Global Power Technologies
1-4
5030
1 .6 Fuel Considerations
Clean Fuel
The fuel used to operate the GPT model 5030 must be clean. See the gas spec
-
ification in section 4.1. If dirty fuel is anticipated then a customer supplied in line fuel filter is
recommended.
Low Temperatures
When using propane (C
3
H
8
) at temperatures below -35ºC (-30ºF) special
consideration must be given to vaporization of the fuel.
Supply Pressure
A minimum gas supply pressure of 105 kPa (15 psi) must be supplied to
the regulator inlet of the generator. A maximum of 172 kPa (25 psi), the rating of the pressure
regulator, is allowed.