D1032 

- SIL 2 Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0041-14 

D1032 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous 
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, 
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1032 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1032 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Testing procedure at T-proof 

D1032 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

13
14

1
2

+

-

-

+

Power Supply

3
4

16

15

-

+

Intrinsically 

Safe Equipment

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

6

5

Control 

Equipment

Control 

Equipment

Control 

Equipment

2

6

8

7

Intrinsically 

Safe Equipment

-

+

10

9

Intrinsically 

Safe Equipment

+

-

11

12

+

-

Power Supply

Control 

Equipment

Control 

Equipment

Control 

Equipment

Control 

Equipment

14

9

11

12

10

16

15

13

4

3

2

7

8
6

2

6

5

1

+

-

+

+

-

-

-

+

Non-incendive

Equipment

Non-incendive

Equipment

Non-incendive

Equipment

Non-incendive

Equipment

D1032 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

The proof test must be performed to reveal dangerous faults which cannot be otherwise detected. This means that it is necessary to specify how dangerous undetected faults, which 

have been noted during the FMEDA analysis, can be revealed during the proof test. 

Note for input contacts: to detect a wire break or a short circuit condition, it is necessary to mount, in the input connections and close to the contacts, a 1k

Ω

 resistor in series and 

a 10 k

Ω

 resistor in parallel to the contacts. 

The 

Proof test

 consists of the following steps: 

 

This test will detect approximately 99% of possible Dangerous Undetected failures in the repeater. 

Steps

 

Action

 

1

 

Bypass the Safety-related PLC or take any other appropriate action to avoid a false trip. 

2

 

Vary the state conditions of the input sensors / contacts coming from field and verify that the transistor outputs change their state from energized to  
de-energized and vice-versa; also check that the de-energized state condition corresponds to the required Safety-related function. 

3

 

Disconnect the input wiring coming from the field sensor / contact and check that the corresponding wire break alarm output is de-energized. 

4

 

Short the input connections and verify that the corresponding outputs remains de-energized. In both cases, the corresponding alarm LEDs on the front 
panel must be turned red. 

5

 

Restore the loop to full operation. 

6

 

Remove the bypass from the Safety-related PLC or restore normal operation. 

Warning 

Summary of Contents for D1032D

Page 1: ...D1032 SIL 2 Switch Proximity Detector Repeater Relay Output ISM0041 14 D1032D D1032Q INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D1032D D1032Q...

Page 2: ...Supply 1 5 KV Out 1 3 Out 2 4 1 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enable...

Page 3: ...using Power Bus enclosure Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C INMETRO EAC...

Page 4: ...t Ch 3 7 Output Ch 4 8 D1032D Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1...

Page 5: ...16 Ch3 Ch4 9 10 11 12 Li Li device L cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Li Ri device and L cable R cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Co Ca 25 F NOTE for USA and Canada IIC equal t...

Page 6: ...SS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1032Q 13 14 3 4 1 2 Common Channels 1 3 Supply 24 Vdc Out 1 5 6 Common Channels 2 4 Out 2 7 Out 3 8 Out 4 15 16 9 10 11 12 2...

Page 7: ...ate condition for OFF operation while they are both closed or relay energized for ON operation Only Out 1 A and 2 A are functional safety related while Out 1 B as Out 1 A Duplicator and Out 2 B as Out...

Page 8: ...e open or closed of its output when its input signal is in OFF or ON state and it gives information about turn on or turn off of the related channel status LED and channel fault LED Failure category F...

Page 9: ...t T proof D1032 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T...

Page 10: ...mum rating 2 A 250 V 500 VA 80 W resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installati...

Page 11: ...th terminating line resistor ON CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON OFF Disabled contact proximity sensor Enabled proximity sensor or contact with ter...

Page 12: ...proximity sensor or contact with terminating line resistor OFF Input Output Input Output Output Input Output Input 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 7 ND 2 NE 7 2 7 ND 2 NE 7 2 Input Output Input...

Page 13: ...Input Output Output Input Output Input 13 NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 1 ND 2 NE 1 2 1 ND 2 NE 1 2 ND Mode NE Mode No Fault No Fault 7 ND 2 NE 7 2 Switch 4 positions Input Output Input Outp...

Page 14: ...E 8 6 Switch 4 positions Input Output Input Output 15 NO 16 NC 15 16 8 NE 6 ND 8 6 Switch 8 positions Input Output Input Output 15 NO 16 OR NC 15 16 8 ND 6 NE 8 6 ON Switch 8 positions OFF Switch 8 po...

Reviews: