3
D5290S-079
- 5 A SIL 3 Relay Output Module (115 Vac coil voltage)
G.M. International ISM0153-2
Ordering Information
Front Panel and Features
•
SIL 3 according to IEC 61508 for Tproof = 10 / 20 years (10 / 20 % of total SIF)
with PFDavg (1 year) 7.01 E-06, SFF = 99.00 % for two NE loads (see application n° 1, 2) or a ND load (see application n° 4)
with NE relay condition.
•
SIL 2 according to IEC 61508 for Tproof = 7 / 14 years (10 / 20 % of total SIF)
with PFDavg (1 year) 1.40 E-04, SFF = 60.12 % for four NE loads with NE relay condition (see application n° 3).
•
5 A SIL 3 / SIL 2 contacts for NE or ND loads with NE Relay condition.
•
Input/Output isolation.
•
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
•
TÜV Certification.
•
Simplified installation using standard DIN-Rail and plug-in terminal blocks.
Model: D5290S-079
DIN-Rail accessories: Cover and fix MCHP196
Normally Open (NO) contact (Out S_1)
Terminal block connections
SAFE AREA
13
4 3 2 1
13 14 15 16
17 18 19 20
21 22 23 24
14
15
16
17
18
19
20
21
22
23
24
1
3
2
4
Normally Open (NO) contact (Out S_2)
Normally Closed (NC) contact (Out P_1)
Normally Closed (NC) contact (Out P_2)
Normally Open (NO) contact (Out S_4)
Normally Open (NO) contact (Out S_3)
115 Vac Input signal line
115 Vac Input signal line