EXAMPLES FOR PROGRAMMING
Example 1: Basement tank for 6000 litres heating oil, litre indication, linear steel tank
Inner height 165 cm, (fill level 125 cm)
SmartBox
®
1Standard probe 0 - 250 mbar
Step
Entries / selection
1.Probe
250 mbar
2.Medium
Heat.oil
3.Tank shape
Linear
4.Tank volume
6000L
(set with [+] / [-] keys)
5.Inner tank height
165.0cm
(set with [+] / [-] keys)
6.Exit
press [Enter] to see the indication
Heat.oil
4.550 L
76 %
Example 2: Well, 7.50 m maximum water level from ground of the well, Display m
(fill level 4.20 m)
relay switching function is desired.
SmartBox
®
2
Standard probe 0 - 1000 mbar, indication in m water column
Relais 1 - On at 99 %-10 % - Off at < 10 %
Step
Entries / selection
1.Probe
1000 mbar
(set with [+] / [-] keys)
2.Medium
H2O
(set with [+] / [-] keys)
3.Tank shape
Linear
4.Max. value
7500 L
(set with [+] / [-] keys)
5.Inner tank height
7500 mm
(set with [+] / [-] keys)
6.Relay 1
active
On: 99 %
Off: 10 %
(set with [+] / [-] keys)
7.Relay 2
deactive
8.Exit
press [+] key to go to
12.Indicated unit
m
13.Rounding
automatic
14.Exit
press [Enter] to see the indication
H2O
4.20 m
56 %