7
D1010-054 / 056 / 057
- mV to mA Converter
G.M. International ISM0098-8
Configuration
Span
Screwdriver
for Trimmers
1 x 0.5 mm
Calibration Trimmers Channel
Zero
Turn the trimmer clockwise to
Increase Output value or turn
the trimmer counterclockwise
if you want to decrease Output
value.
Side A Panel View
Calibration instruction and Troubleshooting
In case a calibration check or readjustment is necessary the following equipment is required:
PS
Supply
=
_
Out 1
+
CAL
In 1
DMM mA
mV
MODELS D1010S-054, D1010S-056, D1010S-057
=
=
=
=
=
15
16
3 +
4 -
1
2
Connect the unit as shown below:
Set power supply (PS) at 24.0 V at terminals 3 (+) and 4 (-), the calibrator (CAL) in the function “mV” 100 mV range at terminals 15 (-) and 16 (+), the multimeter (DMM) for the reading
in DC supply 20 mA range at terminals 1 (+) and 2 (-).
Verify that green led on the front panel is ON.
If the power ON Led is off, check supply voltage, polarity and wiring.
Adjustable Power Supply Range 0-35 V Resolution 0.1 V,
Accuracy 1% Output Capability 200 mA
Current Meter range 20 mA, Resolution 1 µA Accuracy 0.01%
or Voltage Meter Range 10 V, Resolution 1 mV Accuracy 0.01%
Current Calibrator range 100 mV, Resolution 1 µV Accuracy 0.01 %
Agilent
E3611A
Agilent
Yokogawa
7651
Equipment Required
Instrument
PS
DMM
CAL
Identification