+24VDC
COM
Enter/Select Up/Down
Arrows
4)
1) Once ESFR connection is complete from fire
suppression system. Power up the drive.
a) Display should say "SToP".
2) Hold "Enter/Select" for 1 second.
a) Drive will enter programming mode.
b) PAr S (parameter short list) should be
displayed.
c) Press "Enter/Select".
d) Display should show 4 digits (they may
be "0000").
3) Use Up/Down Arrow Keys and locate
parameter 9902.
a) Press "Enter/Select" to select.
Use Up/Down Arrow Keys to change parameter
9902 setting to "6".
5)
6)
a) Press "Enter/Select" to save.
b) Display should return to parameter 9902.
Press and hold "Enter/Select" until display
reads "StoP". You have exited programming
mode.
Drive will immediately fault if ESFR signal is
missing.
This diagram is designed to take a PNP (Sourced) +24 VDC
signal from an ESFR fire suppression system. The ESFR
system will supply the +24 VDC power.
Run the +24 VDC signal wire to terminal 4 and route 0V COM to
terminal 7. There should be room in the terminal block to
accept both wires on terminal 7.
To enable the ESFR signal input see the programming steps
below. The drive will go into a fault condition once the 24VDC
signal is lost and will not allow fan operation until that signal
is restored.
GFY® Connection For ESFR Suppression System
ACS255
Controller - 100-120VAC & 200-240VAC Single Phase Applications
|
27
Z-TECH™
FAN
Installation and Technical Operations
®
GO FAN YOURSELF
Programming Instructions for GFY
®
ACS25
5
Controller - Enable ESFR Input