D1032
- SIL 2 Switch / Proximity Detector Repeater Relay Output
G.M. International ISM0041-14
3
Ordering information
Front Panel and Features
SIL 2 according to IEC 61508:2010 Ed.2 for Tproof = 3 /10 years (
≤
10% / >10 % of total SIF).
PFDavg (1 year) 2.55 E-04, SFF 71.24 %.
SIL 3 Systematic capability.
Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
NO/NC contact/proximity Detector Input.
Four voltage free SPST Relay contact Output Signals.
Relay Output for fault detection on dual channel version.
Line fault detection with common signalling available when using Power Bus enclosure.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1.
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
High Reliability, SMD components.
High Density, four channels per unit.
Simplified installation using standard DIN Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
Model: D1032
2 channels
D
Power Bus enclosure
4 channels
Q
/B
Power Bus and DIN-Rail accessories:
DIN rail anchor MCHP065 DIN rail stopper MOR016
Terminal block male MOR017 Terminal block female MOR022