background image

3

If secondary drain is not installed, the secondary access
must be plugged.

CAUTION

NOTE:

 Trapped lines are required by many local codes. In the

absence of any prevailing local codes, please refer to the
requirements listed in the Uniform Mechanical Building Code.

A drain trap in a 

draw-through

 application prevents air from

being drawn back through the drain line during fan operation
thus preventing condensate from draining, and if connected to
a sewer line to prevent sewer gases from being drawn into the
airstream during blower operation. In a 

blow-through

 applica-

tion the drain trap prevents conditioned air from escaping. It is
permissible in this application to use a shallow trap design
sometimes referred to as a running trap.

Cased Coil

3" MIN.

POSITIVE LIQUID SEAL 

REQUIRED AT TRAP

Drain

Connection

2" MIN.

Figure 4

Condensate Drain Trap

The depth of a running trap (Figure 5) should be  either 1" or a
depth that permits unrestricted condensate drainage without
excessive air discharge.

Field experience has shown condensate drain traps with an
open vertical Tee between the air handler and the condensate
drain trap can improve condensate drainage in some applica-
tions, but may cause excessive air discharge out of the open
Tee. The manufacturer does not prohibit this type of drain but
we also do not recommend it due to the resulting air leakage.
Regardless of the condensate drain design used, it is the
installer’s responsibility to ensure the condensate drain sys-
tem is of sufficient design to ensure proper condensate re-
moval from the coil drain pan.

PITCH
TOWARDS
DRAIN

1” MIN

TRAP

CONDENSATE
DRAIN CONN.
CONNECT DRAIN
SAME SIZE AS ON
UNIT OR LARGER

Figure 5

Running Trap

Horizontal Coil Water Blower-Off Bracket

CHPF4860 coils are shipped with an accessory kit containing
a sheet metal bracket. For horizontal-left applications where
the airflow may exceed 1600 CFM, this bracket must be
installed on the left side of the drain pan as shown in Figure 6.

Figure 6

Horizontal Blow-Off Bracket

Refrigerant Lines

A quenching cloth is strongly recommended to
prevent scorching or marring of the equipment
finish when welding close to the painted surfaces.
Use brazing alloy of 5% minimum silver content.

WARNING

All cut ends are to be round, burr free, and cleaned.  Any other
condition increases the chance of a refrigerant leak. Use a
pipe cutter to remove the closed end of the spun closed suc-
tion line.

To avoid overheating after brazing, quench all welded joints
with water or a wet rag.

For the correct tubing size, follow the specification for the con-
denser/heat pump

The coil is shipped under pressure.  Follow these
instructions to prevent injury.

WARNING

Applying too much heat to any tube can melt the tube. Torch
heat required to braze tubes of various sizes must be
proportional to the size of the tube. Service personnel must
use the appropriate heat level for the size of the tube being
brazed.

CAUTION

NOTE: 

Tubes of smaller size require less heat to bring the

tube to brazing temperature before adding brazing alloy. The
use of a heat shield when brazing is recommended to avoid
burning the serial plate or the finish on the unit.

Summary of Contents for CH SERIES

Page 1: ...dering repair parts give the complete product model and serial numbers as stamped on the product Replacement parts for this product are avail able through your contractor or local distributor For the...

Page 2: ...female connections The connectors re quired can be 3 4 NPT male either PVC or metal pipe and should be hand tightened to a torque of no more than 37 in lbs to prevent damage to the drain pan connecti...

Page 3: ...sys tem is of sufficient design to ensure proper condensate re moval from the coil drain pan PITCH TOWARDS DRAIN 1 MIN TRAP CONDENSATE DRAIN CONN CONNECT DRAIN SAME SIZE AS ON UNIT OR LARGER Figure5 R...

Page 4: ...sulation RUBBER GROMMET SUCTION LINE WITH SPIN CLOSURE Figure8 Suction Line Grommet 11 Check fittings for leaks after complete installation Evacu ate and charge on the low side NOTE With the piston in...

Page 5: ...LLATION AND OPERATING INSTRUCTIONS FOR HORIZONTAL TWO WAY COILS CH SERIES IMPORTANT The United States Environmental Protection Agency EPA has issued various regulations regarding the introduction and...

Page 6: ...cabinet enclosure Drain lines from the auxiliary pan must be installed and terminated so that the homeowner can see water discharges A primary condensate drain connection is located in the drain pan o...

Page 7: ...he 13 16 nut 1 turn only to allow the high pressure tracer gas to escape No gas indicates a possible leak 2 After the gas has escaped remove the nut and discard the cap 3 Use a tube cutter to remove t...

Page 8: ...ficiency We have designed these units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Fi...

Reviews: