background image

 

D5290 

- 10 A SIL 3 Relay Output Module for NE Load 

G.M. International ISM0111-8 

 

13 

15 

21 

Application D5290S - SIL 3 Load Normally Energized Condition (NE) and Normally Energized Relay, 

with interruption of both load supply lines  

PLC 

Output ON 

24 Vdc 

Normal state operation 

De-energized to trip operation 

 

NE 
Load 
SIL 3 

22 

14 

Service 

Load 

(Not SIL) 

13 

15 

21 

PLC 

Output OFF 

0 Vdc 

 

NE 
Load 
SIL 3 

22 

14 

Service 

Load 

(Not SIL) 

- / AC 

+ / AC 

+ / AC 

- / AC 

Functional Safety Manual and Applications 

1) 

Description:

  

Input Signal from PLC/DCS is normally High (24 Vdc) and is applied to pins 1-2 or 3-4 in order to Normally Energize (NE) the internal relays. 
Input Signal from PLC/DCS is Low (0 Vdc) during “de-energize to trip” operation, in order de-energize the internal relays. 
The Load is Normally Energized (NE), therefore its safe state is to be de-energized; the Service Load is normally de-energized, therefore it energizes during  
“de-energized to trip” operation. 

 

Disconnection of the NE Load is done on both supply lines. 

 

The following table describes the status (open or closed) of each output contact when the input signal is High or Low. 

 

Safety Function and Failure behavior:

  

D5290S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. 
In the 1st Functional Safety application, the normal state operation of relay module is energized, with NE (Normally Energized) load.  
In case of alarm or request from process, the relay module is de-energized (safe state), de-energizing the load.  
The failure behaviour of the relay module is described by the following definitions: 
 

 fail-Safe State: it is defined as the output load being de-energized; 

 

 fail Safe: this failure causes the system to go to the defined fail-safe state without a process demand; 

 

 fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state),  

   

    so that the output load remains energized. 

 

 fail “No effect”: failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor a dangerous failure; 

 

    When calculating the SFF this failure mode is not taken into account. 

 

 fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness;  

   

    When calculating the SFF this failure mode is not taken into account. 

Failure rate date: taken from Siemens Standard SN29500. 

 

Failure rate table:

 

 

Failure rates table according to IEC 61508:2010 Ed.2 : 

 
 
 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 

10% of total SIF dangerous failures:      

 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures: 

 

Systematic capability SIL 3.

 

 

Operation

 

Input Signal

 

Pins 1-2 or 3-4

 

Pins

 

13- 21

 

Pins

 

14 - 22

 

Pins

 

13 - 15

 

NE Load (SIL3)

 

Pins 21 - 22

 

Service Load (Not SIL)

 

Pins 15 — - / AC Supply

 

Normal 

High (24 Vdc) 

Closed  Closed Open 

Energized 

De-Energized 

Trip 

Low (0 Vdc) 

Open 

Open 

Closed De-Energized 

Energized 

 

Failure category

 

Failure rates (FIT)

 

λ

dd

 = Total Dangerous Detected failures 

0.00 

λ

du

 = Total Dangerous Undetected failures 

1.60 

λ

sd

 = Total Safe Detected failures 

0.00 

λ

su

 = Total Safe Undetected failures 

191.40 

λ

tot safe

 = Total Failure Rate (Safety Function) = 

λ

dd

 + 

λ

du

 + 

λ

sd

 + 

λ

su

 

193.00

 

MTBF (safety function, single channel) = (1 / 

λ

tot safe

) + MTTR (8 hours)

 

591 years

 

λ

no effect

 = “No effect” failures 

209.60 

λ

not part

 = “Not Part” failures 

0.00 

λ

tot device

 = Total Failure Rate (Device) = 

λ

tot safe

 + 

λ

no effect

 + 

λ

not part

 

402.60

 

MTBF (device, single channel) = (1 / 

λ

tot device

) + MTTR (8 hours)

 

283 years

 

MTTF

S

 (Total Safe) = 1 / (

λ

sd

 + 

λ

su

596 years 

MTTF

D

 (Dangerous) = 1 / 

λ

du

 

71347 years 

 

T[Proof] = 1 year

 

T[Proof] = 14 years

 

PFDavg = 7.01 E-06 - Valid for 

SIL 3

 

PFDavg = 9.81 E-05 - Valid for 

SIL 3

 

 

T[Proof] = 20 years

 

PFDavg = 1.40 E-04 - Valid for 

SIL 3

 

λ

sd

 

λ

su

 

λ

dd

 

λ

du

 

SFF

 

0.00 FIT 

191.40 FIT 

0.00 FIT 

1.60 FIT 

99.17% 

Summary of Contents for D5290S

Page 1: ...D5290 10 A SIL 3 Relay Output Module for NE Load G M International ISM0111 8 10 A SIL 3 Relay Output Module for NE Load DIN Rail and Termination Board Model D5290S D5290S INSTRUCTION SAFETY MANUAL...

Page 2: ...508 FM 3046304 and FMC 3046304C conforms to Class 3600 3611 3810 ANSI ISA 60079 0 ANSI ISA 60079 15 C22 2 No 142 C22 2 No 213 C22 2 No 60079 0 C22 2 No 60079 15 C IT ME92 B 00206 conforms to GOST 3085...

Page 3: ...1 for safety system ATEX IECEx UL C UL FM FM C INMETRO EAC EX UKR TR n 898 NEPSI T V Certifications T V Functional Safety Certification Type Approval Certificate DNV for marine applications Simplified...

Page 4: ...energized position Terminals 13 21 and 14 22 are open terminal 13 15 is closed MODEL D5290S Out 1 NO contact NO2 21 CM1 13 NC1 15 In 1 2 3 4 Service Load Termination board connector Not SIL Out 2 NO...

Page 5: ...to go to the defined fail safe state so that the output load remains energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe fa...

Page 6: ...to go to the defined fail safe state so that the output load remains energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe f...

Page 7: ...d by polarized plug in removable screw terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardou...

Page 8: ...LC line input monitoring function driving line pulse testing 2 low voltage input monitoring UVLO under voltage lock out module reflects a high impedance state to the control unit when the driving volt...