DO NOT RUN input and output power cables in the same conduit.
•
DO NOT RUN control cables with any power cables in the same conduit.
•
DO NOT RUN different fans output power cables in the same conduit.
•
You can run different fans input power cables in the same conduit.
Input Power
MUST be stranded
cable! Do NOT use
solid cable.
•
3 Ph use L1 – L2 – L3 + PE
(Ground)
•
1 Ph use L1 – L2 + PE
(Ground)
Wire Location
Minimum 1 FT
Power In
From Panel
Power Out
To Fan
NOTE: All single phase applications must be wired as 200-240VAC 3 phase applications from
the VFD controller to the fan motor. The controller will change the 1 phase power it is
receiving and supply 200-240VAC 3 phase power to the motor.
120VAC - L1 = Hot
- L2 = Neutral
240VAC - L1 = Hot
- L2 = Hot
|
25
Z-TECH™
FAN
Installation and Technical Operations
®
GO FAN YOURSELF