31
11~22: Heating test, heating
mode takes effect
33
Whether the compressor overload
switch is enabled
0
0
255
Compound options:
0: Disable compressor overload
+ AC 2nd gear
1: Enable compressor ov
AC 2nd gear
2: Disable compressor overload
+ AC 1st gear
3: Enable compressor ov
AC 1st gear
34
None
0
0
255
1: enable
0: disable
35
Cooling inlet and outlet water
temperature difference protection
value/
℃
13
0
255
36
Heating inlet and outlet water
temperature difference protection
value/
℃
13
0
255
37
Maximum operating frequency of
cooling/Rps
70
0
255
38
Maximum operating frequency of
heating/Rps
80
0
255
39
Upper limit of frequency hopping
point 1 /Rps
255
0
255
255 means the setting is
invalid
40
Lower limit of frequency hopping
point 1/Rps
255
0
255
255 means the setting is
invalid
41
Upper limit value of frequency
hopping point 2 /Rps
255
0
255
255 means the setting is
invalid
42
Lower limit of frequency hopping
point 2 /Rps
255
0
255
255 means the setting is
invalid
43
Heating outlet water temperature
correction/
℃
13
0
255
Actual
value
=
set
value-10
℃
44
Cooling return water temperature
correction/
℃
10
0
255
Actual
value
=
set
value-10
℃
45
Cooling suction overheat Kd
correction value 1/
℃
7
0
255
Actual
value
=
set
value-10
℃
46
Cooling suction overheat Kd
correction value 2/
℃
9
0
255
Actual
value
=
set
value-10
℃
47
Cooling suction overheat Kd
correction value 3/
℃
10
0
255
Actual
value
=
set
value-10
℃
48
Cooling suction overheat Kd
11
0
255
Actual
value
=
set
Summary of Contents for NL-BKDX100-400II/R
Page 1: ...1...
Page 7: ...7 NL BKDX50 200II R NL BKDX60 220II R NL BKDX50 200II R32...
Page 8: ...8 NL BKDX80 300II R NL BKDX100 400II R...
Page 18: ...18 7 Connection diagram...