D6030 

- SIL 3 Switch/Proximity Detector Repeater Relay Output 

G.M. International ISM0213-2 

Line fault detection 

SW1 

Disabled 

(switch/proximity sensor)  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON 

SW5 

OFF 

ON 

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE 

(for SIL application) 

OFF 

D6030S Configuration Summary Table 

 

WARNING:

  Dip-switch 7-8 must be set to “OFF” position. 

IN/OUT Operation Output 1 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE 

(for SIL application) 

OFF 

D6030D (used as duplicator or fault output) Configuration Summary Table 

 

WARNING:

 Terminals 9-10 must be shorted to set module as Duplicator or Fault Out. Dip-switch 3 must be set to “OFF” position. 

Channel 

Line fault detection 

SW1 

SW5 

SW3 

Disabled 

(switch/proximity sensor) 

OFF OFF OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON ON ON 

1  

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE  

(for SIL application) 

OFF 

Channel 

SW4 

ON 

OFF 

D6030D (used as double channel) Configuration Summary Table 

 

WARNING:

 dip-switch 6-7-8 must be set to “OFF” position. 

Line fault detection 

SW1  

SW5 

Disabled 

(switch/proximity sensor)  

OFF  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

Output 1,  

(for SIL application) 

De-energized in Fault condition 

ON 

Output 1, 

Not specified Fault condition 

OFF 

ON  

Output 2 Operation 

SW6 

SW7  SW8 

Mode 

SW4 

Duplicator  

De-energized in 
fault condition 
(for SIL application) 
if line fault 
detection enabled 
(SW1 ON) 

ON 

OFF   ON  

Parallel 
(for SIL 

applica-

tion) 

Set equal 

to SW2 

Not specified 
Fault condition 

OFF Reverse 

Set opposite 

to SW2 

OFF  

(for SIL application) 

ON   OFF  

ND ON 

NE 

(for SIL 

applica-

tion) 

OFF 

Fault Output  

SW1  SW2  SW3  SW4  SW5  SW6  SW7  SW8 

OFF OFF OFF OFF OFF OFF OFF OFF 

DIP Switch factory settings (valid for D6030S and D6030D)

 

Configuration 

Summary of Contents for D6030D

Page 1: ...6030 SIL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0213 2 SIL 3 Switch Proximity Detector Repeater Relay Output DIN Rail Models D6030S D6030D D6030S D6030D INSTRUCTION MANUAL ...

Page 2: ...85 W for 2 channels D6030D 0 45 W for 1 channel D6030S with 24 V supply voltage short circuit input and relay energized typical Isolation Test Voltage In Out 2 5 KV In Supply 2 5 KV In In 500 V Out Supply 2 5 KV Out Out 2 5 KV Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range OFF 1 2 mA 0 4 to 1 3 mA range switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA s...

Page 3: ... used as fault indicator only 2nd ch Systematic capability SIL 3 2 fully independent channels High Density 2 channels per unit NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system In field programmability by DIP Switch TÜV ...

Page 4: ...oltage free contact required for line fault detection MODEL D5030D 5 6 1 2 Out 1 SIL 3 10 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 3 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5030D Duplicator or Fault Out 5 6 1 2 Out 1 SIL 3 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 Duplicator or Fault...

Page 5: ...ovable screw terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections Identify the number of channels of the specific card e g D6030S is a single channel model and D...

Page 6: ...mity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 NE 3 4 3 ND 4 Output 3 ND 4 Output NE 3 4 3 3 ON OFF 4 4 ON OFF Position in fault condition 3 4 1 2 3 4 5 6 7 8 ON Dip switch factory settings All Switches are OFF Input Input Output Input Output Input 2 CH1 Setting Line fault detection IN OUT Operat...

Page 7: ...Mode ON OFF OFF ON 2 ON 2 OFF Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output 2 Operation Input Input Output 1 Input Output 1 Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NE 1 2 1 ND 2 Output 1 1 ND 2 Output 1 NE 1 2 NE 3 4 3 ND 4 Set SW4 equal to SW2 Set SW4 opposite to SW2 6 ...

Page 8: ...g Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE 2 ON 2 OFF Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 1 OFF 5 OFF 1 ON 5 ON Input Input Input Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 Output 1 3 2 4 NE Output 1 3 2 4 NE Output 1 3 2 4 ND Output 2 4 ND 1 3 Position in fault condition 1 3 2 ...

Page 9: ... resistors detects field open circuit and short circuit de energizes relay in fault condition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D6030D used as double channel Configuration Summary Table WARNING dip switch 6 7 8 must be set to OFF position Line fault detection SW1 SW5 Disabled switch proximity sensor OFF OFF Enabled for S...

Reviews: