background image

9

19. Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes

or lines are not rubbing against each other or sheet metal surfaces or edges. If so, correct the trouble.

20. Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.
21. Be sure the Owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc.
The foregoing “Start-up Procedure and Check List” is recommended to serve as an indication that the unit will operate
normally.

COMPONENTS
1. Contactor

 - This control is activated (closed) by the room thermostat for both heating and cooling. The contactor has

a 24V coil and supplies power to the compressor and outdoor fan motor.

2. Crankcase Heater – 

This item is “ON” whenever power

 

is supplied to the unit and the crankcase heater thermostat is

closed. Crankcase heater thermostat closes at 67° and opens at 85°. It warms the compressor crankcase thereby

preventing liquid migration and subsequent compressor damage. The insert type heater is self regulating.  It is

connected electrically to the contactor L1 and L2 terminals.

3. Condenser Motor - 

This item is activated by the contactor during heating and cooling, except during defrost and

emergency heat operation.

4. Compressor - 

This item is activated by the contactor for heating and cooling, except during emergency heat. It is

protected by

 

an internal overload.

5. Contactor Relay -

 This control is activated by the thermostat (24V coil) and supplies power to the contactor.

6. Defrost Control

 - The Defrost control provides time/temperature initiation and termination of the defrost cycle.

When a Defrost cycle is initiated, the defrost control shifts the reversing valve to “cooling” mode, stops the outdoor
fan and brings on supplemental heat. Normally, a Defrost cycle will take only 2-3 minutes unless system is low on
charge or outdoor conditions are severe. (Windy and cold.)  The defrost control also provides for a 3 minute off cycle
compressor delay.

7. Outdoor Thermostat -

 These optional controls are used to prevent full electric heater operation at varying outdoor

ambient (0° F-to 45° F). They are normally open above their set points and closed below to permit staging of indoor

supplement heater operation.  If the outdoor ambient temperature is below 0° F (-18° C) with 50% or higher RH, an

outdoor thermostat (OT)  must be installed and set at (0°) on the dial.  Failure to comply with this requirement may

result in damage to the product which may not be covered by the manufacturer’s warranty.

8. Reversing Valve Coil -

 This coil is activated by the thermostat, in the cooling mode and during defrost. It positions

the reversing valve pilot valve for cooling operation.

9. Indoor Blower Motor

Units with EEM Motors 

The EEM model indoor blower motor is activated by the room thermostat by COOLING/

HEATING or FAN ON position. The motor is energized by a 24 volt control signal (from thermostat Y, G or W) for EEM

motors. EEM motors are constant torque motors with very low power consumption.
(See 

Air Flow Measurement and Adjustment

 for speed adjustment instructions).

10. Blower Interlock Relay -

 This relay is used to energize the blower during the electric heat operation. Some room

thermostats do not energize the motor during electric heat. This relay insures blower operation when the room

thermostat energizes heat. This relay has a 240 volt coil and an 8 amp contact relay. This relay is energized by the
electric heat kit sequencer.

EXPLANATION AND GUIDANCE (HEAT PUMP)

The heat pump is a relatively simple device. It operates exactly as a Summer Air Conditioner unit when it is on the cooling
cycle. Therefore, all the charts and data for service that apply to summer air conditioning apply to the heat pump when it
is on the cooling cycle, and most apply on the heating cycle except that “condenser” becomes “evaporator”, “evaporator”
becomes “condenser”, “cooling” becomes “heating”.
When the heat pump is on the heating cycle, it is necessary to redirect the refrigerant flow through the refrigerant circuit
external to the compressor. This is accomplished with a reversing valve. Thus, the hot discharge vapor from the compressor
is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to
liquid.  It then goes through the expansion device to the outdoor coil (condenser on the cooling cycle) where the liquid is
evaporated, and the vapor goes to the compressor.
When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to
the low pressure (high pressure) reverse positions in the reversing valve.
Figure 7 shows a schematic of a heat pump on the cooling cycle and the heating cycle.  In addition to a reversing valve, a
heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor
coil. It is also provided with a defrost control system.
The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling
cycle.  The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow.

Summary of Contents for GPC1524H41

Page 1: ...signed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components However proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency Installation of this product should follow the manufacturer s refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energ...

Page 2: ...nd outside of home Note any potential obstacles or prob lems that might be encountered as noted in this manual Choose a more suitable location if necessary IMPORTANT NOTE If a crankcase heater is used the unit should be energized 24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the com pressor Compressor damage may occur if this step is not followed Before u...

Page 3: ...EPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER WARNING THIS UNIT MUST NOT BE USED AS A CONSTRUCTION HEATER DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES CODES AND REGULATIONS General The PC ...

Page 4: ...s and regulations MAJOR COMPONENTS General The unit includes a hermetically sealed refrigerating system consisting of a compressor condenser coil evaporator coil with flowrator an indoor blower a condenser fan and all necessary internal electrical wiring The heat pump also includes a reversing valve solenoid defrost thermostat and control and loss of charge protection The system is factory evacuat...

Page 5: ...ons as indicated Ducts should run as directly as possible to supply and return outlets Use of non flammable weatherproof flexible connectors on both supply and return connections at the unit to reduce noise transmission is recommended It is preferable to install the unit on the roof of the structure if the registers or diffusers are located in the wall or ceiling A slab installation is recommended...

Page 6: ...e consulted to determine the availability of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch circuit fused disconnect near the unit in accordance with the N E C or local codes Wire sizes and overcurrent protection should be determined from the unit namepla...

Page 7: ...the unit 2 Wire size based on 60 C rated wire insulation and 30 C Ambient Temperature 86 F 3 For more than 3 conductors in a raceway or cable see the N E C for derating the ampacity of each conductor OPERATION Start Up Procedure and Checklist Begin with power turned off at all disconnects 1 Turn thermostat system switch to Cool and fan switch to Auto and turn temperature setting as high as it will...

Page 8: ...heat if installed should now come on Make sure it operates properly NOTE If outdoor thermostats are installed the outdoor ambient must be below the set point of these thermostats for the heaters to operate It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild 14 For thermostats with emergency heat switch return to step 11 The emergency heat switch is ...

Page 9: ...age to the product which may not be covered by the manufacturer s warranty 8 Reversing Valve Coil This coil is activated by the thermostat in the cooling mode and during defrost It positions the reversing valve pilot valve for cooling operation 9 Indoor Blower Motor Units with EEM Motors The EEM model indoor blower motor is activated by the room thermostat by COOLING HEATING or FAN ON position The...

Page 10: ... should close To verify this check for 24 volts between DFT and C on board If the temperature at the thermostat is less than 28 F and the thermostat is open replace the unit s defrost thermostat as it is defective 7 When the unit s defrost thermostat has closed short the test pins on the defrost board until the reversing valve shifts indicating defrost This should take up to 22 seconds depending o...

Page 11: ...meter on liquid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Systems with TXV application should have a subcooling and superheat within the range listed on the chart a If subcooling and superheat are low adjust TXV then check subcooling b If subcooling is low and superheat is high add charge to raise subcoo...

Page 12: ... Heat Pump should operate for many years without excessive service calls if the unit is installed properly However it is recommended that the homeowner inspect the unit before a seasonal start up The coils should be free of debris so adequate airflow is achieved The return and supply registers should be free of any obstructions The filters should be cleaned or replaced These few steps will help to...

Page 13: ...e due to 1 Solenoid not energized In order to determine if the solenoid is energized touch the nut that holds the solenoid cover in place with a screwdriver If the nut magnetically holds the screwdriver the solenoid is energized and the unit is in the cooling cycle 2 No voltage at unit s solenoid Check unit voltage If no voltage check wiring circuit 3 Valve will not shift a Undercharged check for ...

Page 14: ... 775 720 666 Watts 97 109 122 134 147 159 172 184 CFM 1123 1068 1014 959 905 850 796 741 Watts 123 136 148 161 173 186 198 211 CFM 1462 1409 1357 1305 1252 1200 1147 1095 Watts 241 253 266 278 291 303 315 328 CFM 1005 961 918 874 831 787 744 700 Watts 91 102 114 125 137 149 160 172 CFM 1110 1067 1023 980 936 893 849 806 Watts 120 132 144 155 167 178 190 202 CFM 1462 1409 1357 1305 1252 1200 1147 1...

Page 15: ...39 150 161 175 186 190 207 CFM 1712 1655 1587 1541 1486 1444 1393 1340 Watts 337 348 358 375 385 405 414 416 CFM 2002 1935 1885 1827 1767 1732 1669 1618 Watts 498 521 516 534 551 567 571 574 CFM 1337 1297 1218 1155 1118 1088 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1694 1646 1598 1549 1501 1453 1405 1357 Watts 296 303 311 319 327 334 342 350 CFM 1919 1870 1822 1774 1726 1678 1629 1581 Wa...

Page 16: ...essor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage must be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a a Iced evaporator coil a Defective o...

Page 17: ... evaporator coil The safest way to clean the evaporator coil is to sim ply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils An alternate cleaning method is to use one of the products listed in the technical publication TP 109 shipped in the literature bag with the unit to clean the coils The...

Page 18: ...rance around the unit for safety service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place Check gas piping for leaks Verify gas pressure to the unit is within the range specified on the serial plate Check to ensure that all fans pulleys and wheels are secure Check for proper belt tension...

Page 19: ...it 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heating Supply Air Temperature PRESSURES Gas Inlet Pressure Gas Manifold Pressure Suction Circuit 1 Suction Circuit 2 Discharge Circuit 2 Superheat Orif...

Page 20: ...feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights For Product Registration please regi...

Reviews: