GMI D1093S Instruction & Safety Manual Download Page 7

 

D1093 

- SIL 3 Relay Output Module with Line and Load diagnostics 

G.M. International ISM0093-12 

The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic. This means that it is necessary to specify how dangerous undetected faults, which 
have been noted during the FMEDA, can be revealed during proof test.  
Proof test consists of the following steps: 

Testing procedure at T-proof 

 

Steps

 

Action

 

1

 

Bypass the safety-related PLC or take other appropriate action to avoid a false trip.

 

 

2

 

Supply diagnostic circuit (terminals “9-11” and “10-12”) and watch LEDs or fault output for verification. 
For D1093S single channel, verify input-output functionality for two different application: 

1.  normally energized (NE) loads (terminals “5” and “6”): supply input channel (terminals “13” & “14”) and verify that load is energized; then shutdown input 

channel and verify that load is de-energized (safe state). In both cases, if the load is disconnected (fault condition), the fault red LED must be lit and the fault 
output must be de-energized

 

2.  normally de-energized (ND) loads (terminals “7” & “8”): supply input channel (terminals “13” & “14”) and verify that load is energized (safe state); then 

shutdown input channel and verify that load is de-energized. In both cases, if load is disconnected (fault condition), the fault red LED must be lit and the fault 
output must be de-energized. 

3

 

Remove the bypass from the safety-related PLC or restore normal operation.

 

 

This test reveals almost 90 % of all possible Dangerous Undetected failures in the relay module. 

D1093 is an isolated electrical apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, Temperature Classification 
T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous Locations (according to 
EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, and connected to equipment 
with a maximum limit for AC power supply of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. For installation of the unit in a Class I, Division 2 or Class I, Zone 2 
location, the wiring between the control equipment and the D1093 electrical apparatus shall be accomplished via conduit connections or another acceptable Division 2, Zone 2 wiring 
method according to the NEC and the CEC. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1093 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standardsn 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules. De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when 
installed in Hazardous Area/ Hazardous Locations or unless area is known to be nonhazardous. 
 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. Warning: de-energize main power source (turn off power supply 
voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 
 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 

D1093 relay module is suitable for the switching of safety related circuits, providing isolation between the input and output contacts. 
D1093 provides 1 DPST contact for normally energized (NE) loads and 1 SPST contact for normally de-energized (ND) loads. In addition, there is a diagnostic circuit for line breakage 
and load operating anomaly detection in both NE and ND load conditions. 
The fault indication is provided by a SPST normally energized relay (normally close contact), which is de-energized (open contact) in case of line or load fault. 
The fault output, diagnostic circuit, input and output contacts are isolated each other. In fact, the diagnostic circuit is supplied from independent external power supply. 
A “POWER ON” green led lights when supply power is present. A “RELAY STATUS” yellow led lights when input is powered, showing that relay is energized and relay output contacts 
are closed. A “LINE FAULT” red led lights when line breakage and load operating anomaly is detected. 

 

D1093

Relay Output

FM Approved under

non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Control 

Equipment

15
16

13
14

Non-incendive 

Equipment

8

7

6

-

+

5

-

2

4

3

+

1

Non-incendive 

Equipment

+

9

12

10

11

-

-

+

+

-

Power Supply

Non-incendive 

Equipment

 

Summary of Contents for D1093S

Page 1: ...D1093 SIL 3 Relay Output Module with Line and Load diagnostics ISM0093 12 D1093S INSTRUCTION SAFETY MANUAL SIL 3 Relay Output Module with Line and Load diagnostics DIN Rail Model D1093S...

Page 2: ...ed 1 5 W Output voltage free relay contact normally open Contact material Ag Alloy Cd free Contact rating 3 A 250 Vac 750 VA 3 A 125 Vdc 120 W resistive load Contact inrush current 5 A at 30 Vdc 250 V...

Page 3: ...EN61000 6 4 EN61326 1 ATEX IECEx FM FM C EAC EX UKR TR n 898 T V Certifications Type Approval Certificate DNV for maritime applications TUV Certification for SIL TUV Functional Safety Certification H...

Page 4: ...C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 All relay contacts shown in de energized position MODEL D1093S In Out 1 B ND Load 3 4 1 2 5 6 7 8 Out 1 A NE Load Load Diag Fault Out Load Power DC AC max 12...

Page 5: ...ailure nor a dangerous failure When calculating the SFF this failure mode is not taken into account fail Not part failure mode of a component which is not part of the safety function but part of the c...

Page 6: ...lure nor a dangerous failure When calculating the SFF this failure mode is not taken into account fail Not part failure mode of a component which is not part of the safety function but part of the cir...

Page 7: ...apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Haza...

Page 8: ...nect output relay contacts checking the load rating to be within the contact maximum rating 3 A 250 Vac or 125 Vdc 750 VA 120 W resistive load If necessary to prevent relay contacts from damaging an e...

Reviews: