27
User Manual V1.0-2022-08-20
06 Electrical Connection
6.5.2 Connecting the Communication Cable
The cables for remote shutdown, smart meter, parallel connection, and power supply for
RSD module are connected in the same way. The following illustration shows an example of
connecting smart meter communication cable.
NOTICE
• Make sure that the cable is connected correctly and securely. Clear the debris after completing
the connection.
•
Seal the AC output terminal to ensure the ingress protection rating.
6-8mm(0.24-0.31in)
6-8mm(0.24-0.31in)
NOTICE
Make sure that the communication device is connected to the right terminal. Route the
communication cable far away from any interference source or power cable to prevent the
signal from being influenced.
Step 1
Make the communication cable.
Step 2
Connect the cable with the terminal.
Step 3
Disassemble the DC routing hole’s end cap.
Step 4
Use the cable gland for routing wires.
Step 5
Plut the communication connector into the inverter.