the frame should stand firmly on the floor in order to ass...

Page 14: ...Pump 14 Make sure there is min 1 m free space above the unit Distance from the wall depends on the position of the connection pipes and electricity supply cables and may be larger if necessary Do not...

Page 15: ...ther impurities Eventual impurities get deposited on the condenser and may cause malfunctions during operation All required elements must be included in the heating circuit safety valve pressure metre...

Page 16: ...eat pump the minimum required heating water flow rate must be assured This can be achieved by using various techniques including correct adjustment of the over flow valve or a valve manifold with no p...

Page 17: ...filter at the heat inlet source on the heat pump to prevent impurities and protect the evaporator against eventual damages During the first months of use the filter should be cleaned more often Once t...

Page 18: ...source The borehole shall be made on a distance 10 15 m along the water flow direction in order to avoid mixing the warm source inlet water and the cold source outlet water The capacity of the second...

Page 19: ...clude safety elements expansion vessels safety valves bleed valves etc these should be provided by the installation technician Detailed hydraulic drawings with complete elements are composed as separa...

Page 20: ...Diagram 1 Ground water heat pump with direct heating circuit Multifunction inlets outlets RVS61 Diagram 2 Ground water heat pump with direct heating circuit sanitary water tank and Q3 pump Multifunct...

Page 21: ...ump with direct heating circuit sanitary water tank and Q3 reversing valve Multifunctional inlets outlets RVS61 Diagram 4 Ground water heat pump with heat water tank mixing valve or direct heating cir...

Page 22: ...ater tank Q3 pump and mixing or direct heating circuit Multifunctional inlets outlets RVS61 BX1 B4 BX2 B41 Diagram 6 Ground water heat pump with heat water tank sanitary water tank Q3 reversing valve...

Page 23: ...for sanitary water and mixing or direct heating circuit Multifunctional inlets outlets RVS61 BX1 B4 BX2 B41 Diagram 8 Ground water heat pump with combined water tank Q3 reversing valve for sanitary w...

Page 24: ...am 9 Ground water heat pump with combined water tank Q3 reversing valve for sanitary water solar collector and mixing or direct heating circuit Multifunctional inlets outlets RVS61 QX5 Q5 QX6 K8 BX1 B...

Page 25: ...ater Heat Pump 25 Diagram 10 Ground water heat pump with sanitary water tank Q3 reversing valve direct heating circuit and mixing cooling circuit for passive cooling Multifunctional inlets outlets RVS...

Page 26: ...and mixing cooling circuit for passive cooling Multifunctional inlets outlets RVS61 QX2 Y28 QX3 Y21 BX1 B4 BX2 B41 Diagam 23 Ground water heat pump with combined water tank with Q3 reversing valve mix...

Page 27: ...pump that you want to include in the heating system as shown in diagram 5 Select diagram 5 menu Configuration parameter 5700 5 and set heat source to Water menu Configuration parameter 5800 Water If y...

Page 28: ...holder The cable cord should be connected to the DOVOD 3x400 VAC 1X1 terminal pins In case of an incorrect sequence of phases the controller will report the error Electric lock E6 Be careful make sure...

Page 29: ...e and the controls supply line be connected to a separate FI switch so that in case of power failure the heating system continues functioning Connecting cable cords Minimum diameter of wire cross sect...

Page 30: ...mp to the power supply the temperature sensors circulating pumps and other elements also need to be installed All elements are connected via inputs outputs on the heat pump controller Connecting cable...

Page 31: ...evaporator Source outlet temperature CL Communication data indoor unit 2 M Ground s CL Communication ground indoor unit 3 b BX1 Multifunctional sensor input BX1 CL Communication data indoor unit 1 M...

Page 32: ...Water to water Heat Pump 32...

Page 33: ...Water to water Heat Pump 33 10 Electric Wiring Diagrams Dashed lines in the wiring diagram can be connected by the installation technician on site if necessary Wiring diagram ground water...

Page 34: ...Water to water Heat Pump 34 Wiring diagram water water 17...

Page 35: ...Water to water Heat Pump 35 Wiring diagram ground water...

Page 36: ...Water to water Heat Pump 36 Wiring diagram ground water...

Page 37: ...Water to water Heat Pump 37 Wiring diagram ground water...

Page 38: ...Water to water Heat Pump 38 Wiring diagram ground water...

Page 39: ...Water to water Heat Pump 39 Wiring diagram ground water...

Page 40: ...Water to water Heat Pump 40 Wiring diagram ground water...

Page 41: ...Water to water Heat Pump 41 A B C D E F G H 11 Operating of Heat Pump B A H D J G C I E...

Page 42: ...e displayed on the display screen of the operating unit The symbols are displayed according to the selected mode of operation and set parameters Displayed symbols Xxxxxxxxxxxxxxxxxxxxxxxxxxx Xxxxxxxxx...

Page 43: ...ly Additional accessories can be purchased separately to provide comfort and easy operation of the heat pump a ADVANCED ROOM OPERATING UNIT used for setting the same adjustments as on the indoor unit...

Page 44: ...us modes of operation of the heat pump and change parameters When switching on the heat pump for the first time the display turns on and the MAIN MENU is displayed By pressing individual buttons and t...

Page 45: ...and Time of Day and Date will appear on the display Turn the E main navigation knob to the setting Operator section After confirming the selection the word Language will appear on the display Confirm...

Page 46: ...navigation knob one increment to the RIGHT to set the DATE Confirm the selection The current selection DATE in the month flashes Turn the E main navigation knob to the required value Confirm the sele...

Page 47: ...ays are covered by Timer Operation Turn the E main navigation knob and select the required days in the week from Monday until Friday Confirm the selection Turn the E main navigation knob one increment...

Page 48: ...me Operation the heat pump operates in the Night Regime See Section Setting Room Temperature Operation Mode Selection A key This operation mode is used for selection among various heating modes The se...

Page 49: ...is carried out without Timer operation The temperature in the room can be adjusted on two levels 1 In day operation mode the temperature can be set in the range from the Night Operation Mode temperatu...

Page 50: ...th an underline sanitary water is heated according to the selected program Press the B key once again to switch off the Preparation of Sanitary Mode This means that once the heated water is used up it...

Page 51: ...Setting of room temperature Day Operation Mode Press the OK D key and Time of Daily Setting Point will appear on the display Turn the E main navigation knob and confirm the selection Turn the E main n...

Page 52: ...days Press the OK D key and Time of Day and Date will appear on the display Turn the E main navigation knob to Holidays OK1 Confirm the selection Turn the E main navigation knob one increment to the R...

Page 53: ...e only in Automatic operation mode Restart After Failure In case of a failure caused by malfunction in the operation of the heat pump the warning Error appears on the display and the heat pump stops C...

Page 54: ...erating the Heat Pump Setting Feature End user The case below indicates that some user levels do not support all settings highlighted in the example below while on the unit they can not be seen Settin...

Page 55: ...Water to water Heat Pump 55...

Page 56: ...an be adapted In case the set room temperature with defined ambient conditions is too low the curve line can be adapted Press the OK D key and Time of Day and Date will appear on the display Turn the...

Page 57: ...to water Heat Pump 57 Temperatura ogrevalnega voda Temperatura okolice 42 8 0 80 Example with an outside air temperature of 8 C and a preset heating curve of 0 80 the heating line temperature demand i...

Page 58: ...u Configuration parameter 6128 the unit switches on when the temperature is below the set value factory set at 0 C and parameters 6129 the unit switches off when the temperature is below the set value...

Page 59: ...ank needs to be heated but the heat pump failure Limit Source Temp Min Brine too low of a temperature of the source prevents it In this case the heat pump switches off and the water is heated by the e...

Page 60: ...with operating unit No heating operation Incorrect setting Select required mode of operation follow the Instructions No hot sanitary water Incorrect setting Select required mode of operation for heat...

Page 61: ...lves the circulation pump and the plastic pipes the loose rust particles may enter the heating system With a floor heating system use of impermeable material is mandatory We recommend using pipelines...

Page 62: ...pump During the first months of use the filter should be cleaned more often Once the amount of impurities is reduced the cleaning intervals may be longer Required water pureness The underground water...

Page 63: ...0 Nitrate NO3 dissolved 100 100 0 PH value 7 5 7 5 to 9 9 0 0 0 Oxygene 2 2 0 Hydrogene sulfide H2S 0 05 0 05 0 HCO3 SO42 1 1 0 0 Hydrogen carbonate HCO3 70 70 to 300 300 0 0 0 Alumminium Al dissolve...

Page 64: ...Water to water Heat Pump 64...

Reviews: