
Product description 2
0020288229_00
MiSet
Operating and installation instructions
11
MENU
→
SETTINGS
→
Installer level
→
Installation configuration
→
Control:
Weath.-
comp.
It is controlled via the outdoor temperature as soon
as an outdoor temperature sensor is connected.
→
Heat generator 1
→
Status:
→
Current flow temperature: °C
→
Circuit 1
→
Status:
→
Target flow temperature: °C
→
OT switch-off
threshold: °C
Enter the upper limit for the outdoor temperature. If the outdoor
temperature rises above the set value, the system control deac-
tivates heating mode.
→
Heat curve:
The heat curve (
→
section "Product description") is the depend-
ence of the flow temperature on the outdoor temperature for the
desired temperature (target room temperature).
→
Min. target flow tem-
perature:°C
Enter the lower limit for the target flow temperature. The system
control compares the set value with the calculated target flow
temperature, and regulates to the larger of these values.
→
Max. target flow tem-
perature:°C
Enter the upper limit for the target flow temperature. The system
control compares the set value with the calculated target flow
temperature, and regulates to the smaller of these values.
→
Set-back mode:
→
Eco
The heating function is switched off and the frost
protection function is activated.
At outdoor temperatures that are below 4 °C for
longer than four hours, the system control switches
the heat generator on and regulates to the
Set-
back temperature: °C
. At an outdoor temperature
above 4 °C, the system control switches the heat
generator off. The monitoring of the outdoor tem-
perature remains active.
Heating circuit behaviour outside of the time peri-
ods. Prerequisite:
–
Time-contr.
is activated in the
Heating
→
Mode:
function.
–
Active
or
Inactive
is activated in the
Room
temp. mod.:
function.
If
Expanded
is activated in the
Room temp.
mod.:
, the system control regulates to the target
room temperature 5 °C independently of the
outdoor temperature.
→
Normal
The heating function is switched on. The system
control regulates to the
Set-back temperature: °C
.
Prerequisite:
Time-contr.
is activated in the
Heat-
ing
→
Mode:
function.
The behaviour can be adjusted separately for each heating circuit.
→
Room temp. mod.:
→
Inactive