Goodman CVC9/95 Installation Instructions Manual Download Page 6

6

P

RODUCT

 D

ESCRIPTION

 & A

PPLICATION

S

HIPPING

 I

NSPECTION

All units are securely packed in shipping containers tested ac-
cording to International Safe Transit Association specifications.
The carton must be checked upon arrival for external damage.  If
damage is found, a request for inspection by carrier’s agent
must be made in writing immediately.

The furnace must be carefully inspected on arrival for damage
and bolts or screws which may have come loose in transit.  In
the event of damage the consignee should:

1. Make a notation on delivery receipt of any visible damage

to shipment or container.

2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon

as possible -  preferably within five days.

4. File the claim with the following support documents within

a nine month statute of limitations.

Original or certified copy of the Bill of Lading, or
indemnity bond.

Original paid freight bill or indemnity in lieu thereof.

Original or certified copy of the invoice, showing trade
and other discounts or reductions.

Copy of the inspection report issued by carrier’s
representative at the time damage is reported to carrier.

The carrier is responsible for making prompt inspection of dam-
age and for a thorough investigation of each claim. The distribu-
tor or manufacturer will not accept claims from dealers for trans-
portation damage.

E

LECTROSTATIC

 D

ISCHARGE

 (ESD) P

RECAUTIONS

NOTE:

  Discharge body’s static electricity before touching unit.

An electrostatic discharge can adversely affect electrical com-
ponents.

Use the following precautions during furnace installation and
servicing to protect the integrated control module from damage.
By putting the furnace, the control, and the person at the same
electrostatic potential, these steps will help avoid exposing the
integrated control module to electrostatic discharge.  This pro-
cedure is applicable to both installed and non-installed (un-
grounded) furnaces.

1. Disconnect all power to the furnace.  Do not touch the

integrated control module or any wire connected to the
control prior  to discharging your body’s electrostatic
charge to ground.

2. Firmly touch a clean, unpainted, metal surface of the

furnaces near the control.  Any tools held in a  person’s
hand during grounding will be discharged.

3. Service integrated control module or connecting wiring

following the discharge process in step 2.  Use caution
not to recharge your body with static electricity; (i.e., do
not move or shuffle your feet, do not touch ungrounded
objects, etc.).  If you come in contact with an ungrounded
object, repeat step 2 before touching control or wires.

4. Discharge your body to ground before removing a new

control from its container.  Follow steps 1 through 3 if
installing the control on a furnace.  Return any old or new
controls to their containers before touching any ungrounded
object.

T

O

 T

HE

 I

NSTALLER

Before installing this unit, please read this manual thoroughly to
familiarize yourself with specific items which must be adhered to,
including but not limited to: unit maximum external static pres-
sure, gas pressures, BTU input rating, proper electrical connec-
tions, circulating air temperature rise, minimum or maximum CFM,
and motor speed connections.

I

MPORTANT

 N

OTE

 

TO

 

THE

 O

WNER

 

REGARDING

 P

RODUCT

 W

AR

-

RANTY

Your warranty certificate is supplied as a separate document with
the unit installed by your contractor. Read the limited warranty
certificate carefully to determine what is and is not covered and
keep the warranty certificate in a safe place. If you are unable to
locate the warranty certificate please contact your installing con-
tractor or contact customer service (877-254-4729) to obtain a
copy.

To receive the Lifetime Heat Exchanger Limited Warranty, good for
as long as you own your home, and the 10-year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Que-
bec.

To register your Goodman brand unit, go to www.goodmanmfg.com.
Click on the word “Warranty” located on the left side of the home
page.  Next, click on the word “Product Registration” located on
the left side of the Warranty page and complete the forms in the
manner indicated on the Product Registration page.

To register your Amana brand unit, go to www.amana-hac.com.
Click on the word “Warranty” located on the top right of the home
page.  Next, click on the word “Product Registration” located on
the left side of the Warranty page and complete the forms in the
manner indicated on the Product Registration page.

Product limited warranty certificates for models currently in pro-
duction can be viewed at www.goodmanmfg or www.amana-
hac.com.  If your model is not currently in production or does not
appear on the website, please contact your installing contractor or
contact customer service at (877-254-4729) to obtain a copy of
your warranty certificate.

Each product overview page contains a Product Warranty link; by
clicking on it you will be able to view the limited warranty coverage
for that specific product. To view warranty registration information,
click on the Product Warranty text on the left navigation panel on
the home page of each website. The Online Product Registration
pages are located in this same section.

Summary of Contents for CVC9/95

Page 1: ...customer This includes all safety precautions and related items Prior to actual installation thoroughly familiarize yourself with this Instruction Manual Pay special attention to all safety warnings...

Page 2: ...TION AIR PIPE 12 DUAL CERTIFICATION NON DIRECT DIRECT VENT 12 MATERIALS AND JOINING METHODS 13 PROPER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIRE...

Page 3: ...OPERATION 37 GAS SUPPLY PRESSURE MEASUREMENT 37 GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT 38 GAS INPUT RATE MEASUREMENT NATURAL GAS ONLY 39 TEMPERATURE RISE 39 CIRCULATOR BLOWER SPEEDS 40 BLOW...

Page 4: ...A LICENSE TO INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQUIPMENT WARNING MAINTENANCE 50 ANNUAL INSPECTION 50 FILTERS 50 BURNERS 51 INDUCED DRAFT AND CIRCULATOR BLOWERS 51 CONDENSATE TRAP AND DRA...

Page 5: ...T CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAINTENANCE OF THIS PRODUCT WARNING TO PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INS...

Page 6: ...incontactwithanungrounded object repeat step 2 before touching control or wires 4 Discharge your body to ground before removing a new control from its container Follow steps 1 through 3 if installing...

Page 7: ...t pipe is op tional and the furnace can be vented as a Non directvent singlepipe centralforcedairfurnacein which combustion air is taken from the installation area or from air ducted from the outside...

Page 8: ...ate the furnace so condensate flows downwards to the drain Do not locate the furnace or its condensate drainage system in any area subject to below freezing temperatures without proper freeze protecti...

Page 9: ...ichthisfurnacehasbeendesigncertified Theminimum clearanceinformationforthisfurnaceisprovidedontheunit sclear ance label These clearances must be permanently maintained Clearancesmustalsoaccommodateani...

Page 10: ...ontact your distributor for proper airflow requirements and number of required ductwork connec tions Refer to Recommended Installation Positions figure for appropriate installation positions ductwork...

Page 11: ...e from the heat ex changerandinduceddraftblower Forproperfluepipedrainage thefurnacemustbelevellengthwisefromendtoend Thefurnace should also be level from back to front or have a slight tilt with the...

Page 12: ...listing of appropriate manufacturer s kits for propane gas and or high altitude installa tions The indicated kits must be used to insure safe and proper furnaceoperation Allconversionsmustbeperformed...

Page 13: ...entfromthefurnace Hori zontalrunsofvent fluepipingmustbesupportedeverythreetofive feet and must maintain a 1 4 inch per foot downward slope back towardsthefurnace toproperlyreturncondensatetothefurnac...

Page 14: ...lbow should be installed on the combus tionairintake coupling toguardagainstinadvertentblockage Vent Termination Clearances NOTE InCanada theCanadianFuelGasCodetakesprecedence overtheprecedingterminat...

Page 15: ...the induced draft blower and the vent fluepipe 3 UpflowandCounterflowunits Removethevent fluepipefromthefurnace 4 Cut the vent flue pipe 3 75 inches from the flanged end of the pipe see Vent Flue Pip...

Page 16: ...n the blower deck with the plastic plug included in the drain kit bag 4 With the gasket facing the cabinet side panel and the flange sflatspotfacingforward securethecombustionair intakecouplingtotheca...

Page 17: ...58 55 52 49 46 43 40 3 71 68 65 62 59 56 53 50 2 or 2 1 2 61 58 55 52 49 46 43 40 3 71 68 65 62 59 56 53 50 115 000 3 71 68 65 62 59 56 53 50 UPFLOW Non Direct Vent Single Pipe Maximum Allowable Leng...

Page 18: ...run through an existing unused chimney however they must extend a minimum of 12 inches above the top of the chimney The space between the pipes and the chimney must be closed with a weather tight corr...

Page 19: ...stion Air Intake pipe 3 Minimum requirements for each Vent Flue Combustion Air Intake pipe is five 5 feet in length and one elbow tee 4 2 1 2 or 3 diameter pipe can be used in place of 2 diameter pipe...

Page 20: ...ommon roof top maintain the same minimum clear ances between the exhaust vent and air intake terminations of adjacentunitsaswiththeexhaustventandairintaketerminations of a single unit If more than one...

Page 21: ...llation and drain hose hook ups Thedraintrapsuppliedwiththefurnacemustbeused Thedrainlinebetweenfurnaceanddrainlocationmust be constructed of 3 4 PVC or CPVC Thedrainlinebetweenfurnaceanddrainlocation...

Page 22: ...be 1 into rubber elbow drain port and secure with silverhoseclamp Angletubeoutwardtowardfrontoffurnace 5 Cut173 4inchesfromthelongendofHoseBanddiscard Secure the remaining hose to Tube 1 with a green...

Page 23: ...ntheexternally mountedrubberelbow Discardcutportion 5 InsertTube1intorubberelbowdrainportandsecurewitha silver hose clamp Angle tube toward trap 6 Cut173 4inchesfromthelongendofHoseBanddiscard 7 Secur...

Page 24: ...or appropriate length to cut Secure remaininghosetoTube1withagreenhoseclamp Route other end of Hose B to front left side panel grommet hole NOTE Longhose B mustalwaysbeconnectedtoTube1and the elbow an...

Page 25: ...imize sagging Plug left unused pressure tap with plug removed from right side 2 Secure Hose A to front cover drain tap with a red hose clamp Routehosetorearright down sidepanelgrommet holes 3 Cut 1 4...

Page 26: ...ting a hose to the induced draft blower housing 6 Cut 5 1 2 inches straight length from the long end of each Tube 2 and discard radius ends 7 Insert approximately one inch of each Tube 2 through left...

Page 27: ...ust be observed when making field connections Line voltage connections can be made through either the right or left side panel The furnace is shipped configured for a right side left side for counterf...

Page 28: ...tablestodetermineiftherequiredsingle stage cooling airflow can be delivered at low stage Y1 input or high stage Y2 input Additionally use of ramping profile and dehumidificationfeaturesrequireajumperb...

Page 29: ...nable the dehumidify function on the integrated control mod ule setthedehumidificationENABLEdipswitchfromOFFtoON Oncetheswitchisset thedehumidifyfunctionisenabledduringa combinationcallforcooling T St...

Page 30: ...um 5 0 w c Maximum 10 0 w c Propane Gas Minimum 11 0 w c Maximum 13 0 w c Inlet Gas Supply Pressure HIGHALTITUDEDERATE Whenthisfurnaceisinstalledathighaltitude theappropriateHigh Altitude orifice kit...

Page 31: ...must supply a ground joint union drip leg manual shutoff valve and line and fittings to connect to gas valve In some cases the installer may also need to supply a transition piece from 1 2 pipe to a...

Page 32: ...MODEL MANUAL SHUT OFF VALVE UPSTREAM FROM GROUND JOINT PIPE UNION DRIP LEG GROMMET IN STANDARD GAS LINE HOLE DRAIN TRAP ALTERNATE GAS LINE LOCATION MANIFOLD PLUG IN ALTERNATE GAS LINE HOLE GAS VALVE G...

Page 33: ...3 48 kPA PROPANEGASTANKSANDPIPING IF THE GAS FURNACE IS INSTALLED IN A BASEMENT AN EXCAVATED AREA OR CONFINED SPACE IT IS STRONGLY RECOMMENDED TO CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING...

Page 34: ...ities at 15 psig settings multiply by 1 130 To convert to capacities at 5 psig settings multiply by 0 879 Propane Gas Piping Chart I 3 8 1 2 5 8 3 4 7 8 1 2 3 4 1 1 1 4 1 1 2 10 39 92 199 329 501 275...

Page 35: ...duced by approximately 18 if duct flanges are not unfolded This could cause performance issues and noise issues EDGES OF SHEET METAL HOLES MAY BE SHARP USE GLOVES AS A PRECAUTION WHEN REMOVING SHEET M...

Page 36: ...uirement Disposable Minimum Filter area sq in Based on 300 ft min filter face velocity UPRIGHTINSTALLATIONS Dependingontheinstallationand orcustomerpreference differ ing filter arrangements can be app...

Page 37: ...control to the ON position 8 Replacetheburnercompartmentdoor 9 Openthemanualgasshutoffvalveexternaltothefurnace 10 Turnontheelectricalpowertothefurnace 11 Adjustthethermostattoasettingaboveroomtempera...

Page 38: ...ug before turning on gas to furnace 6 Turn OFF any unnecessary gas appliances stated in step 3 Gas Line Gas Shutoff Valve Gas Line To Furnace Drip Leg Cap With Fitting Manometer Hose Manometer Open To...

Page 39: ...atethefurnaceinputinBTUsperhour BTU hr Input equalsthesumoftheinstallation sgasheatingvalueanda conversionfactor hourstoseconds dividedbythenumber of seconds per cubic foot The measured input must not...

Page 40: ...smustbechecked for required air flow Any electronic air cleaners or other devices may require specific air flows consult installation instructions of thosedevicesforrequirements 3 Knowing the furnace...

Page 41: ...to the full demand airflow Profile D has a 1 2 minute at 50 airflow OFF delay OFF OFF AirflowTable Model Tap Low Stage Cool High Stage Cool Low Stage Heat High Stage Heat A 390 600 550 792 B 520 800 6...

Page 42: ...gle stage air conditioner Any other sys temconfigurationsareconsideredinvalidComfortNetsystemsand must be connected as a traditional or legacy system see Elec trical Connectionsfor wiring connections...

Page 43: ...wo Wires between Furnace and AC HP and Four Wires between Furnace and Thermostat CT COMPATIBLE FURNACE WITH NON CT COMPATIBLE SINGLE STAGEAIRCONDITIONER Fourwiresarerequiredbetweenthefurnaceandthermos...

Page 44: ...xt WORKING will be displayed in the scrolling display area while the data is being retrieved The first sub menu is then displayed See tables below for listing of furnace submenus Touch the or _ to ste...

Page 45: ...ecutively repeated faults are shown a maximum of 3 times DIAGNOSTICS Submenu Item Indication for Display Only not User Modifiable Model Number MOD NUM Displays the furnace model number Serial Number S...

Page 46: ...d press the IN STALLER CONFIG button Navigate to dF BAL PNT Adjust the dual fuel system balance point using the back forward ar rows DIAGNOSTICS Accessing the furnace s diagnostics menu provides ready...

Page 47: ...ds for an out of box reset Red Communications LED 2 Flashes x Out of box reset x Control power up x Learn button depressed x None x None Off x No power x Communications error x No power to furnace x O...

Page 48: ...circulatorblowerwillremainonhighheatingspeedforthirty 30 seconds before switching to the low heat circulating speed R and W1 or R and W1 W2 thermostat contacts open completing the call for heat Gasval...

Page 49: ...e burner manifold as sembly and monitor the burner flame They are normally closed electrically manual reset sensors These limits guard against burnerflamesnotbeingproperlydrawnintotheheatexchanger PRE...

Page 50: ...that all fur nacecomponentsareinproperworkingorderandthattheheating system functions appropriately Pay particular attention to the fol lowing items Repair or service as necessary Flue pipe system Chec...

Page 51: ...m the induced draft blower 4 Remove the induced draft blower drain and pressure tap hosesfromtherecuperatorcoilfrontcover 5 Removetherecuperatorcoilfrontcovertoexposethecoil tubesandturbulators 6 Remo...

Page 52: ...rmination ON A OFF OFF B ON OFF C OFF ON D ON ON Normal OFF OFF 10 ON OFF 10 OFF ON Normal ON ON A OFF OFF B ON OFF C OFF ON D ON ON A OFF OFF B ON OFF C OFF ON D ON ON Disabled OFF Unused Enabled ON...

Page 53: ...stion air piping front cover pressure switch opening or improper induced draft blower performance x Locate and correct gas interruption x Check front cover pressure switch operation hose wiring contac...

Page 54: ...heat IMPROPER FLAME E4 x Short to ground in flame sense circuit x Lingering burner flame x Slow closing gas valve x Correct short at flame sensor or in flame sensor wiring x Check for lingering flame...

Page 55: ...ir replace if necessary x Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary x Check induced draft blower performance Correc...

Page 56: ...lost communications with circulator blower motor MOTOR COMM b1 x Loose wiring connection at circulator motor control leads x Failed circulator blower motor x Failed integrated control module x Tighten...

Page 57: ...rmostat Call for Service icon illuminated x ComfortNet thermostat scrolls Check Furnace message b6 x Circulator blower motor shuts down for over or under voltage condition x Circulator blower motor sh...

Page 58: ...ATING CYCLE HIGH STAGE PRSSURE SWITCH STUCK OPEN REVERSED 115 VAC POLARITY DATA NOT YET ON NETWORK INVALID MEMORY CARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOW...

Page 59: ...NTROLS 40 VA Y2 14 IND LO MANUAL RESET ROLLOUT LIMIT CONTROLS 9 WH N PK PINK HUMIDIFIER INDOOR HIGH FIRE PRESS SWTICH DISCONNECT TWO STAGE GAS VALVE AIR CLEANER C ONLY 2 MANUFACTURER S SPECIFIED REPLA...

Page 60: ...IDIFIER 60HZ PKPINK N WH 9 MANUALRESETROLLOUT LIMITCONTROLS INDLO 14 Y2 40VA MANUALRESETAUXILIARYLIMIT CONTROLS 3 HUM OR JUNCTION BLWR PU PURPLE 1 CIRCULATOR BLOWER R 1 GND JUNCTIONBOX SWITCH TEMP NEU...

Reviews: