TROUBLESHOOTING HINTS

An easy way to check that the system is working properly is to disconnect the wiring from the door 
panel and to check the monitor directly connected to the EL500/V2Plus circuit

A short circuit between different terminals of the installation will never damage the connected systems

Nothing operates

Remember that the system remains inactive for 30 seconds after connecting the power 

supply, the same occurs upon connecting any unit to the installation

Check that the power supply's output voltage between the –

terminals is

If not, disconnect the power supply from the installation and measure again If it's 
correct now, it means there is a short circuit in the installation Disconnect the power 
supply from mains and check the installation

If these tests don't solve the problem, check the voltage between the

terminals of 

the

microprocessor module; if the voltage is not 12 Vd.c. then replace the 

EL500/V2Plus

If the previous verifications are correct then check the autodiagnostic LEDs (see page 83)

Inappropriate audio level

Adjust the audio levels as shown on page 84

Audio feedback

Lower the volume of the sound module, using as well, the potentiometer located in the

microprocessor module as shown on page 84

If feedback doesn't disappear refer to the following hint

Continuous audio feedback

w

Check for short circuits in the BUS itself or between the BUS and any other terminal.

Door open function don't work

Remember that this function is only available during call and communication progresses
Create a short circuit between the

terminals of the

microprocessor module; once done, there should be 12 Vd.c. between the lock release 
terminals If so, check the lock release and its wiring

The system cannot be programmed

Check that the switch number 2 of the configuration dip switch is set to ON (see page 83) 

and that the programming steps are correctly followed

the autodiagnostic LEDs of the EL500/V2Plus microprocessor module (see page 83)

Some units don't receive calls

Remember that each apartment must have only one terminal programmed as master

Check that the terminal is correctly programmed; if necessary, program it again

dip switch is configured

Push buttons don't work

When the push button is pressed check that the door panel reproduce a confirmation tone; 

if not, check the wiring of the push buttons (pages 80 and 81)

If there is a confirmation tone, check the programming of the monitors (page 90) and the 

telephones (page 93).

.

.

O

.

w

.

w

 ' ' and '+' 

 

Vd.c. 

.

w

With system in rest, check the voltage between 

. If not, disconnect the 

 in any point of the installation.

w

 

w

O

.

w

 

O

.

w

 

               EL500/V2Plus 

.

               

.

O

.

O

.

w

.

w

 'CV1' and 'CV2' 

 EL500/V2Plus 

 

. .

O

.

w

.

w

Check .

O

.

w

O

Some monitors are not OK the image.

w

Check in the monitor the Sw2 

 (see page 87).

O

.

w

.

w

25,5 

'Bus' terminals of the EL500/V2Plus 

microprocessor module is from 23Vdc to 25,5 Vdc

'Bus' wires and 

verify there is not a short circuit or anomaly

'–' and '+12' 

 EL500/V2Plus 

 

.

.

.

107

108

NOTAS/NOTES

Summary of Contents for V2PLUS

Page 1: ...V2PLUS Video door entry system with unpolarised 2 wire installation Instructions manual TV2PLUS ML rev 0210...

Page 2: ...ing Final adjustments Closing the door panel Power supply installation Lock release installation Platea V2Plus monitor Function push buttons Identification label 87 88 89 90 T 7822VD Description 91 91...

Page 3: ...t call tones which identify the call procedure door panel or apartment door wInput for external door bell push button being necessary the use of digital converter CD V2Plus Up to 120 apartments and 12...

Page 4: ...sh buttons module CE embedding boxes 6xx Sound module EL530 EL531 EL540 on video systems with color camera on audio systems on video systems with b w camera Microprocessor circuit 75 on audio and vide...

Page 5: ...s service life it is recommended to take additional precautions visors covered areas To obtain a quality image on video door entry systems avoid direct incidence from light sources sun street lights 1...

Page 6: ...el modules A Insert the header DOWN marked in the lower module and fix it by screwing the module shafts Place the module spacer between lower and next modules assuring that the spacer adjustment notch...

Page 7: ...he top of the embedding box Insert the circuit in the top flanges of the embedding box 1 Push in the circuit in the bottom flanges 2 by pressing the pcb board To assemble the EL516 encoder screw the t...

Page 8: ...ssed through the header clips as shown For example if the hinges are placed on both clips of the lower header the door panel will open downwards if they are placed on the right clips of both headers t...

Page 9: ...h buttons modules The common terminal of the push buttons contained in a module are linked from factory This wire must be connected to the CP terminal of the EL500 V2PLUS microprocessor module and to...

Page 10: ...nect B terminal to the B terminal of the encoders Link the different push buttons common terminals of all the push buttons modules as shown in diagram Link the push button inputs P1 P8 to the push but...

Page 11: ...5 15 15 15 15 106 0 15 15 15 15 15 15 15 15 120 1 P2 1 P1 31 P4 61 P6 91 P8 16 P3 46 P5 76 P7 106 2 2 32 62 92 17 47 77 107 3 3 33 63 93 18 48 78 108 4 4 34 64 94 19 49 79 109 5 5 35 65 95 20 50 80 11...

Page 12: ...ach backbone must only have one door panel or CD V2Plus converter configured as the master DOOR PANEL INSTALLATION Set to ON the switch number 2 for monitor or telephones programming Once the programm...

Page 13: ...audio volume isn t correct proceed with the necessary adjustments as shown The telecamera has a pan and tilt mechanism If the orientation is not adequate then correct its position In case of low light...

Page 14: ...s Fix the with the specified screws power supply The power supply can be installed on a DIN 46277 guide simply pressing it To disassemble the power supply from the DIN guide use a plain screwdriver to...

Page 15: ...ast control colour control in colour monitors Brightness control depending on the model Inoperative push buttons Cord A Sw2 Dip switch Cable slot a g h b e k m l n d j c i CODIGO CODE SLAVE MASTER INT...

Page 16: ...monitor no function no function push button code see page no function MASTER m SLAVE 2 INTER A1 CODE 82 STAIR End of line and amplifying the video signal The Sw2 configuration dip switch is located o...

Page 17: ...ttachment hooks Vertical wiring input Attachment clip Central wiring input Installation terminals Digital communication bus input to monitor Digital communication bus output to additional monitor tele...

Page 18: ...ust be 5cm Place the monitor at right angles to the connection block and align the attaching holes of the monitor with the attachment hooks of the connection block as it is shown on the drawing Lock o...

Page 19: ...p the monitor s handset To show that the system is ready for programming the door panel and the monitor s handset will reproduce tones and an image will appear on the monitor Audio and video communica...

Page 20: ...dless of the position of the handset activate the PA and PB voltage free contacts with the JP1 jumper inserted see page 96 or activate the SAR 2plus unit if the JP2 jumper is inserted see page 96 this...

Page 21: ...s lose the telephone as shown on the picture Once the telephone is closed connect the handset using the telephone cord and put it on the cradle Avoid placing the telephone near sources of heat in dust...

Page 22: ...lel unit be it a monitor or telephone it must be configured as slave Make a call to check that the telephone has been successfully programmed Repeat these steps to program the rest of telephones Once...

Page 23: ...rs and the telephones incorporate as standards the call reception from the door bell push button This feature spares the use of a bell by placing a push button between the HZ monitor or telephone term...

Page 24: ...phones or call repeaters must never exceed three units Platea V2Plus BUS IN PA PB BUS OUT HZ BUS HZ PA S HZ PB S T 7822VD Platea V2Plus BUS IN PA PB BUS OUT HZ Platea V2Plus BUS IN PA PB BUS OUT HZ Ad...

Page 25: ...lues install a SAR 12 24 relay and TF 104 transformer as shown in the diagram PA and PB 40mA f Opening an additional door PRI SEC TF 104 Main Platea V2Plus BUS IN PA PB BUS OUT HZ JP1 JP2 JP1 JP2 BUS...

Page 26: ...AGRAMS 97 C onfiguring the end of line in the last monitor BUS IN PA PB BUS OUT HZ Platea V2Plus BUS IN PA PB BUS OUT HZ Platea V2Plus Sw2 Sw2 SEC PRI 0 110 230 FA V2PLUS Main Master door panel CV1 12...

Page 27: ...Door panel Monitor P S Door panel For greater distances contact our technical support department BUS D REMEMBER The total number of daisy chain elements in the installation monitors or telephones mus...

Page 28: ...s End of line BUS IN PA PB BUS OUT HZ BUS BUS D Platea V2Plus End of line R 120W Insert a 120 ohm end of line resistor in the last distributor D1L V2Plus Sw2 Sw2 Configuring the end of line in the las...

Page 29: ...nits Sections chart RAP 2150 Terminal SECTIONS CHART 100m Door panel Monitor P S Door panel For greater distances contact our technical support department BUS D 50m Door panel CV 50m 2 5mm 0 5mm IMPOR...

Page 30: ...lus BUS IN PA PB BUS OUT HZ BUS D2 D1 BUS D4 D3 End of line BUS D2 D1 BUS D4 BUS IN PA PB BUS OUT HZ Platea V2Plus BUS IN PA PB BUS OUT HZ R 120W D4L V2Plus Configuring the end of line in the last mon...

Page 31: ...its IMPORTANT In the output to the monitor telephone of a distributor cannot be connected another distributor Sections chart RAP 2150 Terminal SECTIONS CHART 100m Door panel Monitor P S Door panel For...

Page 32: ...120W D4L V2Plus INSTALLATION DIAGRAMS 103 BUS IN PA PB BUS OUT HZ BUS IN PA PB BUS OUT HZ Platea V2Plus Sw2 BUS IN PA PB BUS OUT HZ Platea V2Plus Sw2 Configuring the end of line in the last monitor P...

Page 33: ...istributor the total number of elements monitors or telephones distributed over all 4 outputs of the distributor must never exceed 32 units while one single output must never exceed 16 units 104 Maste...

Page 34: ...n the last distributor D4L V2Plus BUS IN PA PB BUS OUT HZ BUS D2 D1 BUS D4 D3 End of line BUS D2 D1 BUS D4 BUS IN PA PB BUS OUT HZ Platea V2Plus BUS IN PA PB BUS OUT HZ R 120W D4L V2Plus Configuring t...

Page 35: ...l For greater distances contact our technical support department BUS D 50m Door panel CV 50m 2 5mm CV1 CV2 1mm IMPORTANT In the output to the monitor telephone of a distributor cannot be connected ano...

Page 36: ...S itself or between the BUS and any other terminal Door open function don t work Remember that this function is only available during call and communication progresses Create a short circuit between t...

Reviews: