D1010-054 / 056 / 057 

- mV to mA Converter 

G.M. International ISM0098-8 

Parameters Table 

Must 

be 

Hazardous Area 

Device Parameters 

D1010-054, D1010-056, D1010-057 

Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area 

Cable Parameters 

Uo / Voc = 1.1 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the 
Hazardous Area and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters 
(Uo/Voc, Io/Isc, Po/Po) of the D1010-05* series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added 
connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. 
See parameters on

 

enclosure side and the ones indicated in the table below: 

D1010-054, D1010-056, D1010-057 

Terminals 

Ch1 

15 - 16 

Po / Po = 11 mW 

Ch1 

Ch1 

15 - 16 

15 - 16 

Io / Isc = 38 mA 

 

Ii/ Imax 

 

Pi / Pi 

Ci / Ci  C cable 

 

Li / Li L cable 

 

(IIC-A, B) 

Co / Ca = 100 µF 

Co / Ca = 1000 µF 
Co / Ca = 1000 µF 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / La = 11.3 mH 
Lo / La = 45.3 mH 
Lo / La = 90.7 mH 

(IIB-C) 
(IIA-D) 

 

 

D1010-054, D1010-056, D1010-057 

Associated 

Apparatus Parameters 

D1010-054, D1010-056, D1010-057 

Terminals 

Ch1 

15 - 16 

Ch1 

15 - 16 

Li / Ri device and 

L cable / R cable 

 

(IIC-A, B) 

Lo / Ro = 3490 µH/

 

Lo / Ro = 13963 µH/

 

Lo / Ro = 27927 µH/

 

(IIB-C) 
(IIA-D) 

Ch1 

15 - 16 

When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D1010-05* Associated Apparatus are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below: 

Must 

be 

Hazardous Area 

Device Parameters 

D1010-054, D1010-056, D1010-057 

Associated 

Apparatus Parameters 

Ui / Vmax = 30V 

Uo / Voc 

D1010-054, D1010-056, D1010-057 

Terminals 

li / Imax = 104 mA 

 

Io / Isc 

 

Ci = 1.05 nF, Li= 0 nH 

Ch1 

15 - 16 

Ch1 

15 - 16 

Ch1 

15 - 16 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 

Summary of Contents for D1010S-054

Page 1: ...D1010 054 056 057 mV to mA Converter ISM0098 8 D1010S 054 D1010S 056 D1010S 057 INSTRUCTION MANUAL mV to mA Converter DIN Rail Models D1010S 054 D1010S 056 D1010S 057...

Page 2: ...oad 23 1 C ambient temperature Calibration accuracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 02 of full scale for a min to max supply change Load influence 0 02 o...

Page 3: ...gh Accuracy Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 ATEX IECEx Certifications High Reliability SMD components Simplified installation using standard DIN R...

Page 4: ...Co Ca 100 F Co Ca 1000 F Co Ca 1000 F IIB C IIA D IIC A B Lo La 11 3 mH Lo La 45 3 mH Lo La 90 7 mH IIB C IIA D D1010 054 D1010 056 D1010 057 Associated Apparatus Parameters D1010 054 D1010 056 D1010...

Page 5: ...mA Converter G M International ISM0098 8 Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 MODELS D1010S 054 D1010S 056 D1010S 057 15 16 3 4 1 2 RL mA Supply 24 V...

Page 6: ...10 05 must be cleaned only with a damp or antistatic cloth Any penetration of cleaning liquid must be avoided to prevent damage to the unit Any unauthorized card modification must be avoided According...

Page 7: ...3 4 1 2 Connect the unit as shown below Set power supply PS at 24 0 V at terminals 3 and 4 the calibrator CAL in the function mV 100 mV range at terminals 15 and 16 the multimeter DMM for the reading...

Page 8: ...35 000 mV and regulate the current read by multimeter DMM by turning the span trimmer of the unit see Configuration section until reading 20 000 mA 5 A value Set the calibrator CAL at 5 000 mV and reg...

Reviews: