Glow-worm MiSet SRT 380 Operating And Installation Instructions Download Page 5

Product description 2

0020288229_00

MiSet

Operating and installation instructions

5

2 Product description

2.1 Which nomenclature is used?

System control: Instead of

SRT 380

Remote control: Instead of

SR 92

2.2 What is the effect of the frost

protection function?

The frost protection function protects the
heating installation and flat from frost dam-
age.
At outdoor temperatures

Below 4 °C for longer than four hours,
the system control switches the heat
generator on and regulates the target
room temperature to at least 5 °C.

Above 4 °C, the system control does
not switch the heat generator on, but it
monitors the outdoor temperature.

2.3 What do the following

temperatures mean?

Desired temp.

is the temperature to which

you want to heat up the living rooms.

Set-back temp.

is the level below which

the temperature in the living rooms does
not fall when outside of the time periods.

Flow temp.

is the temperature at which

the heating water leaves the heat gener-
ator.

2.4 What is a zone?

A building can be divided into multiple
areas, which are known as zones. A dif-
ferent requirement can be placed on the
heating installation in each zone.
Examples for dividing into zones:

Underfloor heating (zone 1) and panel
radiator heating (zone 2) are available in
one building.

A building is made up of several self-
contained residential units. Each resid-
ential unit has its own zone.

2.5 What is the circulation?

An additional water pipe is connected to
the domestic hot water pipe and forms a
circuit with the domestic hot water cylin-
der. A circulation pump facilitates the con-
tinuous circulation of domestic hot water
through the pipework system which means
that hot water is immediately available,
even at more distant draw-off points.

2.6 What is meant by "time

period"?

Example of heating mode in the mode:
Time-controlled

24 °C

18:00

16:30

22:30

16 °C

21 °C

20:00

A

B

5

1

2

3

4

A

Time

B

Temperature

1

Desired temper-
ature

2

Set-back tem-
perature

3

Time period 2

4

Outside of the
time periods

5

Time period 1

You can divide a day up into several time
periods

(3)

and

(5)

. Each time period can

comprise an individual start time and end
time. The time periods must not overlap.
You can assign a different desired temper-
ature

(1)

to each time period.

Example:
16:30 to 18:00; 21 °C
20:00 to 22:30; 24 °C
The system control regulates the living
rooms to the desired temperature within
the time periods. In the times outside of
the time periods

(4)

, the system control

Summary of Contents for MiSet SRT 380

Page 1: ...Operating and in stallation instructions MiSet SRT 380 GB IE...

Page 2: ...ling the system control 15 4 Start up 17 4 1 Prerequisites for starting up 17 4 2 Running the installation assistants 17 4 3 Changing the settings later 17 5 Fault and maintenance messages 17 5 1 Faul...

Page 3: ...IP code This product can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given su...

Page 4: ...ns and all other ap plicable documents particu larly the Safety section and the warnings As the end user you should only carry out those activities for which these instructions provide instructions an...

Page 5: ...ation in each zone Examples for dividing into zones Underfloor heating zone 1 and panel radiator heating zone 2 are available in one building A building is made up of several self contained residentia...

Page 6: ...C D 18 22 20 0 4 70 60 50 40 30 15 10 5 0 5 10 15 20 A Outdoor temper ature C B Target flow tem perature C C Target room temperature C D Axis a If the heat curve 0 4 is selected and 21 C is specified...

Page 7: ...ion 2 0020288229_00 MiSet Operating and installation instructions 7 2 9 2 Symbols Time controlled heating active Button lock active Maintenance required Fault in the heating installation Contact the c...

Page 8: ...on behaves out side of the time period in the Set back mode function In Set back mode means Eco The heating is switched off outside of the time periods Frost protection is activated Normal The set bac...

Page 9: ...he desired temperature for Monday Friday and Sat urday Sunday the programming applies for the time controlled Heat ing Domestic hot water and Circulation functions Overwrites the weekly planner for th...

Page 10: ...of the temperature difference between the measured value in the system control and the value for a reference thermometer in the living room Outdoor temper ature K Comparison of the temperature differe...

Page 11: ...it for the target flow temperature The system control compares the set value with the calculated target flow temperature and regulates to the smaller of these values Set back mode Eco The heating func...

Page 12: ...rresponds to a modulating control system Zone Zone activated Deactivate zones that are not required All existing zones appear in the display Zone assignment Assign the system control and or remote con...

Page 13: ...m control enables the heating function The setting Off means that the cylinder char ging time is not restricted Cyl charg anti cycl time min Setting the time period during which the cylinder charging...

Page 14: ...ectrical installation The heating installation must be decom missioned before work is carried out on it 3 1 Selecting the lines Do not use flexible lines for power sup ply cables Use sheathed cables f...

Page 15: ...Electrical installation set up 3 0020288229_00 MiSet Operating and installation instructions 15 3 2 Installing the system control 6 1 5 m 6 60 1 25 mm A B C 2...

Page 16: ...3 Electrical installation set up 16 Operating and installation instructions MiSet 0020288229_00 A B 3...

Page 17: ...sist ant switches to the basic display and the heating installation works with the values you have set 4 3 Changing the settings later All settings that you have made via the in stallation assistant c...

Page 18: ...ss that is provided on the back page or you can visit www glow worm co uk 6 7 Recycling and disposal The competent person who installed your product is responsible for the dis posal of the packaging I...

Page 19: ..._00 MiSet Operating and installation instructions 19 Temperature for the ball pressure test 75 Maximum permitted environ mental temperature 0 to 60 Current room air hum 35 to 95 Mode of operation Type...

Page 20: ...Switch off the mains switch on all heat generators for approx 1 minute and then switch them on again 3 If the fault message persists inform the competent person Display Button lock activated it is not...

Page 21: ...the heat generator this is the same power supply that feeds the system control The product is defect ive Replace the product No changes in the display can be made via the control ele ments Software er...

Page 22: ...n the correct address to the remote control in the Zone assignment function Zone activation miss ing A zone that is in use is not yet activated In the Zone activated function select the value Yes B 3...

Page 23: ...nes maximum length 14 Lines minimum cross section 14 Lines selecting 14 M Maintenance 17 O Operating and display functions 8 P Prerequisites for starting up the heating installation 17 Prerequisites s...

Page 24: ...9 Technical helpline 0330 100 7679 After sales service 0330 100 3142 www glow worm co uk 0020288229_00 12 12 2019 These instructions or parts thereof are protected by copyright and may be reproduced o...

Reviews: