background image

20

2000225227C

8 Servicing

Diagram 8.2

BAFFLE
(6 off)

12312

REMEMBER:

 When replacing a part on this appliance, use

only spare parts that you can be assured conform to the safety
and performance specification that we require.  Do not use
reconditioned or copy parts that have not been clearly authorised
by Glow-worm.

Products of Combustion Check

Note: To obtain a products of combustion reading, remove the
cap from the sampling point, located on top of the inner casing,
see diagram 8.1.

Connect the analyser tube onto the nipple.

Switch on the electrical supply and gas supply then operate the
boiler.

On completion of the test switch off the electrical supply and the
gas supply, remove analyser tube and replace sampling point
cap.

Servicing

Before servicing turn off the gas and isolate the electrical supply
to the boiler.

After completing a service always test for gas soundness, make
electrical checks and carry out functional check on controls.

Unless stated otherwise all parts are replaced in the reverse
order to removal.

8.1 Access

Remove the boiler case, see diagram 5.1 and Section 5.2.

8.2 Burner

Remove front combustion chamber cover which is secured by
two screws, see diagram 8.3.

Pull back electrode protection sleeve and disconnect electrode
connection along with earth connection, see diagram 8.6.

Remove the burner retaining screw located at the right hand
side of the burner, see diagram 8.4.

When completed, take hold of burner and slide it to the left
clearing the injector and remove.  Take care not to damage the
combustion chamber insulation

Use a vacuum cleaner or suitable stiff brush (not wire) to clean
the burner thoroughly, making sure that all the burner ports are
clear and unobstructed.

On refitting and after cleaning the heat exchanger make sure
the burner is fitted correctly, that is, located on the  injector and
horizontal.

Note: It is advisable while servicing the burner to check the
combustion chamber  insulation and replace if damaged, see
Section 10.10.

8.3 Cleaning Heat Exchanger Flueways

Disconnect the air pressure switch tube connections, red from
fan, both clear tubes from test nipple, see diagram 8.1.

Remove the blue and purple electrical connections from the fan
see diagram 5.5.

If top outlet  installation: Remove air deflector, or it may just be
swung back by loosening the wing-nuts, to enable fan assembly
to be removed, see diagram 8.7 and Section 5.3.

Remove the fan assembly complete with the flue elbow, see
diagram 5.5 and Section 5.3.

Place a sheet of paper in the base of the combustion chamber
and over the injector to prevent particles entering.

Remove the baffles, see diagram 8.2.

Diagram 8.1

CLEAR AIR

PRESSURE
TUBES

SAMPLING

POINT

RED AIR
PRESSURE

TUBE

7231

COMBUSTION
CHAMBER COVER

SCREW

Diagram 8.3

6778

Diagram 8.4

7226

BURNER RETAINING

SCREW

BURNER

Summary of Contents for Micron 50FF

Page 1: ...I2H Appliance Reference in these instructions to British Standards and Statutory Regulations Requirements apply only to the United Kingdom For Ireland the current edition of I S 813 Domestic Gas Insta...

Page 2: ...tified body 0086 The CE mark on this appliance shows compliance with 1 Directive 90 396 EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels 2 Directi...

Page 3: ...on the owner of the property by the current issue of The Gas Safety Installation and Use Regulations Section 35 It is the law that any servicing is carried out by a competent person To obtain service...

Page 4: ...ied out by a competent person and installed in accordance with the current edition of I S 813 Domestic Gas Installations the current Building Regulations and reference should be made to the current ET...

Page 5: ...nd any applicable local regulations External wiring must be correctly earthed polarised and in accordance with the relevant standards In GB this is BS6891 In IE this is the current edition of I S 813...

Page 6: ...ram 1 3 This boiler must be positioned so that at least the minimum operational and servicing clearances are provided Additional clearances may be required for installation If fixtures are positioned...

Page 7: ...ons There are various flue systems to choose from as follows Standard Top Outlet Flue Pack Pt No 230483 Easyfit Top Outlet Flue Pack Pt No 232057 Standard Rear Outlet Flue Pack Pt No 230482 Extended T...

Page 8: ...fer also to the current edition of I S 813 Domestic Gas Installations In GB it is necessary to comply with the Water Supply Water Fittings Regulations 1999 for Scotland the Water Byelaws 2000 Scotland...

Page 9: ...g is also given in the current issue of BS5449 and BS7074 Part 1 for IE refer to the current edition of I S 813 Domestic Gas Installations The charge pressure must not be less than the static head of...

Page 10: ...10 2000225227C 4 Flue and Appliance Preparation Diagram 4 1 9354...

Page 11: ...pplies if you use the flue kit without the optional wall liner kit irrespective of wall thickness 4 3 Rear Top and Side Flue Application Select the boiler location and flue application with due regard...

Page 12: ...screw see diagram 4 6 4 7 Internal Access Flue If access to the outside wall is not practical the flue system can be installed from inside Use of the optional wall liner kit is required 4 8 Rear Flue...

Page 13: ...flue bend orientations is incorporated Instructions are supplied with these kits Lift the boiler into position hooking over the top mounting bracket Note Anti theft screw kits are available part no s...

Page 14: ...t in air deflector allows you to do this to allow easy access to fitting fan assembly Note Apply soap to seals on flue duct extension piece to help it slide in be careful not to damage O ring Insert f...

Page 15: ...s to be installed it should be fittedatthisstage seeseparateinstallationinstructionssupplied with programmer Take care not to damage any internal wiring Using heat resistant 85o C cable of at least 0...

Page 16: ...LUE DUCT EXTENSION Diagram 5 8 MAINS SUPPLY 230V 50Hz BLOCK CONNECTOR bl LS N g y g y g y br b bl b b Diagram 5 10 SECURING SCREW 12384 CONTROL BOX HINGE PIN CABLE CLAMP GROMMET Diagram 5 11 7333 TAIL...

Page 17: ...uge should be set to coincide with the indicating pointer 6 3 Initial Lighting and Testing CAUTION This work must be carried out by a competent person in accordance with the current issue of BS6798 Ma...

Page 18: ...decrease pressure see diagram 6 2 Replace cap Should any doubt exist about the gas rate check it using the gas meter test dial and stop watch at least 10 minutes after the burner has lit making sure t...

Page 19: ...d be enough Draw attention if applicable to the current issue of the Gas Safety Installation and Use Regulations Section 35 which imposes a duty of care on all persons who let out any property contain...

Page 20: ...emove the burner retaining screw located at the right hand side of the burner see diagram 8 4 When completed take hold of burner and slide it to the left clearing the injector and remove Take care not...

Page 21: ...tes at any other time do as above the burner should relight If the fault persists refer to fault finding chart AIR DEFLECTOR WING NUT 2 8 Servicing Diagram 8 5 BURNER INJECTOR 6801 Clean the heat exch...

Page 22: ...22 2000225227C Diagram 9 2 9 Fault Finding 10270...

Page 23: ...23 2000225227C Diagram 9 3 10271 9 Fault Finding 10275...

Page 24: ...ER P C B CONTROL BOARD GAS CONTROL VALVE THERMISTOR ELECTRODE AIR PRESSURE SWITCH T3 15A FUSE p y g p b bk b bk bk b r g y br br br br br r g y g y A B JUMPER POSITION LS LIVE Switched NEUTRAL EARTH M...

Page 25: ...the cable clips these are located down left hand side of boiler Draw thermistor lead followed by thermistor out through the case grommet Re assembly note When fitting the electrical thermistor make su...

Page 26: ...and swing out the control box see diagram 5 10 Disconnect the electrical plug Disconnect the gas cock on the left hand side Support the multifunctional control remove the four extended screws from the...

Page 27: ...227034 diagram 10 7 Refer to Section 5 3 Remove the electrical connections and disconnect the air tubes Note Remove the electrical connections by pulling insulation boots only If top outlet installat...

Page 28: ...provement details may vary slightly from those in the instructions Ref Part No Description Location GC Part No 1 2000801159 Multifunctional control Diagram 10 4 E24851 2 227034 Fan Diagram 10 7 E24975...

Reviews: