In all levels of menu, it will automatically enter the first item of the level 1 menu if no action is taken within 30S, meanwhile, the 

modified data will be stored into internal memory. 

(

4)

 

Menu introduction:

Long press ‘ENTER’ in the Configure Safety interface,there will be set safety interface .press ‘Down’ or ‘Up’ to choose the safety you 

need and then long press ‘ENTER’,the safety you need can be set.

● 

When PV panel is feeding power to the inverter, the screen shows the first interface of level 1 menu. The interface displays current 

state of the system. It shows 'Waiting' in the initial state; it shows 'Normal' during power generation mode; if there is something 

wrong with the system, error message is shown.

 

Error

 

code

 

can

 

be

 

refered

 

to

 

4

.

3.

● 

Press any key once to turn on the LCD backlight when it is off; if the backlight is on, press 'DOWN' key to enter the next menu 

displaying data of Vpv and Ipv; press 'ENTER' to lock the current  interface.

● 

In the level 1 menu, the displayed information can be switched through 'DOWN' and 'UP' key operation, there are 7 interfaces in 

total, which are circulatory.

 

The level 2 menu can only be selected through 'ENTER' from the seventh interface.

In the level

 

2 menu, short press 'Error Log' to enter the historical error message interface, press 'up' and 'down' to inquire the first 

5 historical error message, press 'Esc' to return. 

In the level

 

2 menu, short press 'Date&Time' to enter the time setting interface, press 'up' and 'down' to change the data, short 

press 'Enter' to move cursor, long press 'Enter' to save the settings. 

In  the  level  2  menu,  choose  'Language'  and  press  'Enter'  to  enter  language  setting  interface,    the  LCD  will  flash,  press  'up'  or 

'down' to change language, long press 'Enter' to save the settings, when it stops flashing, press 'Esc' to return. 

In the level 2 menu, choose 'Histogram', short press 'Enter' to enter the level 3 menu to inquire the historical power generation, in 

the level 3 menu, press 'up' or 'down' to inquire power generation data in Year Mode, Month Mode, Day Mode and Hour Mode, 

short press 'Enter' to show the historical power generation, press 'Esc' back to main menu. 

In  the  level  2,  the  Menu  after  'Histogram'  is  communication  selecting  interface,  if  it  is W

i

Fi  model,  It  shows  as    'Set  Zigbee'

 

(It 

shows  as  'Set  Local'  for  the  SDT  series).  Long  press  'Enter',  It  becomes  'set Web',    the  communication  type  turn  into  non WiFi 

model, long press 'Enter' to back to 'Set Zigbee', the communication mode turns back to WiFi model. 

In the level 2 menu, if it is WiFi model, please choose 'WiFi Reset' or 'WiFi Reload' and short press 'Enter' to enter the interface. 

Then long press 'Enter' will reset or reload the inverter WiFi mode. Wait for 25 seconds, operation result will show on display. Press 

'Esc' to return.

In the level 2 menu, if it is non

-

WiFi model, please choose 'Zigbee ID' and short press 'Enter'. The display shows 'Zigbee ID Reset', 

long press 'Enter' to reset the inverter Zigbee ID mode. Wait for 25 seconds, operation result will show on display. Press 'Esc' to 

return. (Notice: The operation only suits the Zigbee mode inverter.)

In the level 2 menu, long press 'Set Modbus' to get 'Set Usual' and an added menu 'ADDR: 247'. Press “Down' to choose 'ADDR: 

247' and short press 'Enter' to enter Modbus address interface. Press 'Up' or “Down' to set the address.

Long press 'ENTER' in the model type interface,

 

there will be set safety interface.

 

Press 'Down' or 'Up' to choose the safety you 

need and then long press 'ENTER',

 

the chosen

 

safety w

ill

 be set.

 

If there is no EXACTLY proper country code, please choose '50Hz 

Grid Default' or '60Hz Grid Default' accordingly

.

In the level 2 menu, choose  'Shadow OFF'( if shadow mode has not been turned on), long press 'Enter', it shows  'Shadow ON' 

indicating shadow mode has been successfully  turned on. (Only available for DT series. )

This function is used for special requirements.

This function is used for special requirements.

This function is used for special requirements.

4.3 Error Code

The error message in below diagram will be displayed on the LCD if a fault occurs. 

4.4 WiFi Reset & WiFi Reload

Choose 'WiFi Reset ' button in level 1,  short press 'enter' to enter level 2 menu 'WiFi Reset '; long press 'Enter' to reset inverter WiFi

 

model;  wait  for  a  while,  operation  result  will  show  on  display,  the  function  can  be  applied  when  inverter  is  unable  to  connect  to 

router or monitor server. 

Choose 'WiFi Reload' button in level 1, short press 'WiFi Reload' to enter level 2 menu 'WiFi Reload'; long press 'enter' button will 

reload the inverter W

i

Fi model to initial setting. Wait for a while, operation result will show on display, the function can be applied 

when inverter is unable to connect to WiFi model. Once WiFi model restore initial setting, WiFi model need be reset again. 

Notice

WiFi

 

model

 

only

.

Error

 

code Error

 

message

01

02

03

07

25

13

14

15

16

17

19

20

21

22

23

30

31

24

32

26

Others

SPI Failure

EEPROM R/W Failure

Fac Failure

Relay Check Failure

DC Injection High

Isolation Failure

Vac  Failure

EFan Fault

PV Over Voltage

Over Temperature

IFan Fault

DC Bus High

Ground I Failure

Utility Loss

Ref 1.5V Failure 

AC HCT Failure

GFCI Failure

Device Failure 

Description

Internal communication failure 

Memory chip failure 

Grid frequency out of range

Relay self-checking failure 

Overhigh DC injection

Ground insulation impedance is too low

Grid voltage out of range

External Fan Failure

Overvoltage at DC input

Overtemperature on the case

Internal Fan Failure

Overhigh BUS voltage

Overhigh ground leakage current

Grid disconnection/fault

1.5V reference voltage failure

Output current sensor failure

Detection circuit of ground leakage current failure

Internal device failure

● 

In the level 2 menu, choose '70% Rated',  at this time, the inverter is 100% output power, long press ‘Enter’, it becomes '100% 

Rated' , then the output power will be limited to 70%. The function is only for using with VDE AR-N 4105 standard or in  France  

areas , and only for service person. Misuse will cause the inverter derating. This menu is not shown for other standards.

5

Operation of Display when commissioning.

When the input voltage reaches inverter turn-on voltage, LCD displays 'waiting'. If the grid is accessible, 'Checking xxx Sec'(The time 

is decided by the grid connection standards from different country) will be shown up in 5sec, During the counting, the inverter is self-

checking, when it shows '00Sec' you can hear the relay triggers, LCD displays 'Normal' afterwards. The instant power output will be 

shown at the right bottom of LCD.

Enter

long

 

press

ESC

Model

:

GW 17K-DT

Ver:1.02

.

02

Set

 

Safety

:

Down

U

p

Set

 

Safety

:

Set

 

Safety

Successful

Enter

long

 

press

This function is used for special requirements.

Enter

long

 

press

ESC

Configure

Safety

Set

 

Safety

:

Down

U

p

Set

 

Safety

:

Set

 

Safety

Successful

Enter

long

 

press

Summary of Contents for GW009K-DT

Page 1: ...D Suzhou 215163 China T 86 512 6239 6771 service goodwe com cn www goodwe com cn GoodWe Australia 74 Tarana Avenue Glenroy VIC 3046 Australia T 61 3 9972 9938 australia goodwe com cn www goodwe de Goo...

Page 2: ...tificates 3 1 Mounting Instruction 3 2 Overview and Packaging 3 3 Inverter Installation 3 4 Electrical Connection 4 1 LED Lights 4 2 User Interface and Controls 4 3 Error Code 4 4 WiFi Reset WiFi Relo...

Page 3: ...should not touch replace any of the components except for the DC AC connectors GOODWE will not bear any consequences caused by unauthorized actions which will lead to potential injury to people and da...

Page 4: ...ts The installation method and mounting location must be suitable for the inverter s weight and dimensions Mount on a solid surface Select a well ventilated place sheltered from direct sun radiation P...

Page 5: ...the impedance of neutral wire and earth wire less than 10 ohm 4 Disconnect the breaker or fuse between the inverter and the utility 5 Connect the inverter to the grid as follows Installation instructi...

Page 6: ...connector There are two types of DC connectors SUNCLIX and MC4 series Please refer to Figure 3 4 2 1 Installation instruction of SUNCLIX connectors please refer to Figure 3 4 2 2 SUNCLIX Series MC4 Se...

Page 7: ...terproof kit to inverter Fasten the screw cap of the cable gland Cables 3 4 5 WiFi Communication The WiFi communication function is only applied to WiFi models the detailed configuration instruction c...

Page 8: ...User Interface and Controls LED lights in Yellow Green Red correspondently refer to POWER RUN FAULT Yellow Light on indicates the inverter is electrified To WiFi model inverters If the Power light fla...

Page 9: ...ar mode display annual power generation for recent 10 years Take day mode for example 72kWh means the maximum power generation of recent 16 days The unit on the left corner sometimes turns to MWh from...

Page 10: ...Long press ENTER in the model type interface there will be set safety interface Press Down or Up to choose the safety you need and then long press ENTER the chosen safety will be set If there is no EX...

Page 11: ...s Vac Failure 1 The PV Inverter will automatically restart within 5 minutes if the grid returns to normal 2 Make sure grid voltage is in conformity with the specification 3 Contact local service offic...

Page 12: ...ng Ambient temperature range Relative humidity Moisture location category Max operating altitude Protection degree Environment category External environment pollution degree Topology Night power consu...

Page 13: ...ble tools and other plug connected equipment Category III applies to fixed equipment downstream of and including the main distribution board Examples are switchgear and other equipment in an industria...

Page 14: ...Fans DT series inverter is fitted with two fans on its left side The fan intakes and handle covers should be cleaned yearly with a vacuum cleaner For more thorough cleaning completely remove the fans...

Page 15: ...I RES_13E 7 2 Checking the DC Switch DC switch does not require any maintenance It is recommended though not compulsory to Check the DC switch regularly Activate the DC switch 10 times in a row once a...

Reviews: