background image

2

Figure 2

Horizontal Right Application

3.

Using the hardware and brackets provided, attach the coil

to the furnace then attach the plenum to the coil (Figure 3).

COIL

PLENUM

FRONT BRACKET

ACCESSORY

FURNACE

TOP & BACK
BRACKET
ACCESSORY

COIL

FURNACE

PLENUM

TRANSITION

MAX 10° ANGLE

ACCESSORY

TOP & BACK

ACCESSORY

FRONT BRACKET

COIL

FURNACE

BRACKET

PLENUM

(Z-BRACKET WITH NARROW FURNACE)

Figure 3

Furnace, Coil and Plenum Installation

COIL

FURNACE

PLENUM

DUCT BOARD, SHEET 

METAL OR OTHER 

FILLER MATERIAL

Figure 3a

Incorrrect Furnace, Coil and Plenum Installation

Using tape or mastic seal between the coil and furnace and
the coil and plenum.

Condensate Drain Piping

When coils are installed above ceilings, or in other locations
where damage from condensate overflow may occur, it is 

MAN-

DATORY 

to install a field-fabricated auxiliary drain pan under

the coil cabinet enclosure. Drain lines from the auxiliary pan
must be installed and terminated so that the homeowner can
see water discharges.

The coil drain pan has a primary and an optional secondary
drain with 3/4" NPT female connections. The connectors re-
quired can be 3/4" NPT male either PVC or metal pipe and
should be hand tightened to a torque of no more  than 37 in-lbs.
to prevent damage to the drain pan connection.  An insertion
depth between .355 to .485 inches (3-5 turns) should be ex-
pected at this torque. If using a copper drain line, solder a
short piece of pipe to the connector before installing a drain
fitting. DO NOT over torque the 3/4” copper connector to the
plastic drain connection.

1. Ensure drain pan hole is NOT obstructed.

2. To prevent potential sweating and dripping on finished

space, it may be necessary to insulate the condensate
drain line located inside the building. Use Armaflex

® 

or

similar material.

A Secondary Condensate Drain Connection has been provided
for areas where the building codes require it. Pitch the drain
line 1/4" per foot to provide free drainage.  Insulate drain lines
(primary and secondary) located inside the building to prevent
sweating.  Install a condensate trap in the primary drain line to
ensure proper drainage. If the secondary line is required, run
the line separately from the primary drain and end it where it
can be easily seen.

NOTE:

 Water coming from this line means the coil primary

drain is plugged and needs clearing.

Summary of Contents for CH SERIES

Page 1: ...dering repair parts give the complete product model and serial numbers as stamped on the product Replacement parts for this product are avail able through your contractor or local distributor For the...

Page 2: ...female connections The connectors re quired can be 3 4 NPT male either PVC or metal pipe and should be hand tightened to a torque of no more than 37 in lbs to prevent damage to the drain pan connecti...

Page 3: ...sys tem is of sufficient design to ensure proper condensate re moval from the coil drain pan PITCH TOWARDS DRAIN 1 MIN TRAP CONDENSATE DRAIN CONN CONNECT DRAIN SAME SIZE AS ON UNIT OR LARGER Figure5 R...

Page 4: ...sulation RUBBER GROMMET SUCTION LINE WITH SPIN CLOSURE Figure8 Suction Line Grommet 11 Check fittings for leaks after complete installation Evacu ate and charge on the low side NOTE With the piston in...

Page 5: ...LLATION AND OPERATING INSTRUCTIONS FOR HORIZONTAL TWO WAY COILS CH SERIES IMPORTANT The United States Environmental Protection Agency EPA has issued various regulations regarding the introduction and...

Page 6: ...cabinet enclosure Drain lines from the auxiliary pan must be installed and terminated so that the homeowner can see water discharges A primary condensate drain connection is located in the drain pan o...

Page 7: ...he 13 16 nut 1 turn only to allow the high pressure tracer gas to escape No gas indicates a possible leak 2 After the gas has escaped remove the nut and discard the cap 3 Use a tube cutter to remove t...

Page 8: ...ficiency We have designed these units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Fi...

Reviews: