background image

 

D5290 

- 10 A SIL 3 Relay Output Module for NE Load 

G.M. International ISM0111-8 

 

 

 

Technical Data 

Characteristics 

Input: 

24 Vdc nom (21.6 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

The following monitoring circuits are mutually exclusive:

 

1) 

Line input monitoring (DIP-Switch selectable):

 to allow DCS/PLC line monitoring function (pulse test). 

2) 

Voltage monitoring (DIP-Switch selectable):

 

 21.6 Vdc for normal operation, 

 17 Vdc reflects a high impedance (

 10 mA consumption) to the control device. 

3) Short circuit fault detection 

(DIP-Switch selectable):

 to allow DCS/PLC to detect short circuit fault of module. 

Current consumption @ 24 V:

 60 mA with relay energized, typical. 

Power dissipation:

 1.5 W with 24 V input voltage, relay energized, typical. 

Isolation (Test Voltage): 

Input / All Outputs 2.5 KV ; Out 1 / Out 2: 500V. 

Output: 

1 voltage free SPDT relay contact identified with outputs: Out 1 (NO contact) terminals 13-21 and Service Load Out (NC contact) terminals 13-15; 

 

1 voltage free SPST relay contact identified with output Out 2 (NO contact) terminals 14-22. 

Terminals 13-21 (Out 1) and 14-22 (Out 2) are open when relay is de-energized, closed in energized relay condition. 

Service load output (not SIL) at terminals 13-15 is normally close when relay is de-energized, open in energized relay condition. 

Contact material: 

Ag Alloy (Cd free) or AgSnO

2

Contact rating: 

10 A 250 Vac 2500 VA, 10 A 250 Vdc 300 W (resistive load). 

Contact inrush current: 

16 A at 24 Vdc, 250 Vac. 

DC Load breaking capacity: 

  Mechanical / Electrical life: 

10 * 10

6

 / 5 * 10

4

 operation, typical. 

Operate / Release time: 

8 / 4 ms typical. 

Bounce time NO / NC contact: 

4 / 6 ms, typical. 

Frequency response: 

10 Hz maximum.

 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 60 °C, relative humidity 95 %, up to 55 °C. 

Storage:

 temperature limits - 45 to + 80 °C. 

Safety Description:

 

ATEX:

 II 3G Ex nA nC IIC T4 Gc 

IECEx / INMETRO / NEPSI:

 Ex nA nC IIC T4 Gc 

FM: 

NI / I / 2 / ABCD /T4, I / 2 / AEx nA nC / IIC /T4 

FMC: 

NI / I / 2 / ABCD /T4, I / 2 / Ex nA nC / IIC /T4 

EAC-EX: 

2ExnAnCIICT4 X. 

UKR TR n. 898:

 2ExnAnCIICT4 X. 

non-sparking electrical equipment. -40 °C 

 Ta 

 70 °C. 

Approvals: 

BVS 10 ATEX E 114 conforms to EN60079-0, EN60079-15. 

IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-15. 

INMETRO DNV 13.0109 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-15. 

UL & C-UL E477485 conforms to ANSI/UL508 

FM 3046304 and FMC 3046304C conforms to Class 3600, 3611, 3810, ANSI/ISA-60079-0, ANSI/ISA-60079-15, C22.2 No.142, C22.2 No.213, C22.2 No. 60079-0, C22.2 No. 60079-15. 

C-IT.ME92.B.00206 conforms to GOST 30852.0, 30852.14. 

C

Ц

 16.0036 X conforms to 

ДСТУ

 7113, 

ДСТУ

 I

ЕС

 60079-15. 

GYJ14.1406X conforms to GB3836.1, GB3836.8. 

TÜV Certificate No. C-IS-236198-04, SIL 3 conforms to IEC61508:2010 Ed.2. 

TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

DNV Type Approval Certificate No.A-13625 and KR No.MIL20769-EL002 Certificates for maritime applications. 

Mounting:

 

T35 DIN-Rail according to EN50022 or on customized Termination Board. 

Weight:

 about 165 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4. 

Protection class:

 IP 20. 

Dimensions: 

Width 22.5 mm, Depth 123 mm, Height 120 mm. 

General Description: 

The single channel Relay Output, D5090S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 

for high risk industries. It provides isolation between input and output contacts. 
Three mutually exclusive (by DIP-Switch programming) monitoring circuits are provided: 
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, 
   executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering; 
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold; 
3) short circuit fault detection: when enabled, it allows DCS/PLC to detect short circuit fault of module. 
D5290S provides two NO contacts for normally energized load and a NC contact for service purpose, in order to switch the NE load on both supply lines. 
See the following pages for Functional Safety applications with related SIL value. Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous 
Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2. 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

3

Resistive 

Load

4 5

10

250

FSM

SIL 3

Summary of Contents for D5290S

Page 1: ...D5290 10 A SIL 3 Relay Output Module for NE Load G M International ISM0111 8 10 A SIL 3 Relay Output Module for NE Load DIN Rail and Termination Board Model D5290S D5290S INSTRUCTION SAFETY MANUAL...

Page 2: ...508 FM 3046304 and FMC 3046304C conforms to Class 3600 3611 3810 ANSI ISA 60079 0 ANSI ISA 60079 15 C22 2 No 142 C22 2 No 213 C22 2 No 60079 0 C22 2 No 60079 15 C IT ME92 B 00206 conforms to GOST 3085...

Page 3: ...1 for safety system ATEX IECEx UL C UL FM FM C INMETRO EAC EX UKR TR n 898 NEPSI T V Certifications T V Functional Safety Certification Type Approval Certificate DNV for marine applications Simplified...

Page 4: ...energized position Terminals 13 21 and 14 22 are open terminal 13 15 is closed MODEL D5290S Out 1 NO contact NO2 21 CM1 13 NC1 15 In 1 2 3 4 Service Load Termination board connector Not SIL Out 2 NO...

Page 5: ...to go to the defined fail safe state so that the output load remains energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe fa...

Page 6: ...to go to the defined fail safe state so that the output load remains energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe f...

Page 7: ...d by polarized plug in removable screw terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardou...

Page 8: ...LC line input monitoring function driving line pulse testing 2 low voltage input monitoring UVLO under voltage lock out module reflects a high impedance state to the control unit when the driving volt...

Reviews: