34
G
AS
S
UPPLY
AND
P
IPING
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
10
730
1,700
3,200
5,300
8,300
3,200
7,500
20
500
1,100
220
3,700
5,800
2,200
4,200
30
400
920
2,000
2,900
4,700
1,800
4,000
40
370
850
1,700
2,700
4,100
1,600
3,700
50
330
770
1,500
2,400
3,700
1,500
3,400
60
300
700
1,300
2,200
3,300
1,300
3,100
80
260
610
1,200
1,900
2,900
1,200
2,600
100
220
540
1,000
1,700
2,600
1,000
2,300
125
200
490
900
1,400
2,300
900
2,100
150
190
430
830
1,300
2,100
830
1,900
175
170
400
780
1,200
1,900
770
1,700
200
160
380
730
1,100
1,800
720
1,500
Pipe or
Tubing
Length
Feet
Tubing Size, O.D. Type L
Nominal Pipe Size
Schedule 40
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Propane Gas Piping Chart I
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
1"
1-1/4" 1-1/2"
10
39
92
199
329
501
275
567
1,071 2,205
3,307
20
26
62
131
216
346
189
393
732
1,496
2,299
30
21
50
107
181
277
152
315
590
1,212
1,858
40
19
41
90
145
233
129
267
504
1,039
1,559
50
18
37
79
131
198
114
237
448
913
1,417
60
16
35
72
1,211
187
103
217
409
834
1,275
80
13
29
62
104
155
89
185
346
724
1,066
100
11
26
55
90
138
78
162
307
630
976
125
10
24
48
81
122
69
146
275
567
866
150
9
21
43
72
109
63
132
252
511
787
200
8
19
39
66
100
54
112
209
439
665
250
8
17
36
60
93
48
100
185
390
590
Tubing Size, O.D. Type L
Nominal Pipe Size
Schedule 40
Pipe or
Tubing
Length
Feet
*Data in accordance with NFPA pamphlet No. 54
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum Propane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Propane Gas Piping Chart II