9
D6030
- SIL 3 Switch/Proximity Detector Repeater Relay Output
G.M. International ISM0213-2
Line fault detection
SW1
Disabled
(switch/proximity sensor)
OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
ON
SW5
OFF
ON
IN/OUT Operation
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
D6030S Configuration Summary Table
WARNING:
Dip-switch 7-8 must be set to “OFF” position.
IN/OUT Operation Output 1
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
D6030D (used as duplicator or fault output) Configuration Summary Table
WARNING:
Terminals 9-10 must be shorted to set module as Duplicator or Fault Out. Dip-switch 3 must be set to “OFF” position.
Channel
2
Line fault detection
SW1
SW5
SW3
Disabled
(switch/proximity sensor)
OFF OFF OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
ON ON ON
1
IN/OUT Operation
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
Channel
1
2
SW4
ON
OFF
D6030D (used as double channel) Configuration Summary Table
WARNING:
dip-switch 6-7-8 must be set to “OFF” position.
Line fault detection
SW1
SW5
Disabled
(switch/proximity sensor)
OFF
OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
Output 1,
(for SIL application)
De-energized in Fault condition
ON
Output 1,
Not specified Fault condition
OFF
ON
Output 2 Operation
SW6
SW7 SW8
Mode
SW4
Duplicator
De-energized in
fault condition
(for SIL application)
if line fault
detection enabled
(SW1 ON)
ON
OFF ON
Parallel
(for SIL
applica-
tion)
Set equal
to SW2
Not specified
Fault condition
OFF Reverse
Set opposite
to SW2
OFF
(for SIL application)
ON OFF
ND ON
NE
(for SIL
applica-
tion)
OFF
Fault Output
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
OFF OFF OFF OFF OFF OFF OFF OFF
DIP Switch factory settings (valid for D6030S and D6030D)
Configuration