GMI D1093S Instruction & Safety Manual Download Page 3

 

D1093 

- SIL 3 Relay Output Module with Line and Load diagnostics 

G.M. International ISM0093-12 

Ordering information 

Model:  

D1093S 

Power Bus enclosure 

/B 

 

 

Front Panel and Features 



SIL 3 according to IEC 61508:2010 Ed. 2 

for Tproof = 14 / 20 years (

10% / >10 % of total SIF) with NE Load. 



SIL 3 according to IEC 61508:2010 Ed. 2 

for Tproof = 9 / 20 years (

10% / >10 % of total SIF) with ND Load. 



PFDavg (1 year) 7.02 E-06, SFF 99.03 % with NE Load. 



PFDavg (1 year) 1.03 E-05, SFF 97.61 % with ND Load. 



SIL 3 Systematic capability. 



Installation in Zone 2, Division 2. 



Line and Load open diagnostic in NE and ND conditions. 



1 DPST contact for NE load and 1 SPST contact for ND load. 



5 A inrush current at 30 Vdc / 250 Vac. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1. 



ATEX, IECEx, FM & FM-C, EAC-EX, UKR TR n. 898, TÜV Certifications. 



Type Approval Certificate DNV for maritime applications. 



TUV Certification for SIL. 



TUV Functional Safety Certification. 



High Reliability, SMD components. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 

+ Power Supply 24 Vdc 

Terminal block connections 

SAFE AREA 

SAFE AREA 

- Power Supply 24 Vdc 

+ Power Supply 24 Vdc 

- Power Supply 24 Vdc 

9

 

10

 

11

 

12

 

+ Loop Powered DC/AC maximum 125 Vdc, 250 Vrms 

1

 

- Loop Powered DC/AC maximum 125 Vdc, 250 Vrms 

2

 

+ Loop Powered DC/AC maximum 125 Vdc, 250 Vrms 

3

 

- Loop Powered DC/AC maximum 125 Vdc, 250 Vrms 

4

 

+ Output Ch 1-A for NE Load 

5

 

- Output Ch 1-A for NE Load 

6

 

+ Output Ch 1-B for ND Load 

7

 

- Output Ch 1-B for ND Load 

8

 

+ Input Ch 1 

- Input Ch 1 

Fault Output 

Fault Output 

13

 

14

 

15

 

16

 

Power Bus and DIN-Rail accessories: 
DIN rail anchor MCHP065   

DIN rail stopper MOR016 

Terminal block male MOR017 

Terminal block female MOR022 

Summary of Contents for D1093S

Page 1: ...D1093 SIL 3 Relay Output Module with Line and Load diagnostics ISM0093 12 D1093S INSTRUCTION SAFETY MANUAL SIL 3 Relay Output Module with Line and Load diagnostics DIN Rail Model D1093S...

Page 2: ...ed 1 5 W Output voltage free relay contact normally open Contact material Ag Alloy Cd free Contact rating 3 A 250 Vac 750 VA 3 A 125 Vdc 120 W resistive load Contact inrush current 5 A at 30 Vdc 250 V...

Page 3: ...EN61000 6 4 EN61326 1 ATEX IECEx FM FM C EAC EX UKR TR n 898 T V Certifications Type Approval Certificate DNV for maritime applications TUV Certification for SIL TUV Functional Safety Certification H...

Page 4: ...C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 All relay contacts shown in de energized position MODEL D1093S In Out 1 B ND Load 3 4 1 2 5 6 7 8 Out 1 A NE Load Load Diag Fault Out Load Power DC AC max 12...

Page 5: ...ailure nor a dangerous failure When calculating the SFF this failure mode is not taken into account fail Not part failure mode of a component which is not part of the safety function but part of the c...

Page 6: ...lure nor a dangerous failure When calculating the SFF this failure mode is not taken into account fail Not part failure mode of a component which is not part of the safety function but part of the cir...

Page 7: ...apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Haza...

Page 8: ...nect output relay contacts checking the load rating to be within the contact maximum rating 3 A 250 Vac or 125 Vdc 750 VA 120 W resistive load If necessary to prevent relay contacts from damaging an e...

Reviews: