Goodman GPG13 Installation & Operating Instructions Manual Download Page 11

11

V E N T I N G

NOTE:  Venting is self-contained.  Do not modify or block.

F

LUE

 H

OOD

 I

NSTALLATION

Install the flue hood and bug screen prior to operation of the
unit.
To install the flue hood cover and bug screen:
1. Remove the flue hood and bug screen from inside the

heat exchanger compartment.

2. Slide the bug screen over the flanges of the flue hood and

attach the flue hood and screen to the unit with the sheet
metal screws provided.

Flue Hood and Bug Screen Installation

CONDENSATE DRAIN

C

ONDENSATE

 D

RAIN

 C

ONNECTION

A 3/4” NPT drain connection is supplied for condensate piping.  An
external trap must be installed for proper condensate drainage.

DRAIN
CONNECTION

UNIT

2" MINIMUM

FLEXIBLE
TUBING-HOSE
OR PIPE

3" MINIMUM

A POSITIVE LIQUID
SEAL IS REQUIRED

Drain Connection

NORMAL SEQUENCES OF OPERATION

H

EATING

This unit is equipped with an ignition control that automatically
lights the main burner.  DO NOT attempt to light the main
burners by any other method.
1. Thermostat calls for heat. The induced draft blower

energizes for a 15-second pre-purge.

2. The spark igniter and gas valve energizes for 7 seconds.

NOTE:  

The igniter produces a very intense electrical spark

that ignites the gas.

3. The 30-second HEAT FAN ON delay time begins.

*PG13(48,60)***1A ONLY

: Heat on delay begins when

thermostat calls for heat. ECM motor is energized
approximately 45 seconds later. NOTE: ECM motor may
operate at approximately 100 CFM or less during the 45
second on delay period. ECM motor will energize at heating
speed after the 45 second delay regardless of the status
of the main burner flame.

4. The unit delivers heat to the conditioned space until the

thermostat is satisfied.

5. The gas valve deenergizes.  The induced draft blower

continues operation for a 29-second post-purge.

6. Ignition control begins timing the HEAT FAN OFF delay.

There is an adjustable HEAT FAN OFF delay of
approximately 120/135/150 seconds (factory set at 150).
After the HEAT FAN OFF delay time has elapsed, the blower
will deenergize.  This allows any additional heat in the
heat exchanger to be transferred to the conditioned space.

*PG13(48,60)***1A ONLY

: HEAT FAN OFF delay is fixed at

180 seconds. Airflow level is 50% of nominal heating
airflow.

C

OOLING

1. Thermostat calls for cooling. The compressor and outdoor

fan are energized.

2. Approximately seven seconds later, the indoor fan starts.
3. The unit will deliver cooling to the conditioned space until

the thermostat is satisfied.

4. The compressor and outdoor fan will be deenergized when

the thermostat opens.

5. The indoor fan continues to run for approximately 60

seconds after the thermostat is satisfied.  This allows
additional cooling from the indoor coil to be transferred to
the conditioned space. Then, the indoor fan stops.

*PG1348***1A ONLY:

1. Thermostat calls for cooling. Outdoor fan and compressor

are energized. ECM motor is energized almost immediately
for 30 seconds at 50% of the nominal  airflow.  Airflow then
increases to nominal airflow.

2. The unit will deliver cooling to the conditioned space until

thermostat is statisfied.

3. The outdoor fan and compressor will be de-energized when

thermostat opens.

4. ECM motor continues to operate for approximately 60

seconds at 50% of nominal airflow after thermostat opens.

*PG1360***1A ONLY:

1. Thermostat calls for low stage cooling. Outdoor fan and

low stage compressor are energized. ECM motor is
energized almost immediately for 30 seconds at 50% of
the nominal low stage airflow.  Airflow then increases to
nominal low stage airflow.
If thermostat calls for high stage cooling, outdoor fan and
low and high stage compressor is energized. ECM motor is
energized almost immediately for 30 seconds at 50% of
the nominal high stage airflow.  Airflow then increases to
nominal high stage airflow.

2. The unit will deliver cooling to the conditioned space until

thermostat is satisfied.

3. The outdoor fan and low stage compressor (or low and high

stage compressor) will be de-energized when thermostat
opens.

4. ECM motor continues to operate for approximately 60

seconds at 50% of nominal low stage airflow (or high
stage airflow if thermostat call was for high stage cooling)
after thermostat opens.

Summary of Contents for GPG13

Page 1: ...Requirements Embodied in The American National Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING...

Page 2: ...11 HEATING 11 COOLING 11 FAN ONLY 12 Startup Adjustments and Checks 12 HEATING STARTUP 12 COOLING STARTUP 15 Troubleshooting 15 IGNITION CONTROL ERROR CODES 15 ABNORMAL OPERATION HEATING 16 ABNORMAL O...

Page 3: ...L TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE S...

Page 4: ...the outdoor air i e combustion air for the unit will be frequently contaminated by compounds containing chlorine or fluorine Common sources of such compounds include swimming pool chemicals and chlor...

Page 5: ...TION ELECTRIC SHOCK OR CARBON MONOXIDE THIS UNIT MUST BE PROPERLY INSTALLED REPAIRED OPERATED AND MAINTAINED This unit is approved for outdoor installation ONLY To assure that your unit operates safel...

Page 6: ...TION AND OR EQUIPMENT DAMAGE HIGH ALTITUDE KITS ARE FOR U S INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE IN CANADA The rating plate is stamped with the model number type of gas and gas input rating...

Page 7: ...E A MATCH OR OPEN FLAME TO TEST FOR LEAKS NEVER EXCEED SPECIFIED PRESSURES FOR TESTING HIGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE THI...

Page 8: ...acturers and propane gas suppliers Since propane gas will quickly dissolve white lead or most standard commercial compounds special pipe dope must be used Shellac base compounds resistant to the actio...

Page 9: ...SI Z21 20 AUTOMATIC IGNITION SYSTEM L2 L2 L2 L2 ECON 120 135 150 SPEED UP LOW VOLTAGE CONNECTOR Y Y2 Low Voltage Wiring PG1360 1A Only Refer to the unit wiring diagram for electrical connections When...

Page 10: ...onal Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Systems Pamphlets No 90A and 90B The supply duct from the unit through a wall may be installed...

Page 11: ...lower will deenergize This allows any additional heat in the heat exchanger to be transferred to the conditioned space PG13 48 60 1A ONLY HEAT FAN OFF delay is fixed at 180 seconds Airflow level is 50...

Page 12: ...lout protection device is located on the burner bracket The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control WARNING TO AV...

Page 13: ...gas being delivered to the unit 3 INPUT GAS HTG VALUE x 3600 SEC PER CUBIC FOOT Example Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step...

Page 14: ...utward from the burner without curling floating or lifting off Temperature Rise Check Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to...

Page 15: ...does not operate Compressor Protection Devices The compressor includes components which are designed to protect the compressor against abnormal operating conditions WARNING TO PREVENT PERSONAL INJURY...

Page 16: ...and carefully clean with steel wool Check wiring Check wiring for opens shorts and miswiring Important If you have to frequently reset your gas electric package unit it means that a problem exists th...

Page 17: ...bris CONDENSER EVAPORATOR AND INDUCED DRAFT MOTORS Bearings on the air circulating blower motor condenser motor and the combustion fan motor are permanently lubricated No additional oiling is required...

Page 18: ...rical power and gas supply CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION CAUTION ALWAYS VERIFY PROPER OPERATION AFTER...

Page 19: ...Seconds 0 7 30 0 60 Circulator Blower Outdoor Fan and Compressor Thermostat ON OFF ON OFF ON OFF Legend PG10 12 24 60 PG1324 42 PG1348 60 100 50 Light Signal Refer to Abnormal Heating or Cooling Opera...

Page 20: ...SUPPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PAN...

Page 21: ...H OPTIONAL CONNECTED AT L1 L2 NOTE 4 B BL Y R FS R O R H C F Y BR CAP1 BL B PU 4 SPEED MOTOR ALS Y Y PS PU W G G W R BL Y Y PU R C Y Y2 Y1 Y BL 6 5 2 3 G 4 1 Y PU PL RS MV GAS VALVE MV GV PU W R BL GV...

Page 22: ...ER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH B4312003 REV B Wiring is subject to change Always...

Page 23: ...TC OT1 O T2 BR CM PU B Y COMP B B S C R CH OPTIONAL BL C LS R R BL BL PU BL R PU R R G G Y W PU Y1 Y 208 230 1 60 POWER SUPPLY B NOTE 2 B B BL BL BL BL B PU L1 B R CC L2 T1 T2 R B Y GRD R Y R Y2 CH O...

Page 24: ...ENSER MOTOR CC CONTACTOR CH CRANKCASE HEATER FS FLAME SENSOR COMPONENT LEGEND CAP CAPACITOR L2 L2 MARKED TERMINAL LINE VOLTAGE LOW VOLTAGE UNMARKED TERMINAL WIRING WIRE SPLICE Y Y C Y2 Y2 1 REPLACEMEN...

Page 25: ...PU B Y COMP B B S C R CH OPTIONAL BL C LS R R BL BL PU BL R PU R R G G Y Y Y2 W PU Y1 Y 208 230 1 60 POWER SUPPLY B NOTE 2 B B BL BL BL BL B PU L1 B R CC L2 T1 T2 R B Y GRD R Y1 PU PU BL BL BL PU Y Y...

Page 26: ...NSER MOTOR CC CONTACTOR CH CRANKCASE HEATER FS FLAME SENSOR COMPONENT LEGEND CAP CAPACITOR L2 L2 MARKED TERMINAL LINE VOLTAGE LOW VOLTAGE UNMARKED TERMINAL WIRING WIRE SPLICE SOL SOLENOID 2 STAGE nd Y...

Page 27: ...U PU PU BL BR 1 4 3 2 5 6 F C 240 24V 1 C 2 208 3 NOTE 4 GAS VALVE NOTE 5 ALT HONEYWELL W R GAS VALVE PLF Y1 Y2 Y C R W G CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 NOTE 4 NOTE 2 208 230 3 60 CH OPTIONAL P...

Page 28: ...ALS LS 8 6 3 RS PLF 6 5 2 3 C 1 4 GV FALSE FLAME SENSED OUTPUT DELAY OPEN LIMIT SWITCH COMPRESSOR ANTI CYCLE TIMER MAIN LIMIT OPEN STICKING GAS VALVE BAD SWITCH 3 MIN COMP WITHOUT INDUCER ON PRESSURE...

Page 29: ...ECON 120 150 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 208 230 3 60 CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 Y1 Y2 CH OPTIONAL NOTE 5 PLF T1 T2 T3 T4 T5 NOTE 4 NO TE2 SEE NOTE 6...

Page 30: ...CITOR WITH ECONOMIZER OPTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00087 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 3 TR NOTE NOTE 7 NO...

Page 31: ...IONAL 460 3 60 SEE NOTE 6 BK BK PU RD BK YL RD GND RD BK BK RD CH OPTIONAL CONNECTED AT L1 L2 NOTE 2 SEE NOTE 3 SEE NOTE 5 TO THERMOSTAT VM GAS VALVE IGN FS MV ALT HONEYWELL GAS VALVE MV W R GV 5 4 1...

Page 32: ...TYPE OF INSULATION AS ORIGINAL USE COPPER CONDUCTOR ONLY 0140G00088 4 ACCESSORY ECONOMIZER PLUG ON SELECT MODELS ADJACENT SPEED REPLACE THE BLACK MOTOR LEAD AT IBR 3 WITH RED 3 460V UNITS ARE SINGLE...

Page 33: ...WH WH RD BK PU BL W R GAS VALVE GAS VALVE ALT HONEYWELL TO THERMOSTAT R C G Y W COOL P1 ECON 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 460 3 60 CH OPTIONAL CONNECTED AT L1 L...

Page 34: ...PTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00089 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 2 TR NOTE NOTE 6 NOTE 6 4 SEE NOTE 7 EM R...

Page 35: ...135 ECON 120 150 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 208 230 1 60 CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 Y1 Y2 CH OPTIONAL NOTE 5 PLF T1 T2 T3 T4 T5 NOTE 4 N OTE2 SEE N...

Page 36: ...ZER OPTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00267 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 3 TR NOTE NOTE 7 NOTE 7 5 NOTE 2 EM R...

Page 37: ...Ton 2 1 2 Ton 3 Ton 3 1 2 4 Ton 5 Ton Min Filter Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 2 20 x 25 x 1 MINIMUM CLEARANCES NOTE Roof overhang should be no more than 36 3 MIN 12 MIN...

Page 38: ...38 THIS PAGE LEFT BLANK INTENTIONALLY...

Page 39: ...39 THIS PAGE LEFT BLANK INTENTIONALLY...

Page 40: ...significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it...

Reviews: