22
User Manual V1.0-2022-08-20
06 Electrical Connection
20mm(0.79in)
20mm(0.79in)
6.4 Connecting the AC Output Cable
WARNING
•
Do not connect loads between the inverter and the AC switch directly connected to the
inverter.
• The Residual Current Monitoring Unit (RCMU) is integrated into the inverter. The inverter
will disconnect the utility grid rapidly once it detects any leak current over the permissible
range.
NOTICE
•
Install one AC circuit breaker for each inverter. Multiple inverters cannot share one AC circuit
breaker.
•
An AC circuit breaker shall be installed on the AC side to make sure that the inverter can
safely disconnect the grid when an exception happens. Select the appropriate AC circuit
breaker in compliance with local laws and regulations. Recommended AC circuit breakers:
Step 1
Make the DC output cable.
Step 2
Disassemble the DC routing hole’s end cap.
Step 3
Use the cable gland for routing wires.
Step 4
Connect the DC terminals to the inverters.