3
D1061
- RS422 / RS485 Fieldbus Isolating Repeater
G.M. International ISM0068-12
Ordering information
Model: D1061S
Power Bus enclosure
/B
Front Panel and Features
Input/Output from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
RS422 / RS485 Hazardous Area I.S. Signal.
RS232 / RS422 / RS485 Safe Area Signal.
Transmission speed up to 1.5 Mbit/s.
For Modbus, Fieldbus, Profibus and all other RS485 protocols.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4.
In-field programmability by DIP Switch.
ATEX, IECEx, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898 Certifications.
Type Approval Certificate KR for marine applications.
High Reliability, SMD components.
Simplified installation using standard DIN Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
D1061
1 2 3 4
9 10 11 12
16
15
14
13
5 6 7 8
PWR ON
Tx Rx
To shield
Terminal block connections
HAZARDOUS AREA
SAFE AREA
To shield
Not used
Not used
A - for IN/OUT RS485 orTxD RS422
B + for IN/OUT RS485 orTxD RS422
A - for RxD RS422
B - for RxD RS422
9
10
11
12
13
14
15
16
Not used
1
Not used
2
+ Power Supply 24 Vdc
3
- Power Supply 24 Vdc
4
A - for IN/OUT RS485 orTxD RS422
5
B + for IN/OUT RS485 orTxD RS422
6
A - for RxD RS422
7
B - for RxD RS422
8