background image

16

Main Burner Flame Check

Flames should be stable, soft and blue (dust may cause
orange tips but they must not be yellow) and extending directly
outward from the burner without curling, floating or lifting off.

Temperature Rise Check

Check the temperature rise through the unit by placing
thermometers in supply and return air registers as close to
the unit as possible. Thermometers must not be able to
sample temperature directly from the unit heat exchangers,
or false readings could be obtained.
1. All registers must be open; all duct dampers must be in

their final (fully or partially open) position and the unit
operated for 15 minutes before taking readings.

2. The temperature rise must be within the range specified

on the rating plate.

NOTE:

 Air temperature rise is the temperature difference between

supply and return air.

With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit is
operated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it
may  be necessary to change the blower speed. A higher
blower speed will lower the temperature rise. A slower blower
speed will increase the temperature rise.

NOTE: 

Blower speed MUST be set to give the correct air tempera-

ture rise through the unit as marked on the rating plate.

External Static Pressure Check

The total external static pressure must be checked on this
unit to determine if the airflow is proper.

Blower Speed Adjustments

WARNING

T

O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE

ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE

BLOWER MOTOR.

Refer to the wiring diagram in the appendix to verify speed tap
settings.
All models are equipped with EEM motors. EEM motors are
constant torque motors with very low power consumption.
This motor is energized by 24V. Adjust the CFM for the unit by
changing the 24V low voltage leads to the speed terminal
block on the motor.

Single Stage Models:

Heating-White Lead

Cooling-Yellow Lead

T1 - Low Speed

T4 - Low Speed

T2 - Medium Speed

T5 - High Speed

T3 - High Speed

Two-Stage Models:

       

Speed

Tap

De fin ition

Lead

C olo r

Spee d

Tap

Def inition

Lead

Color

T1

Low 

Speed Heat

White

T3

Low Speed

Coo l

Purple

T2

High

Speed Heat

Bro wn

T4

High Spee d

Coo l

Yellow

T5

High Spee d

Coo l Hi-Sta tic

HEATI NG

COOLING

NOTE:

 Heating airflow must be adjusted to provide the tempera-

ture rise shown on rating plate.

Limit Check

Check limit control operation after 15 minutes of operation
by blocking the return air grille(s).
1. After several minutes the main burners must go OFF.

Blower will continue to run.

2. Remove air restrictions and main burners will relight

after a cool down period of a few minutes.

Adjust the thermostat setting below room temperature.
1. Main burners must go OFF.
2. Circulating Air Blower will continue to run for 120, 135 or

150 seconds, (single stage models) or 90, 120, 150, or
180 seconds (two-stage models), depending on the
setting.

1

2

3

10

11

12

9

6

23

6

5

8

9

11

12

L2

L2

L2

L2

D1

L

1

L

1

U

N

U

SED

H

EAT

CO

O

L

FS

K2

K1

R8

R10

R3

K4

K3

R31

  

LED

1068-83-400A

C27

D3

R38

D9

D10

R34

R35

R4

R11

R42

D12

R36

D11

D14

C20

Z1

R29

R22

C13

R25

D5

D7

Control Board (Single Stage)

LO COOL

HI COOL

LO HEAT

HI HEAT

U6

U7

U4

U5

U3

K2

K1

P1

ECON

STAGE
DELAY

SPEEDUP

SW1

FAULT
RECALL

BLOWER

OFF DELAY

F1

R

C W1 W2 G Y1 Y2

Control Board (Two-Stage)

NOTE:

 If necessary, adjust fan OFF delay settings to obtain satis-

factory comfort level.

Unit Shutdown

1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the unit.
3. Remove the heat exchanger door on the side of the unit by

removing screws.

4. Move the gas control valve switch to the OFF position. Do

not force.

5. Close manual gas shutoff valve external to the unit.
6. Replace the heat exchanger door on the unit.
7. If cooling and/or air circulation will be  desired, turn ON the

electrical power.

Summary of Contents for Maytag Amana A/GPG14 M Series

Page 1: ...ational Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING PERSONNEL Prior to installation thorough...

Page 2: ...Operation 12 HEATING 12 COOLING 12 FAN ONLY 12 Startup Adjustments and Checks 12 HEATING STARTUP 12 GAS SUPPLY PRESSURE MEASUREMENT 14 GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT 15 COOLING START...

Page 3: ...ODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARN...

Page 4: ...ces from the enclosure for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit m...

Page 5: ...oftopInstallation The unit may be installed directly on wood floors or on Class A Class B or Class C roof covering material To avoid possible personal injury a safe flat surface for service personnel...

Page 6: ...aled damage carrier should be notified as soon as possible preferably within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond...

Page 7: ...2 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressu...

Page 8: ...PIPE OR TUBING LENGTH FEET Table 3 Propane Gas Pipe Sizing GAS PIPING CHECKS CAUTION TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GA...

Page 9: ...NE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE IF THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A CONFINED SPACE A WARNING DEVICE IS REQUIRED DUE TO PROPANE GAS IS HEAVIER THAN AIR AND...

Page 10: ...transformer primary lead as shown on the unit wiring diagram HEAT ANTICIPATORSETTING The heat anticipator is to be set by measuring the load amperage at the R circuit Follow the instructions provided...

Page 11: ...ossible unit operating sound transmission FILTERS CAUTION TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS NE...

Page 12: ...fan are energized Two Stage Models If the thermostat call is for low stage cooling the compressor and outdoor fan are energized at low stage If the thermostat call is for high stage cooling the compr...

Page 13: ...NJURY OR DEATH DUE TO FIRE OR EXPLOSION A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE Rollout Prote...

Page 14: ...re boss plug Install an 1 8 NPT hose barb fitting into the outlet pressure tap b White Rodgers 36G22 or 36G54 valve Back inlet pressure test screw inlet pressure boss out one turn counterclockwise not...

Page 15: ...ase pressure or counterclockwise to decrease pressure Replace regulator cover screw Two Stage Models White Rodgers 36G54 valve Remove regulator cover screw from the low LO outlet pressure regulator ad...

Page 16: ...his motor is energized by 24V Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor Single Stage Models Heating White Lead Cooling Yellow Lead T1 L...

Page 17: ...place adjustment cap Wait a minimum of 10 minutes between adjustments to allow time for the TXV and pressures to stabilize NOTE The expansion valve will not need adjustment for most applications Ensur...

Page 18: ...flashes Pressure Switch Stuck Closed A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring If the control encounters a pressure switch stuck closed the induced draf...

Page 19: ...filters should be discarded and replaced with a new clean filter Dirty permanent filters should be washed with water thoroughly dried and sprayed with a filter adhesive before being reinstalled Filte...

Page 20: ...of burners in retention slots 6 Reconnect electrical power and gas supply CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATI...

Page 21: ...M WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS 0 1 680 61 45 840 103 37 1 035 174 30 1 035 174 1 225 276 0 2 640 72 48 795 109 39 995 184 31 995 184 1 185 275 0 3 605 80 51 750 117 41 960 192 32 960...

Page 22: ...140 338 1 295 456 0 6 450 115 X 895 242 X 1 055 319 58 1 095 349 1 255 456 0 7 395 118 X 845 248 X 1 010 326 X 1 050 350 1 220 465 0 8 345 126 X 785 252 X 960 335 X 1 010 357 1 180 468 CFM WATTS RISE...

Page 23: ...1 305 343 47 1 480 468 1 695 661 0 4 880 181 X 1 220 327 50 1 260 353 49 1 425 479 1 640 679 0 5 825 189 X 1 160 336 53 1 200 359 51 1 380 479 1 595 675 0 6 760 204 X 1 115 342 55 1 150 371 53 1 335 4...

Page 24: ...296 1 655 638 1 825 857 0 5 905 199 64 1 295 351 59 1 135 308 1 610 656 1 790 865 0 6 840 215 X 1 235 359 62 1 085 318 1 560 659 1 735 867 0 7 770 218 X 1 180 371 X 1 040 328 1 520 664 1 700 877 0 8...

Page 25: ...Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only IGNITION CONTROL DIAGNOSTIC INDICATOR CHART SINGLE STAGE MODELS ONLY 0 15 22 45 52 0 29 1...

Page 26: ...tdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Signal Refer to Abnor...

Page 27: ...27 APPENDIX UNIT DIMENSIONS EXHAUST FLUE HOOD CONTROL WIRE ENTRANCE POWER WIRE ENTRANCE HEAT EXCHANGE ACCESS PANEL B B A FLUE EXHAUST BLOWER ACCESS PANEL FLUE EXHAUST HOOD...

Page 28: ...BR BR RD OR BL BL BL RD RD RD RD PU WH OR RD YL YL Y IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 150 120 ECON 135 P1 F1 FUSE 3 AMP MAX P3 G...

Page 29: ...D YELLOW WIRE HEATING SPEED WHITE WIRE T4 LOW SPEED T1 LOW SPEED T5 HIGH SPEED T2 MED SPEED T3 HIGH SPEED 5 USE COOPER CONDUCTORS ONLY 6 L1 AND L2 ON IIC CONTROL IS 24V INPUT ALS AUXILLARY LIMIT SWITC...

Page 30: ...BR RD OR BL BL BL BL RD RD RD RD PU WH OR RD YL YL Y Y2 IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 1 5 0 1 2 0 ECON 1 3 5 P1 F1 FUSE 3 AM...

Page 31: ...ANDTYPEOF INS ULATIONAS O RIGINAL USE COPPERCONDU CTORONLY 2 FOR208 VOLT TRA NSFORMEROPERATION MOVE BLACK WIRE FROMTER MINAL 3 TOTERM INAL 2 O NTRA NSFORMER 3 CRANKC ASE HEATERNOT SUPPLIEDON ALL U NIT...

Page 32: ...CER L2 BK YL RD GR SEE NOTE 3 EM 208 PU YL PU BK N G L T5 T4 T3 T2 T1 240 3 TR 2 RD 24V C 1 YL BL 208 230 1 60 POWER SUPPLY GND C PU PU RD BK BR PU BK R S COMP C T2 T1 CC L2 L1 ALS CM LPS HPS PARK BK...

Page 33: ...LS TR EM VM H F RCCF C L2 T2 208 230 1 60 CM L1 R T1 S COMP C L1 SUPPLY VOLTAGE P1 INTEGRATED IGNITION CONTROL CC CC COM HLI SEE NOTE 2 INTERGRATED IGNITION CONTROL F Y1 R C Y2 W2 W1 TO MICRO TO MICRO...

Page 34: ...Ton 2 1 2 Ton 3 Ton 3 1 2 4 Ton 5 Ton Min Filter Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 2 20 x 25 x 1 MINIMUM CLEARANCES NOTE Roof overhang should be no more than 36 3 MIN 12 MIN...

Page 35: ...ED SERVICER ONLY Your package unit should be inspected by a qualified installer or service agency at least twice every year This check should be performed before the heating and cooling seasons begin...

Page 36: ...th refrigerant piping or sharp metal edges Check all electrical connections and terminals Tighten as needed Verify that the crankcase heaters have been energized for 24 hours Verify the scroll compres...

Page 37: ...Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heatin...

Page 38: ...38 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 39: ...39 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 40: ...San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com 2014 2016 Goodman Manufacturing Company L P is a registered trademark of Maytag Corporation or its related companies and...

Reviews: