30
10
Whether heating auxiliary electric
heating is enabled
1
0
255
1: enable
0: disable
11
Cooling or heating water circuit
auxiliary electric heating start
ambient temperature /
℃
30
0
255
Actual temperature = set
temperature-50
℃
12
Whether water circuit auxiliary
heating of hot water is enabled
1
0
255
1: enable
0: disable
13
Hot
water
sterilization
temperature/
℃
65
0
255
14
Hot water sterilization cycle/day
10
0
255
15
Hot water sterilization retention
time/min
2
0
255
16
Outdoor ambient
temperature
Tao/
℃
0
255
Read only
17
Suction temperature Ts/
℃
0
255
Read only
18
Defrosting
coil
temperature
Tdef/
℃
0
255
Read only
19
Exhaust temperature Td/
℃
0
255
Read only
20
Opening
degree
of
main
electronic
expansion
valve
PMV1/PLS
0
255
Read only
21
Injection
enthalpy
electronic
expansion valve PMV2/PLS
0
255
Read only
22
Inverter compressor operating
frequency/Rps
0
255
Read only
23
Return water temperature/
℃
0
255
Read only
24
Outlet water temperature/
℃
0
255
Read only
25
Compressor fault code
0
255
Read only
26
External machine main control
fault code
0
255
Read only
27
Main control fault code
0
255
Read only
28
Reserved
0
255
Read only
29
Reserved
0
255
Read only
30
Air
conditioning
mode
type
selection
0
0
255
0: heating and cooling / 1:
cooling only / 2: heating only
31
Water pump shut down type
(Active only for terminal pump is
connected )
0
0
255
0: Water pump will be not
stopped
1: Water pump will be
stopped until reach setting
temperature
32
Energy efficiency test selection,
no memory
0
0
255
0: Not enabled
1~4: Cooling test, cooling
mode takes effect