D5098 

- 5 A SIL 3 Relay Out Module for NE Load 

G.M. International ISM0305-2 

Ordering information 

Front Panel and Features 



SIL 3 (low demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2, with Tproof = 14 / 20 yrs (10 / 20 % of total SIF) and 

PFDavg (1 year) = 7.02 E-06, SFF = 98.71 %. 



SIL 3 (high demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2, with PFH = 1.60 E-09 h

-1



Systematic capability SIL 3. 



Installation in Zone 2. 



Compatible with DCS/PLC pulse testing. 



SIL 3 contact for NE Load and contact for service purposes. 



6 A inrush current at 24 Vdc / 250 Vac. 



Input/Output isolation. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



ATEX, IECEx, TÜV Certifications. 



TÜV Functional Safety Certification.  



Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards. 

 

 

DIN-Rail accessories: Cover and fix MCHP196 
Terminal block male MOR017 

Terminal block female MOR022 

Terminal block connections 

(CM1) 1st pole of Out 1 (NO contact) for NE Load or (NC contact) for Service 

SAFE AREA 

(NO1) 2nd pole of Out 1 (NO contact) for NE Load 

(CM2) 1st pole of Out 2 (NO contact) for NE Load or (NC contact) for Service 

7

 

8

 

9

 

+ Input 

1

 

- Input 

2

 

+ Input (only for D5098D) 

3

 

- Input (only for D5098D) 

4

 

(NO2) 2nd pole of Out 2 (NO contact) for NE Load 

10

 

(NC1) 2nd pole of Out 1 (NC contact) for Service load 

(NC2) 2nd pole of Out 2 (NC contact) for Service load 

11

 

12

 

Not used 

5

 

Not used 

6

 

2 channels 

1 channel 

Model:  

D5098 

7 8 

9 10 

11 12 

D5098 

7  8 

1  2 

SIL 3 

9  10 

STS 1 

11  12 

3  4 

STS 2 

Summary of Contents for D5098S

Page 1: ...D5098 5 A SIL 3 Relay Out Module for NE Load G M International ISM0305 2 5 A SIL 3 Relay Output Module for NE Load DIN Rail and Termination Board Models D5098S D5098D D5098S D5098D INSTRUCTION MANUAL ...

Page 2: ...ating temperature limits 40 to 70 C relative humidity 95 up to 55 C Storage temperature limits 45 to 80 C Safety Description ATEX II 3G Ex nA nC IIC T4 Gc IECEx Ex nA nC IIC T4 Gc non sparking electrical equipment 40 C Ta 70 C Approvals IMQ 17 ATEX 009 X conforms to EN60079 0 EN60079 15 IECEx IMQ 17 0006X conforms to IEC60079 0 IEC60079 15 TÜV Certificate No C IS 272994 01 SIL 3 conforms to IEC615...

Page 3: ...safety system ATEX IECEx TÜV Certifications TÜV Functional Safety Certification Simplified installation using standard DIN Rail and plug in terminal blocks or customized Termination Boards DIN Rail accessories Cover and fix MCHP196 Terminal block male MOR017 Terminal block female MOR022 Terminal block connections CM1 1st pole of Out 1 NO contact for NE Load or NC contact for Service SAFE AREA NO1 ...

Page 4: ...open terminals 7 11 and 9 12 are closed To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay breaking capacity diagram MODEL D5098D Out 1 NO contact NO1 8 CM1 7 In 1 1 2 Service Load Out 1 Termination board connector Not SIL NC1 11 Out 2 NO contact NO2 10 CM2 9 In 2 3 4 Service Load Out 2 Not SIL NC2 12 SIL 3 SIL 3 2 Inputs 2 Loads ...

Page 5: ...ilar chosen according to the relay breaking capacity diagram MODEL D5098S Out 1 NO contact NO1 8 CM1 7 In 1 1 2 Service Load Out 1 Termination board connector Not SIL NC1 11 SIL 3 MODEL D5098D Out 1 NO contact NO1 8 CM1 7 In 1 1 2 Service Load Out 1 Termination board connector Not SIL NC1 11 Out 2 NO contact NO2 10 CM2 9 3 4 Service Load Out 2 Not SIL NC2 12 SIL 3 SIL 3 Relay contacts shown in de ...

Page 6: ...to the relay breaking capacity diagram on data sheet The enclosure provides according to EN60529 an IP20 minimum degree of protection or similar to NEMA Standard 250 type 1 For non hazardous location the unit shall be installed in an area of not more than pollution degree 2 For hazardous location the unit shall be installed in a certified Ex enclosure with a minimum ingress protection of at least ...