D1061 

- RS422 / RS485 Fieldbus Isolating Repeater 

G.M. International ISM0068-12 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. 
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. 
Turn on power, the “power on” green led must be lit, transmission led should reflect the communication line activity. 

Installation 

 

D1061 is a RS232/RS422/RS485 fieldbus isolating repeater housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
D1061 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit 
without suffering or causing any damage; for RS232, RS422 and RS485 serial line connection in Safe Area, a SUB D 9 poles female connector is also provided 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in relation to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections and configuration DIP switches. 
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”. 
Connect field serial line type RS485 or receiving section of RS422 in Hazardous Area at terminal “13” and  “14” corresponding to A- and B+. 
In addition when using RS422 serial line, connect transmitting section at terminal “15” and “16” corresponding to A- and B+. 
Connect field serial line type RS485 or receiving section of RS422 in Safe Area at terminal “5” and  “6” corresponding to A- and B+. 
In addition when using RS422 serial line, connect transmitting section at terminal “7” and “8” corresponding to A- and B+. 
Safe Area side connection are also available on SUB D 9 poles female connector. 

Note:

 please pay attention to the serial cable used for Safe Area connection. The internal wiring of the cable must be straight. 

 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
The wiring between the Intrinsically Safe Equipment located in Hazardous Area/Hazardous Locations and the D1061 Associated Apparatus must have a minimum insulation 
thickness of 0.25 mm. 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1061 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D1061 series must be connected to SELV or SELV-E supplies. 

Summary of Contents for D1061S

Page 1: ...D1061 RS422 RS485 Fieldbus Isolating Repeater ISM0068 12 D1061S INSTRUCTION MANUAL RS422 RS485 Fieldbus Isolating Repeater Din Rail Model D1061S...

Page 2: ...ssion speed 1 2 2 4 4 8 9 6 14 4 19 2 38 4 57 6 93 75 115 2 187 5 375 500 750 Kbit s or 1 0 1 5 Mbit s DIP switch configurable RS422 RS485 Transmission cable length 1200 m up to 93 75 Kbit s 1000 m up...

Page 3: ...X IECEx FM FM C INMETRO EAC EX UKR TR n 898 Certifications Type Approval Certificate KR for marine applications High Reliability SMD components Simplified installation using standard DIN Rail and plug...

Page 4: ...13 14 15 16 Li Li device L cable Li Ri device and L cable R cable 15 16 13 14 15 16 13 14 15 16 When used with separate powered intrinsically safe devices check that maximum allowable voltage current...

Page 5: ...IC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1061S 13 14 15 3 4 5 6 7 Supply 24 Vdc 8 6 5 8 3 9 4 A B A 16 B...

Page 6: ...S I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1061S 13 14 15 3 4 5 6 7 Supply 24 Vdc 8 6 5 8 3 9 4 B A 16 9 10 31 A B 5 V SUB D 9 poles female connector RT RT 2 1 RT 31 2...

Page 7: ...T RS485 Field Devices From 200 to 1200 m depending on data rate MODEL D1061S 13 14 15 3 4 5 6 7 Supply 24 Vdc 8 6 5 8 3 9 4 B A 16 9 10 31 A B 5 V RT RT 2 1 RT RS485 Field Devices From 200 to 1200 m d...

Page 8: ...epaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation D1061 fieldbus isolating repeater prov...

Page 9: ...ct transmitting section at terminal 15 and 16 corresponding to A and B Connect field serial line type RS485 or receiving section of RS422 in Safe Area at terminal 5 and 6 corresponding to A and B In a...

Page 10: ...istors can also be configured Dip switch configuration Side A Panel View SW2 SW3 Safe Area Serial Line Connection Type RS232 RS422 5 V on pin 6 SUB D connector Unconnected pin 6 SUB D connector RS485...

Page 11: ...parity 1 stop bit 9 7 data bit no parity 2 stop bit 7 data bit odd parity 1 stop bit 7 data bit even parity 1 stop bit 8 data bit no parity 1 stop bit 10 10 10 10 OFF ON OFF OFF ON ON ON 7 data bit o...

Page 12: ...FF OFF OFF 187 500 ON OFF ON OFF 93 750 ON ON OFF OFF 115 200 ON ON ON ON 57 600 OFF OFF OFF ON 38 400 OFF OFF ON ON 19 200 OFF ON OFF ON 14 400 OFF ON ON ON 9 600 ON OFF OFF ON 4 800 ON OFF ON ON 2 4...