background image

12

• Parts
• Contractor Programs and Training
• Financing Options

TROUBLESHOOTING CHART

NOTE:  SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE

Quality Makes the Difference!

All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency.
We have designed these units to significantly reduce the most frequent causes of product failure. They are simple to
service and forgiving to operate. We use quality materials and components. Finally, every unit is run tested before it
leaves the factory. That’s why we know. . .

There’s No Better Quality.

SYMPTOM

High head - low suction

a. Restriction in liquid line or flowrator

a. Remove or replace with proper size flowrator.

High head - high or normal suction

a. Dirty condenser coil

a. Clean coil

b. Overcharged

b. Correct System charge

c. Condenser fan not running

c. Repair or Replace

a.  Incorrect flowrator

a. Replace with correct flowrator

b. Defective compressor valves

b. Replace compressor

c. Flowrator not seating properly

c. Check for debris under flowrator or deformed 

flowrator. Remove debris or replace flowrator.

a. Power off or loose electrical connection

a. Check for unit voltage at contactor in unit

b. Thermostat out of calibration set too high b. Reset
c. Defective contactor

c. Check for 24 volts at contactor coil replace if 

contacts are open

d. Blown fuses or tripped breaker

d. Replace fuse or reset breaker Check wiring - 

replace transformer

e. Transformer defective

f. High or low pressure control open 

(Optional)

f. Reset high pressure control or check unit charge

High pressure control opens at 425 psig

Low pressure control opens at 25 psig

g. Compressor overload contacts open

g. Replace compressor

NOTE: Wait at least 2 hours for overload to reset

Condenser fan runs,
compressor doesn't

a. Loose connection

a. Check for unit voltage at compressor check & 

tighten all connections

b. Compressor stuck, grounded or open 

winding

 

open internal overload

b. Wait at least 2 hours for overload to reset  If still 

open, replace the compressor.

c. Low voltage connection

c. At compressor terminals, voltage must be within 

10 % of nameplate volts when unit is operating

d. Capacitor weak, open, or shorted

d.  Check capacitor. If defective, replace.

Low suction - cool compressor

a.

a.

Iced evaporator coil

a. Defective overload protector

a. Replace - check for correct voltage

b. Unit cycling on low pressure control

b. Check refrigerant charge and / or airflow

a.

a. Increase speed of blower or reduce restriction 

replace air filters

a. Excessive load

a. Recheck load calculation

b. Defective compressor

b. Replace

c. Reversing valve not seating properly.

c. Replace

a. Improperly sized unit

a. Recalculate load

b. Improper airflow

b. Check - should be approximately 400 CFM per 

ton

c. Incorrect refrigerant charge.

c. Charge per procedure attached to unit service 

panel

d. Incorrect voltage 

d. At compressor terminals, voltage must be within 

10% of nameplate volts when unit is operating

Evaporator coil freezing or frosting

a. Low airflow

a. Check - should be approximately 400 CFM per 

ton, dirty air filters, all duct outlets open

b. Low refrigerant charge

b. Properly charge unit

c. Operating unit in cooling mode below 

65°F outdoor temperature

c. Install or check low ambient control, should be 

open below 65°F outdoor temperature

Low indoor airflow

Increase speed of blower or reduce restriction - 
replace air filters

Insufficient cooling

High suction pressure

REMEDY

POSSIBLE CAUSE

Compressor short cycles

Registers sweat

Low airflow

Low head - high suction

Unit will not run

Visit our website at www.goodmanmfg.com for information on:

©

 2005-2006 Goodman Manufacturing Company, L.P.

• Goodman Products
• Warranties
• Customer Services

DISCONNECT ALL POWER TO UNIT BEFORE SERVICING.  FAILURE TO FOLLOW THIS WARNING
MAY RESULT IN PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK.

WARNING

Summary of Contents for GPC SERIES

Page 1: ...on TX 77092 06 06 www goodmanmfg com www amana hac com 2005 2006 Goodman Manufacturing Company L P All information contained herein is subject to change without notice INSTALLATION OPERATING INSTRUCTI...

Page 2: ...her shipping or concealed should be filed immediately with the shipping company Check the unit model number specifications electrical characteristics and accessories to determine if they are correct I...

Page 3: ...ntinuous operating conditions independent of any installed system EPA Regulations IMPORTANT THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY EPA HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCT...

Page 4: ...gisters are low on the wall or in the floor compressor compartment and controls The top of the unit should be completely unobstructed If units are to be located under an overhang there should be a min...

Page 5: ...ty use an insulation with a good K factor and a vapor barrier Industry practices should be followed Balancing dampers are recommended for each branch duct in the supply system Ductwork should be prope...

Page 6: ...o 18AWG as follows LEAD THERMOSTAT Red R 24V Green G Fan Yellow Y Cool White W1 Heat Brown W2 Heat TABLE 2 b Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control...

Page 7: ...ht will come on 15 If checking the unit in the wintertime when the outdoor coil is cold enough to actuate the defrost control observe at least one defrost cycle to make sure the unit defrosts complete...

Page 8: ...herefore all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle and most apply on the heating cycle except that condenser beco...

Page 9: ...the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 75 F the defrost cycle is terminated and the timing period is reset...

Page 10: ...the proper amount All package units are charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superheat at the compresso...

Page 11: ...perly SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the He...

Page 12: ...nnection a Check for unit voltage at compressor check tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still...

Reviews: