Diagram 1 – Typical Generator Power Cord Connection

2.5.2  INSTALLATION BETWEEN INVERTER AND ALTERNATING SOURCE 

(

CONFIGURATION C

)

1.  For installation between inverter (default) and another power supply (dominant), such as the output from a prior power 

cord/ generator transfer switch.  These connections will allow any other supply to dominate the inverter, and the inverter 

output will pass through the normally closed contacts of the switch. This allows the inverter to operate only in the 

absence of the other power supplies, which is ideal for inverters.  Three AC sources require two transfer switches.

2.  Connect the inverter to terminals 7 and 8, and connect the other power supply (output from the first transfer switch) to 5 

and 6. Output terminals always remain the same. (See Diagram 1 above for number locations)

INSTALLATION

#1

#2

Summary of Contents for GP-TS-30

Page 1: ...nsfer Switch User Manual GP TS 30 2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP T...

Page 2: ...formation size install date battery type Product Packaging Please safely store the packing the IC Series was delivered in or recycle the packaging components as outlined below LDPE Low Density Polyeth...

Page 3: ...ric com page 3 CONTENTS 1 INTRODUCTION 4 2 INSTALLATION 4 3 OPERATIONAL TESTING 7 4 TROUBLESHOOTING 8 5 HI POT TESTING 9 6 GENERATOR NOTE 10 7 MEDICAL APPLIANCES 10 8 CAUTION 10 9 WARNINGS 10 10 WARRA...

Page 4: ...mpartment designed for storage of flammable liquids such as gasoline 2 3 ELECTRICAL PREPARATION Any numbered knockout on the TS 30 can be used for installation Choose a knockout that will facilitate i...

Page 5: ...IONS A B 1 Connect the power cord leads to terminal 7 and 8 on the narrow end of the relay these are the normally closed N C contacts See Diagram 1 on page 6 for numbered locations 2 Connect the gener...

Page 6: ...allow any other supply to dominate the inverter and the inverter output will pass through the normally closed contacts of the switch This allows the inverter to operate only in the absence of the othe...

Page 7: ...enerator There is a pre programmed 20 30 second delay in the transfer switch The delay is designed to allow the generator a brief warm up period When the delay completes its cycle the switch should en...

Page 8: ...o drop out at which point the voltage will rise to the pre in rush level The contacts will chatter when the A C compressor kicks in however the voltage may read normal Most meters are not fast enough...

Page 9: ...hould be performed from either the transfer switch output or from the main panel Test as follows 1 Turn on all circuit breakers in the panel 2 Make sure the generator is off 3 Make sure the power cord...

Page 10: ...tion may cause arcing In addition the act of turning on a light switch or unplugging the cord on an electrical appliance can cause a spark which can ignite any combustible liquids or vapors Therefore...

Page 11: ...lting from but not limited to Misuse and or abuse neglect or accident Exceeding the unit s design limits Improper installation including but not limited to improper environmental protection and improp...

Page 12: ...2020 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 MOBI_MAN_GP TS 30 RevE...

Reviews: