GMI D1093S Instruction & Safety Manual Download Page 4

 

D1093 

- SIL 3 Relay Output Module with Line and Load diagnostics 

G.M. International ISM0093-12 

 

Function Diagram 

SAFE AREA, ZONE 2 GROUP IIC T4, 

NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 

All relay contacts shown in de-energized position 

MODEL D1093S

In

+

Out 1-B ND Load

+ 3

- 4

+ 1

- 2

+ 5

- 6

+ 7

- 8

Out 1-A NE Load

Load
Diag.

Fault Out

Load Power DC/AC
max. 125 Vdc, 250 Vrms

15

16

13

14

9 +

10 -

11 +

12 -

Supply 24 Vdc

To prevent relay contacts from damaging, connect an external protection (fuse or similar),  

chosen according to the relay breaking capacity diagram. 

Summary of Contents for D1093S

Page 1: ...D1093 SIL 3 Relay Output Module with Line and Load diagnostics ISM0093 12 D1093S INSTRUCTION SAFETY MANUAL SIL 3 Relay Output Module with Line and Load diagnostics DIN Rail Model D1093S...

Page 2: ...ed 1 5 W Output voltage free relay contact normally open Contact material Ag Alloy Cd free Contact rating 3 A 250 Vac 750 VA 3 A 125 Vdc 120 W resistive load Contact inrush current 5 A at 30 Vdc 250 V...

Page 3: ...EN61000 6 4 EN61326 1 ATEX IECEx FM FM C EAC EX UKR TR n 898 T V Certifications Type Approval Certificate DNV for maritime applications TUV Certification for SIL TUV Functional Safety Certification H...

Page 4: ...C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 All relay contacts shown in de energized position MODEL D1093S In Out 1 B ND Load 3 4 1 2 5 6 7 8 Out 1 A NE Load Load Diag Fault Out Load Power DC AC max 12...

Page 5: ...ailure nor a dangerous failure When calculating the SFF this failure mode is not taken into account fail Not part failure mode of a component which is not part of the safety function but part of the c...

Page 6: ...lure nor a dangerous failure When calculating the SFF this failure mode is not taken into account fail Not part failure mode of a component which is not part of the safety function but part of the cir...

Page 7: ...apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Haza...

Page 8: ...nect output relay contacts checking the load rating to be within the contact maximum rating 3 A 250 Vac or 125 Vdc 750 VA 120 W resistive load If necessary to prevent relay contacts from damaging an e...