background image

8

D’installation de ce générateur de chaleur à des altitudes 

supérieures à 2000 pi (610 m) doit être effectuée conformé

-

ment auxinstructions accompagnant la trousse de conver-

sion pour haute altitude fournie avec cet appareil.

IMPORTANT NOTE:

 The gas/electric units naturally derate 

with altitude. Do not attempt to increase the firing rate by 

changing orifices or increasing the manifold pressure. This 

can cause poor combustion and equipment failure. At all alti-

tudes, the manifold pressure must be within 0.3 inches W.C. 

of that listed on the nameplate for the fuel used. At all alti-

tudes and with either fuel, the air temperature rise must be 

within the range listed on the unit nameplate. Contact your 

distributor or refer to the specification sheet for your model 

for listing of approved high altitude conversion kit(s). Refer 

to the Installation Manual provided with the high altitude kit 

for altitude adjustments.

NOTE:

 No changes are required up to 2,000 feet. Use the 

appropriate high altitude kit above 2,000 feet.

Piping

IMPORTANT NOTE:

 To avoid possible unsatisfactory opera-

tion or equipment damage due to under firing of equipment, 

do not undersize the natural/propane gas piping from the 

meter/tank to the unit. When sizing a trunk line, include all 

appliances on that line that could be operated simultaneously.

The rating plate is stamped with the model number, type of 

gas and gas input rating. Make sure the unit is equipped to 

operate on the type of gas available. The gas line installa-

tion must comply with local codes, or in the absence of local 

codes, with the latest edition of the National Fuel Gas Code 

NFPA 54/ANSI Z223.1.

 

Natural Gas Connection

Refer to the Proper Piping Practice drawing for the general 

layout at the unit. The following rules apply: 

1. 

Use black iron pipe and fittings for the supply piping. 

The use of a flex connector and/or copper piping is per

-

mitted  as long as it is in agreement with local codes.

2.  Use pipe joint compound on male threads only. Pipe 

joint compound must be resistant to the action of the 

fuel used. 

3.  Use ground joint unions. 

4.  Install a drip leg to trap dirt and moisture before it can 

enter the gas valve. The drip leg must be a minimum of 

three inches long.

5.  Use two pipe wrenches when making connection to the 

gas valve to keep it from turning.

6. 

Install a manual shut-off valve in a convenient location 

(within six feet of unit) between the meter and the unit.

7.  Tighten all joints securely.

8.  The unit must be connected to the building piping by 

one of the following methods:

• 

Rigid metallic pipe and fittings

• 

Semirigid  metallic  tubing  and  metallic  fittings  (Alumi

-

num alloy tubing must not be used in exterior locations)

•  Listed gas appliance connectors used in accordance 

with the terms of their listing that are completely in the 

same room as the equipment

•  In the prior two methods above the connector or tubing 

must be protected from physical and thermal damage. 

Aluminum alloy tubing and connectors must be coated 

to protect against external corrosion when in contact 

with masonry, plaster or insulation or are subject to re-

peated wettings by liquids (water - not rain water, de

-

tergents or sewage).

NOTE:

 The unit gas supply entrance is factory sealed with 

plugs. Keep plugs in place until gas supply is ready to be 

installed. Once ready, replace the plugs with the supplied 

grommets and install gas supply line.

Length of 

Pipe in Feet

1/2

3/4

1

1  1/4

1  1/2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based 

on 0.60 Specific Gravity Gas)

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Nominal Black  Pipe Size (inches)

BTUH Furnace Input

Heating Value of Gas (BTU/Cubic Foot)

CFH =

Proper Piping Practice

Gas Piping Checks 

There will be air in the gas supply line after testing for leaks 

on a new installation. Therefore, the air must be bled from 

the line by loosening the ground joint union until pure gas is 

expelled. Tighten union and wait for five minutes until all gas 

has been dissipated in the air. Be certain there is no open 

flame in the vicinity during air bleeding procedure. The unit 

is placed in operation by closing the main electrical discon-

nect switch for the unit.

Summary of Contents for GPG 16 M Series

Page 1: ...e and air flow may reduce energy efficiency and shorten equipment life ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MAN...

Page 2: ...Primary Limit 18 Flame Detected with Gas Valve Closed 18 Low Flame Signal 19 Abnormal Operation Cooling 19 Short Cycle Compressor Delay 19 High Pressure Switch Loss of Charge Switch 19 MAINTENANCE 19...

Page 3: ...RNINGS EXACTLY COULD RESULT IN SERIOUS INJURY DEATH OR PROPERTY DAMAGE NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS...

Page 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Page 5: ...dition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and National Standard of Canada CAN CSA B149 Installation Codes The heating and cooling capacities of the unit should be greater than or equal...

Page 6: ...e for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstruct...

Page 7: ...at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Con...

Page 8: ...drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Use two pipe wrenches when making connection to the gas valve to keep it from...

Page 9: ...peration Because of the danger of ex plosion or fire never use a match or open flame to test for leaks Never exceed specified pressure for testing Higher pressure may damage gas valve and cause overfi...

Page 10: ...nd two stages of me chanical cooling Units which will have economizers may use thermostats with two or three stages of cooling All units can use single stage or multi stage thermostats Refer to figure...

Page 11: ...esidential or Manual Q Commercial All ductwork exposed to the outdoors must include a weather proof barrier and adequate insulation A duct system should be installed in accordance with Stan dards of t...

Page 12: ...elay time expires the control will transition from low stage to high stage 6 The 30 second HEAT FAN ON delay time begins after the main burners light 7 The unit delivers heat to the conditioned space...

Page 13: ...ated temperatures at the control are normally caused by blower failure The reason for the opening should be determined and repaired prior to resetting If the power to the unit is interrupted during th...

Page 14: ...ternately remove pre drilled cap from drip leg Reinstall original cap sealing with pipe thread compound 7 Turn on electrical power and gas supply to the system 8 Turn on system power and energize valv...

Page 15: ...e Rise Check Check the temperature rise through the unit by placing ther mometers in supply and return air registers as close to the unit as possible Thermometers must not be able to sample temperatur...

Page 16: ...lower will continue to run for 90 120 150 or 180 seconds depending on the setting NOTE If necessary adjust fan OFF delay settings to obtain satisfactory comfort level Control Board Top Unit Shutdown 1...

Page 17: ...3 Record the gauge pressure and the temperature of the line 4 The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling Subcooling Formula Sat...

Page 18: ...d heat exchanger a failed induced draft blower or insufficient combustion air The rollout protection device is a manual reset limit located on the burner bracket The cause of the flame rollout must be...

Page 19: ...ecked at least once a year before the heating season begins to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combus tion air and a...

Page 20: ...r lifting off At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit w...

Page 21: ...Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansio...

Page 22: ...Flashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Sig...

Page 23: ...e Height W D A B GPG1624 M41 47 51 32 34 1 2 Medium GPG1630 M41 47 51 32 34 1 2 Medium GPG1636 M41 47 51 40 42 1 2 Large GPG1642 M41 47 51 40 42 1 2 Large GPG1648 M41 47 51 40 42 1 2 Large GPG1660 M41...

Page 24: ...ECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH C CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED CHE...

Page 25: ...nufacturer s instal lation instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d instal lation du fabricant MINIMUM CLEARANCES UNI...

Page 26: ...SPEED T5 COOLING SPEED GPG1642100M41 Rise Range 35 65 E S P T1 LOW STAGE HEATING SPEED T2 HIGH STAGE HEATING SPEED T3 LOW STAGE COOLING SPEED T4 HIGH STAGE COOLING SPEED T5 COOLING SPEED GPG1648100M41...

Page 27: ...available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners Annual Inspection Qualified Servicer Only Your package unit should be ins...

Page 28: ...ignment per installa on instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure i s no n contact with refrigerant piping or sharp metal edges Check...

Page 29: ...or Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Sta c Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Ci...

Page 30: ...30 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 31: ...31 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 32: ...or Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registration You can also scan the QR code on the right for the product brand you purchased t...

Reviews: