D1053 

- SIL 2 Analog Signal Converter and Trip Amplifiers 

G.M. International ISM0016-13 

Parameters Table 

NOTE for USA and Canada: 

IIC equal to Gas Groups A, B, C, D, E, F and G 
IIB equal to Gas Groups C, D, E, F and G 

IIA equal to Gas Groups D, E, F and G 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1053 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.8 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1053 Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that 
added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas 
group. See parameters on

 

enclosure side and the ones indicated in the table below: 

When used with separate powered intrinsically safe devices, check that maximum allowable voltage (Ui/Vmax) of the D1053 Associated Apparatus are not exceeded by the safety 
parameters (Uo/Voc) of the Intrinsically Safe device, indicated in the table below: 

D1053 Terminals 

Ch1  14 - 15 - 16 

Io / Isc = 4 mA 

Ch1  14 - 15 - 16 

Po / Po = 11 mW 

Ch1  14 - 15 - 16 

 

Ii/ Imax 

 

Pi / Pi 

 

D1053 Terminals 

Ch1  14 - 15 - 16 

Ch1  14 - 15 - 16 

Ch1  14 - 15 - 16 

D1053 Associated 

Apparatus Parameters 

Ci / Ci  C cable 

 

Li / Li L cable 

 

Li / Ri device and 

L cable / R cable 

 

(IIC-A, B) 

Co / Ca = 2.135 µF 

Co / Ca = 14.995 µF 
Co / Ca = 65.995 µF 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / La = 2541 mH 

Lo / La = 10167 mH 
Lo / La = 20335 mH 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / Ro = 3520 µH/

 

Lo / Ro = 14090 µH/

 

Lo / Ro = 28180 µH/

 

(IIB-C) 
(IIA-D) 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system 
when the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1053 Associated 

Apparatus Parameters 

Ui / Vmax = 30V 

Uo / Voc 

D1053 Terminals 

Ch1  14 - 15 - 16 

 

Ci = 4.5 nF, Li= 0 nH 

Ch1  14 - 15 - 16 

 

Summary of Contents for D1053S

Page 1: ...D1053 SIL 2 Analog Signal Converter and Trip Amplifiers ISM0016 13 D1053S INSTRUCTION MANUAL SIL 2 Analog Signal Converter and Trip Amplifiers Din Rail Model D1053S ...

Page 2: ...ripple 20 mVrms on 250 Ω load Alarm Trip point range within rated limits of input sensor see input for step resolution Delay time 0 to 1000 s 100 ms step Hysteresis 0 to 5 mA on current or 0 to 5 V on voltage see input for step resolution Output voltage free SPST relay contact Contact rating 2 A 250 Vac 500 VA 2 A 250 Vdc 80 W resistive load Performance Ref Conditions 24 V supply 250 Ω load 23 1 C...

Page 3: ...inear or reverse Two independent trip amplifiers Output for burnout detection High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD componen...

Page 4: ...4 15 16 Io Isc 4 mA Ch1 14 15 16 Po Po 11 mW Ch1 14 15 16 Ii Imax Pi Pi D1053 Terminals Ch1 14 15 16 Ch1 14 15 16 Ch1 14 15 16 D1053 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 135 µF Co Ca 14 995 µF Co Ca 65 995 µF IIB C IIA D IIC A B Lo La 2541 mH Lo La 10167 mH Lo La 20335 mH IIB C IIA D IIC A B Lo Ro 3520 µH Ω Lo Ro...

Page 5: ... 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 I Signal 5 6 7 8 Alarm A Alarm B Set A Set B MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 V Signal 5 6 7 8 Alarm A Alarm B Set A Set B For SIL applications alarm contacts ...

Page 6: ...when connected to live hazardous potential Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his ...

Page 7: ...tional installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conducto...

Page 8: ... 12 V I dc mA dc input from externally powered transmitter range from 4 to 24 mA 8 Br LO 3 Level Menu Displays the burnout LOW trip point value configuration Press Enter to set the burnout condition trip point value below this value indicate a burnout fault condition set 5 000 to disable press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key y...

Page 9: ...n Press Enter to set the delay time value press the Select key to the next menu level item or Up key to return to third level If you pressed Enter key you can set the delay value 100 ms step press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key The value is settable from 0 to 1000 seconds in...

Reviews: