GMI D1053S Instruction Manual Download Page 3

 

D1053 

- SIL 2 Analog Signal Converter and Trip Amplifiers 

G.M. International ISM0016-13 

Front Panel and Features 

Ordering information 

Operating parameters are programmable by the GM Pocket Portable Configurator PPC1090 or via RS-232 serial line with PPC1092 Adapter and SWC1090 Configurator software. 
If the parameters are provided with the purchasing order the unit will be configured accordingly, otherwise the unit will be supplied with default parameters. 

Model:  

D1053S 

Power Bus enclosure 

/B 

 

 

 



SIL 2 according to IEC 61508, IEC 61511 using analog output or trip amplifiers for Tproof = 2 / 4 years (10 / 20 % of total SIF). 



PFDavg (1 year) 4.16 E-04, SFF 80 % using analog output. 



PFDavg (1 year) 4.11 E-04, SFF 82 % using trip amplifiers. 



Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2. 



0/4-20 mA, 0/1-5 V, 0/2-10 V Input-Output Signal linear or reverse. 



Two independent trip amplifiers. 



Output for burnout detection. 



High Accuracy, µP controlled A/D converter. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4. 



Fully programmable operating parameters. 



ATEX, IECEx, UL & C-UL, FM & FM-C, Russian and Ukrainian Certifications. 



Type Approval Certificate DNV and KR for marine applications. 



High Reliability, SMD components. 



High Density, one channel, 2 trips per unit. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

Not used 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

+ Input Ch 1 for Signal Voltage 

+ Input Ch 1 for Signal Current 

- Input Ch 1 for Signal Voltage or 
- Input Ch 1 for Signal Current 

13

 

14

 

15

 

16

 

+ Output Ch 1 for Current Source mode or 
+ Output Ch 1 for Voltage Source mode 

1

 

- Output Ch 1 for Current Source mode or 
- Output Ch 1 for Voltage Source mode 

2

 

+ Power Supply 24 Vdc 

3

 

- Power Supply 24 Vdc 

4

 

Alarm A 

5

 

Alarm A 

6

 

Alarm B 

7

 

Alarm B 

8

 

Summary of Contents for D1053S

Page 1: ...D1053 SIL 2 Analog Signal Converter and Trip Amplifiers ISM0016 13 D1053S INSTRUCTION MANUAL SIL 2 Analog Signal Converter and Trip Amplifiers Din Rail Model D1053S ...

Page 2: ...ripple 20 mVrms on 250 Ω load Alarm Trip point range within rated limits of input sensor see input for step resolution Delay time 0 to 1000 s 100 ms step Hysteresis 0 to 5 mA on current or 0 to 5 V on voltage see input for step resolution Output voltage free SPST relay contact Contact rating 2 A 250 Vac 500 VA 2 A 250 Vdc 80 W resistive load Performance Ref Conditions 24 V supply 250 Ω load 23 1 C...

Page 3: ...inear or reverse Two independent trip amplifiers Output for burnout detection High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD componen...

Page 4: ...4 15 16 Io Isc 4 mA Ch1 14 15 16 Po Po 11 mW Ch1 14 15 16 Ii Imax Pi Pi D1053 Terminals Ch1 14 15 16 Ch1 14 15 16 Ch1 14 15 16 D1053 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 135 µF Co Ca 14 995 µF Co Ca 65 995 µF IIB C IIA D IIC A B Lo La 2541 mH Lo La 10167 mH Lo La 20335 mH IIB C IIA D IIC A B Lo Ro 3520 µH Ω Lo Ro...

Page 5: ... 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 I Signal 5 6 7 8 Alarm A Alarm B Set A Set B MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 V Signal 5 6 7 8 Alarm A Alarm B Set A Set B For SIL applications alarm contacts ...

Page 6: ...when connected to live hazardous potential Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his ...

Page 7: ...tional installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conducto...

Page 8: ... 12 V I dc mA dc input from externally powered transmitter range from 4 to 24 mA 8 Br LO 3 Level Menu Displays the burnout LOW trip point value configuration Press Enter to set the burnout condition trip point value below this value indicate a burnout fault condition set 5 000 to disable press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key y...

Page 9: ...n Press Enter to set the delay time value press the Select key to the next menu level item or Up key to return to third level If you pressed Enter key you can set the delay value 100 ms step press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key The value is settable from 0 to 1000 seconds in...

Reviews: