D5034 

- SIL 3 Switch/Proximity Interface 

G.M. International ISM0113-7 

General Description:

 The single and dual channel Switch/Proximity Detector Interface, D5034S and D5034D is a high integrity repeater, designed to interface contacts or proximity 

detectors (EN60947-5-6, NAMUR) located in Hazardous Area and is suitable for applications requiring SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for 
high risk industries. 
Field loop integrity and status (line plus contact or proximitor) are continuously and directly monitored, in transparent mode, into the PLC, ESD, DCS using their existing input line, 
without requiring an additional channel for line fault detection. 
PLC / DCS can detect the following conditions: 
0.5 to 1.3 mA 

Input open condition 

2.0 to 6.0 mA 

Input close condition 

0 to 0.4 mA 

Input fault condition (Line break) 

6.5 to 8.0 mA 

Input fault condition (Short circuit) 

These are automatically detected for proximity switches inputs. 
For contact inputs is necessary to install end of line resistors close to the contacts. 
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards, in Safe Area or in Zone 2. 

 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. 

 

 

 

Technical Data 

Characteristics 

Supply:

 24 Vdc nom (18 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp, 2 A time lag fuse internally protected. 

Current consumption @ 24 V:

 30 mA for 2 channels D5034D, 15 mA for 1 channel D5034S with short circuit input, typical. 

Power dissipation:

 0.72 W for 2 channels D5034D, 0.36 W for 1 channel D5034S with 24 V supply voltage and short circuit input, typical. 

Isolation (Test Voltage): 

I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. 

Input:

 

Current levels: 

 0.1 mA to 

 8.0 mA 

 

Input equivalent source: 

8 V 1 K

 typical (8 V no load, 8 mA short circuit). 

Output:

 0.1 to 8.0 mA in sink mode, V max. 30 V, current limited at 

 8 mA, repeats input current level. 

Response time:

 

1 ms (0 to 100 % step change). 

Output ripple:

 

 20 mVrms. 

Power dissipation:

 0.4 W for 2 channels D5034D, 0.2 W for 1 channel D5034S short circuit input/output and 24 Vdc loop voltage, typical. 

Performance:

 Ref. Conditions 24 V supply, 23 ± 1 °C ambient temperature. 

Calibration accuracy: 

 ± 0.25 % of full scale. 

Linearity error: 

 ± 0.25 % of full scale. 

Supply voltage influence: 

 ± 0.05 % of full scale for a min to max supply change. 

Load influence: 

 ± 0.05 % of full scale for a 0 to 100 % load resistance change. 

Temperature influence: 

 ± 0.03 % of full scale on zero and span for a 1 °C change. 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions:

 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Storage:

 

temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I 

IECEx / INMETRO / NEPSI:

 Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, 

UL:

 NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nA [ia Ga] IIC T4 Gc 

C-UL:

 NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nA [ia Ga] IIC T4 Gc 

FM: 

NI-AIS / I / 2 / ABCD /T4, AIS / I,II,III / 1 / ABCDEFG, I / 2 / AEx nA [ia] / IIC /T4 

FMC: 

NI-AIS / I / 2 / ABCD /T4, AIS / I,II,III / 1 / ABCDEFG, I / 2 / Ex nA [ia] / IIC /T4

 

EAC-EX: 

2ExnA[ia]IICT4 X 

UKR TR n. 898:

 2ExnAiaIICT4 X, ExiaI X 

associated apparatus and non-sparking electrical equipment. 
Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10. 
Um = 250 Vrms, -40 °C 

 Ta 

 70 °C. 

Approvals: 

BVS 10 ATEX E 113 X conforms to EN60079-0, EN60079-11, EN60079-15. 
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-11, IEC60079-15. 
INMETRO DNV 13.0109 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26. 
UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15, 
ANSI/ISA 12.12.01 for UL and CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11, CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL. 
FM 3046304 and FMC 3046304C conforms to Class 3600, 3610, 3810, 3611,  
ANSI/ISA-60079-0, ANSI/ISA-60079-11, ANSI/ISA-60079-15, C22.2 No.142, C22.2 No.157, C22.2 No.213, C22.2 No. 60079-0, C22.2 No. 60079-11, C22.2 No. 60079-15. 
C-IT.ME92.B.00206 conforms to GOST 30852.0, 30852.10, 30852.14. 
C

Ц

 16.0036 X conforms to 

ДСТУ

 7113, 

ГОСТ

 22782.5-78, 

ДСТУ

 I

ЕС

 60079-15. 

GYJ14.1406X conforms to GB3836.1, GB3836.4; GB3836.8, GB3836.20. 
TÜV Certificate No. C-IS-236198-04, SIL 2 / SIL 3 conforms to IEC61508:2010 Ed. 2. 
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 
DNV No.A-13625 and KR No. MIL20769-EL002 Certificates for maritime applications. 

Mounting:

 

T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. 

Weight:

 about 140 g D5034D, 115 g D5034S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4. 

Protection class:

 IP 20. 

Dimensions: 

Width 12.5 mm, Depth 123 mm, Height 120 mm. 

FSM

SIL 3

Summary of Contents for D5034S

Page 1: ...D5034 SIL 3 Switch Proximity Interface G M International ISM0113 7 SIL 3 Switch Proximity Interface DIN Rail and Termination Board Models D5034S D5034D D5034S D5034D INSTRUCTION SAFETY MANUAL...

Page 2: ...to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 03 of full scale on zero and span for a 1 C change Compatibility CE mark compliant...

Page 3: ...TR n 898 NEPSI T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications High Density two channels per unit Simplified installation using s...

Page 4: ...ve group See parameters indicated in the table below D5034 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 15 mA Ch1 Ch2 7 8 9 10 Po Po 39 mW Ii Imax Pi Pi D5034 Terminals D5034 Associated Apparatu...

Page 5: ...ector Power Bus PLC In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5034S 5 6 1 2 7 8 mA Out SIL 3 RL PLC Terminati...

Page 6: ...at causes the output signal to go above 7 mA as short circuit of input Assuming that the application program in the safety logic solver is configured to detect High failure and does not automatically...

Page 7: ...field in order to go to open connection condition equivalent to line breakage and verify that the output current of the repeater reaches low current value 0 35 mA This tests for possible quiescent cur...

Page 8: ...ew terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardous before servicing The wiring cables...

Reviews: