background image

9

When the solenoid valve coil is operated either from heating
to cooling or vice versa, the piston in the reversing valve to
the low pressure (high pressure) reverse positions in the
reversing valve.

The following figures show a schematic of a heat pump on
the cooling cycle and the heating cycle.  In addition to a
reversing valve, a heat pump is equipped with an expansion
device and check valve for the indoor coil, and similar
equipment for the outdoor coil. It is also provided with a
defrost control system.

The expansion devices are flowrator distributors and perform
the same function on the heating cycle as on the cooling
cycle.  The flowrator distributors also act as check valves
to allow for the reverse of refrigerant flow.

When the heat pump is on the heating cycle, the outdoor
coil is functioning as an evaporator.  The temperature of the
refrigerant in the outdoor coil must be below the temperature
of the outdoor air in order to extract heat from the air.  Thus,
the greater the difference in the outdoor temperature and
the outdoor coil temperature, the greater the heating capacity
of the heat pump.  This phenomenon is a characteristic of a
heat pump.  It is a good practice to provide supplementary
heat for all heat pump installations in areas where the
temperature drops below 45° F.  It is also a good practice to
provide sufficient supplementary heat to handle the entire
heating requirement should there be a component failure of
the heat pump, such as a compressor, or refrigerant leak,
etc.

Since the temperature of the liquid refrigerant in the outdoor
coil on the heating cycle is generally below freezing point,
frost forms on the surfaces of the outdoor coil under certain
weather conditions of  temperature and relative humidity.
Therefore, it is necessary to reverse the flow of the refrigerant
to provide hot gas in the outdoor coil to melt the frost
accumulation. This is accomplished by reversing the heat
pump to the cooling cycle. At the same time, the outdoor
fan stops to hasten the temperature rise of the outdoor coil
and lessen the time required for defrosting. The indoor blower
continues to run and the supplementary heaters are
energized.

DEFROST CONTROL

During operation the power to the circuit board is controlled
by a temperature sensor, which is clamped to a feeder tube
entering the outdoor coil. Defrost timing periods of 30,60
and 90 minutes may be selected by connecting the circuit
board jumper to 30, 60 and 90 respectively. Accumulation
of time for the timing period selected starts when the sensor
closes (approximately 31° F), and when the wall thermostat
calls for heat.  At the end of the timing period, the unit’s
defrost cycle will be initiated provided the sensor remains
closed. When the sensor opens (approximately 75° F), the
defrost cycle is terminated and the timing period is reset. If
the defrost cycle is not terminated due to the sensor
temperature, a ten minute override interrupts the unit’s
defrost period.

C

Y

W2

R

R DFT

TEST

DF1

DF2

JUMPER WIRE

90
60
30

A

FIGURE 7

SUGGESTED FIELD TESTING/TROUBLE SHOOTING

1.

Run unit in the heating mode (room thermostat calling for
heat).

2.

Check unit for proper charge. 

Note: Bands of frost on the

condenser coil indicate low refrigerant charge.

3.

Shut off power to unit.

4.

Disconnect outdoor fan by removing the purple lead from
“DF2” on defrost control.

5.

Restart unit and allow frost to accumulate.

6.

After a few minutes of operation, the unit’s defrost
thermostat should close. To verify this, check for 24 volts
between “DFT” and  “C” on board. If the temperature at the
thermostat is less than 28° F and the thermostat is open,
replace the unit’s defrost thermostat, as it is defective.

7.

When the unit’s defrost thermostat has closed, short the
test pins on the defrost board until the reversing valve shifts,
indicating defrost.  This should take up to 21 seconds
depending on what timing period the control is set on.
After defrost initiation, the short must instantly be removed
or the unit’s defrost period will only last 2.3 seconds.

8.

After the unit’s defrost thermostat has terminated, check
the defrost thermostat for 24 volts between “DFT” and “C”.
The reading should indicate 0 volts (open sensor).

9.

Shut off power to unit.

10. Replace outdoor fan motor lead to terminal “DF2” on defrost

board and turn on power.

AIR FLOW MEASUREMENT AND ADJUSTMENT

After reviewing section on DUCTING, proceed with airflow
measurements and adjustments.  Unit’s blower curves (in
Specification Sheets) are based on external static pressure
(ESP, in. of W.C.).  The duct openings on the unit are
considered internal static pressure, so as long as ESP is
maintained, the unit will deliver the proper air up to the
maximum static pressure listed for the CFM required by
the application (i.e. home, building, etc.)

In general 400 CFM per ton of cooling capacity is a rule of
thumb.  Some applications depending on the sensible and
latent capacity requirements may need only 350 CFM or up
to 425 CFM per ton.  Check condition space load
requirements (from load calculations) and equipment
expanded ratings data to match CFM and capacity.

After unit is set and ducted, verify ESP with a 1" inclined
manometer with pitot tubes or a Magnahelic gauge and
confirm CFM to blower curves in the specification sheets.
All units have three speed blower motors. If low speed is
not utilized, the speed tap can be changed to medium or
high speed.   Never run CFM below 350 CFM per ton,
evaporator freezing or poor unit performance is possible.

Summary of Contents for GPC SERIES

Page 1: ...on TX 77092 06 06 www goodmanmfg com www amana hac com 2005 2006 Goodman Manufacturing Company L P All information contained herein is subject to change without notice INSTALLATION OPERATING INSTRUCTI...

Page 2: ...her shipping or concealed should be filed immediately with the shipping company Check the unit model number specifications electrical characteristics and accessories to determine if they are correct I...

Page 3: ...ntinuous operating conditions independent of any installed system EPA Regulations IMPORTANT THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY EPA HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCT...

Page 4: ...gisters are low on the wall or in the floor compressor compartment and controls The top of the unit should be completely unobstructed If units are to be located under an overhang there should be a min...

Page 5: ...ty use an insulation with a good K factor and a vapor barrier Industry practices should be followed Balancing dampers are recommended for each branch duct in the supply system Ductwork should be prope...

Page 6: ...o 18AWG as follows LEAD THERMOSTAT Red R 24V Green G Fan Yellow Y Cool White W1 Heat Brown W2 Heat TABLE 2 b Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control...

Page 7: ...ht will come on 15 If checking the unit in the wintertime when the outdoor coil is cold enough to actuate the defrost control observe at least one defrost cycle to make sure the unit defrosts complete...

Page 8: ...herefore all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle and most apply on the heating cycle except that condenser beco...

Page 9: ...the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 75 F the defrost cycle is terminated and the timing period is reset...

Page 10: ...the proper amount All package units are charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superheat at the compresso...

Page 11: ...perly SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the He...

Page 12: ...nnection a Check for unit voltage at compressor check tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still...

Reviews: