background image

4

CAUTION

APPLYING TOO MUCH HEAT TO ANY TUBE CAN MELT THE TUBE.  

TORCH HEAT REQUIRED TO BRAZE TUBES OF VARIOUS SIZES 

MUST BE PROPORTIONAL TO THE SIZE OF THE TUBE.  SERVICE 

PERSONNNEL MUST USE THE APPROPRIATE HEAT LEVEL FOR 

THE SIZE OF THE TUBE BEING BRAZED.

9.4  Tubing Connections for TXV Version
  TXV models come with factory installed adjustable TXV 

with the bulb permanently located on the suction tube.

1.  Remove coil access panel and rubber grommets.  

2.  Remove access valve fitting cap and depress the valve 

stem in access fitting to release pressure. No pressure 

indicates possible leak.

3.  Reinstall the the Coil Access Panel & rubber grommets.
4.  Remove the spin closure on both the liquid and suction 

tubes using a tubing cutter. DO NOT USE A CUTTING 

METHOD THAT WOULD RESULT IN THE GENERA-

TION OF COPPER SHAVINGS OR COPPER DUST.

SUCTION

LINE SET

SUCTION

TUBE

RUBBER

GROMMET

Figure 5.1

TORQUE 180-240 IN-LBS

ENSURE THAT SEAL 

WASHERS STAY 

IN POSITION

CC

Figure 5.2

CAUTION

EXCESSIVE TORQUE CAN CAUSE TXV RETAINING RING TO 

WEAKEN & CREATE LEAK AND WILL BECOME DIFFICULT TO 

RE-INSTALL TXV. USE THE PROPER TORQUE (180-240 IN. LBS) 

SETTINGS WHEN TIGHTENING THE TXV OR HAND TIGHTEN 

PLUS 1/2 TURN.

LIQUID

LINE SET

LIQUID

LINE

RUBBER

GROMMET

Figure 5.3

5.  Insert liquid line set into liquid tube expansion and slide 

grommet about 18” away from braze joint. 

6.  Insert suction line set into suction tube expansion and 

slide insulation and grommet about 18” away from braze 

joint. 

7.  Braze suction and liquid line joints.

9.5 Thermal Expansion Valve System Adjustment 

Run the system at Cooling for 10 minutes until refrigerant 

pressures stabilize. Use the following guidelines and meth-

ods to check unit operation and ensure that the refrigerant 

charge is within limits. Charge the unit on low stage.
Purge gauge lines. Connect service gauge manifold to base-

valve service ports.
Temporarily install a thermometer on the liquid line at the 

liquid line service valve and 4-6” from the compressor on the 

suction line. Ensure the thermometer makes adequate contact 

and is insulated for best possible readings. Use liquid line 

temperature to determine subcooling and vapor temperature 

to determine superheat.
Check subcooling and superheat. Systems with TXV appli-

cation should have a subcooling of 7 to 9ºF and superheat 

of 7 to 9 ºF.

a.  If subcooling and superheat are low, adjust TXV to 7 

to 9 ºF superheat, then check subcooling.

NOTE: To adjust superheat, turn the valve stem clock-

wise to increase and counter clockwise to decrease.

b.  If subcooling is low and superheat is high, add charge 

to raise subcooling to 7 to 9ºF then check superheat.

c.  If subcooling and superheat are high, adjust TXV valve 

to 7 to 9 ºF superheat, then check subcooling.

Summary of Contents for DOWNFLOW

Page 1: ...PFLOW DOWNFLOW COILS INSTALLATION INSTRUCTIONS 2 1 Handling Use caution when transporting carrying unit Do not carry unit with hooks or sharp object The preferred method of carrying the unit after arr...

Page 2: ...the preferred wrapping material 1 Ensure drain pan hole is NOT obstructed 2 To prevent potential sweating and dripping on finished space it may be necessary to insulate the condensate drain line loca...

Page 3: ...Y RECOMMENDED TO PREVENT SCORCHING OR MARRING OF THE EQUIPMENT FINISH WHEN BRAZING CLOSE TO THE PAINTED SURFACES USE BRAZING ALLOY OF 5 MINIMUM SILVER CONTENT NOTE Refrigerant tubing must be routed to...

Page 4: ...line set into liquid tube expansion and slide grommet about 18 away from braze joint 6 Insert suction line set into suction tube expansion and slide insulation and grommet about 18 away from braze joi...

Page 5: ...onnect manifold set installation is complete NOTE ChecktheSchraderportsforleaksandtightenvalve cores if necessary Install caps finger tight SUBCOOL FORMULA SAT LIQUID LINE TEMP LIQUID LINE TEMP SUPERH...

Page 6: ...ling Along The Panel Gap IMPORTANT NOTE To prevent cabinet sweating and airflow leak apply field provided insulation tape along all joining surfaces between the coil gas furnace duct work and panels S...

Page 7: ...uminum coils TP 109 is also available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners 16 Start Up Procedure WARNING HIGH VOLTAGE DI...

Page 8: ...F Heating Supply Air Temperature DB F Temperature Rise DB F Delta T Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV and EEV wiring...

Page 9: ...9 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 12: ...oduct brand you purchased to be directed to the feedback page DAIKIN AMANA BRAND GOODMAN BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the...

Reviews: