![GMC Camille Bauer SINEAX DM5000 Operating Instructions Manual Download Page 31](http://html.mh-extra.com/html/gmc/camille-bauer-sineax-dm5000/camille-bauer-sineax-dm5000_operating-instructions-manual_2235743031.webp)
PM 1001484 000 06
Device handbook SINEAX DM5000
31/87
6.2 Parametrization of the device functionality
A full parameterization of all functions of the device is possible directly at the device (for devices with
display only) or via web browser. See:
6.3 Installation check
The correct connection of the current and voltage inputs can be checked in two ways.
a)
Sense of rotation check
: Using the sequence of the current and voltage phasors the sense of
rotation is determined and compared to the configured one. The phase rotation indicator is arranged
in the menu “Phasor diagram”.
Test requirement: Magnitude of all connected voltages at least 5% of nominal, magnitude of all
connected currents at least 0.2% of nominal.
Possible results
Correct sense of rotation
Wrong sense of rotation
Missing phase or magnitude too
small