0020239568_03 Ultimate 3 Installation and maintenance instructions
23
Condition
: 230 V 3-wire connection
▶
Ensure that the control is designed for a maximum nom-
inal current of 7 A.
▶
Connect the control to the main plug X1.
–
Terminal assignment: L
‑
line, N
‑
neutral conductor,
‑
earth
▶
Draw the end user's attention to the fact that the follow-
ing features are present with this installation type.
◁
The frost protection function is deactivated. If the
product is installed in a room where there is a risk
of frost and it has not been protected by a room ther-
mostat, install an additional frost protection thermo-
stat.
◁
The pump programmes are not active.
◁
If the product is switched off, the display is switched
off.
◁
Each time the unit is started, the fan runs for
20 seconds.
◁
Residual heat in the heating return may result in the
product blocking the burner for 10 minutes.
4.
Close the electronics box.
Summary of Contents for Ultimate 3
Page 1: ...en Installation and maintenance instructions Ultimate 3 25r A H GB 0020239568_03 31 07 2020...
Page 49: ......
Page 50: ......
Page 51: ......