GMI D1010S-054 Instruction Manual Download Page 2

 

D1010-054 / 056/ 057 

- mV to mA Converter 

G.M. International ISM0098-8 

General Description:

 The single channel DIN Rail mV to mA converters, D1010S-054, D1010S-056, D1010S-057, convert a mV signal from sensors located in Hazardous Area, 

and repeat the current in floating circuit to drive a Safe Area load. 

Function:

 1 channel I.S. analog input, provides 3 port isolation (input/output/supply) and current (source) output signal. 

Signalling LED:

 Power supply indication (green). 

EMC:

 Fully compliant with CE marking applicable requirements. 

Supply:

 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V: 

40 mA with 20 mA output typical. 

Power dissipation:

 0.9 W with 24 V supply voltage and 20 mA output typical. 

Max. power consumption: 

at 30 V supply voltage and overload condition 1.2 W. 

Isolation (Test Voltage):

 I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 500 V. 

Input:

 

-5 to +55 mV for D1010S-054; 
-5 to +35 mV for D1010S-056; 
-5 to +10 mV for D1010S-057; 

Output:

 4 to 20 mA, on 250 

 load in source mode. 

Response time: 

25 ms (10 to 90 % step change) with 8.6 dB of NMRR. 

Common mode rejection: 

better than 80 dB. 

Output ripple:

 

 20 mVrms on 250 

 load. 

Burnout: 

Upscale in 25 ms. 

Performance:

 Ref. Conditions 24 V supply, 250 

 load, 23 ± 1 °C ambient temperature. 

Calibration accuracy: 

 ± 0.1 % of full scale. 

Linearity error: 

 ± 0.1 % of full scale. 

Supply voltage influence: 

 ± 0.02 % of full scale for a min to max supply change. 

Load influence: 

 ± 0.02 % of full scale for a 0 to 100 % load resistance change. 

Stability: 

estimated degradation in 3 years 

 ± 0.47 % least sensitive range. 

Compatibility: 

 
CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive. 

Environmental conditions: 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 95 %. 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety Description:

 

II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA II T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus. 
Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16. Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16. 
Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals:  

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11, 
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15, 

Mounting:

  

T35 DIN Rail according to EN50022. 

Weight: 

about 110 g. 

Connection: 

by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location: 

Safe Area or Zone 2, Group IIC T4 installation. 

Protection class: 

IP 20. 

Dimensions: 

Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

Characteristics 

 

Summary of Contents for D1010S-054

Page 1: ...D1010 054 056 057 mV to mA Converter ISM0098 8 D1010S 054 D1010S 056 D1010S 057 INSTRUCTION MANUAL mV to mA Converter DIN Rail Models D1010S 054 D1010S 056 D1010S 057...

Page 2: ...oad 23 1 C ambient temperature Calibration accuracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 02 of full scale for a min to max supply change Load influence 0 02 o...

Page 3: ...gh Accuracy Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 ATEX IECEx Certifications High Reliability SMD components Simplified installation using standard DIN R...

Page 4: ...Co Ca 100 F Co Ca 1000 F Co Ca 1000 F IIB C IIA D IIC A B Lo La 11 3 mH Lo La 45 3 mH Lo La 90 7 mH IIB C IIA D D1010 054 D1010 056 D1010 057 Associated Apparatus Parameters D1010 054 D1010 056 D1010...

Page 5: ...mA Converter G M International ISM0098 8 Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 MODELS D1010S 054 D1010S 056 D1010S 057 15 16 3 4 1 2 RL mA Supply 24 V...

Page 6: ...10 05 must be cleaned only with a damp or antistatic cloth Any penetration of cleaning liquid must be avoided to prevent damage to the unit Any unauthorized card modification must be avoided According...

Page 7: ...3 4 1 2 Connect the unit as shown below Set power supply PS at 24 0 V at terminals 3 and 4 the calibrator CAL in the function mV 100 mV range at terminals 15 and 16 the multimeter DMM for the reading...

Page 8: ...35 000 mV and regulate the current read by multimeter DMM by turning the span trimmer of the unit see Configuration section until reading 20 000 mA 5 A value Set the calibrator CAL at 5 000 mV and reg...