CONTROLS
BUZZER SILENCE
: Pressing this button will silence the internal buzzer during a new FIRE condition as well as during a new FAULT
condition.
BUZZER SILENCE
: If the LED is lit it indicates that a new FIRE or FAULT condition is present on the system.
SYSTEM RESET
: Pressing this button restores the panel to its normal operating condition after an alarm. Alarms must be silenced
before a SYSTEM RESET can be performed. A SYSTEM RESET does not clear any settings or disablements; it only clears FIRE and FAULT
conditions (and then only if the source of the FIRE or FAULT has been cleared).
LAMP TEST
: Whilst this button is depressed all of the repeater’s LEDs will be illuminated and all of the LCD display pixels will be set to
black. Use this button to confirm the LEDs and LCD display are functional.
SOUNDERS ACTIVATE/SILENCE
: Pressing this button will activate all sounders (main panel and Repeaters). Pressing the button
again will silence the sounders.
SOUNDERS ACTIVATE/SILENCE
: If the LED is lit it means that all sounders are active.
DISABLEMENTS
AUXILIARY RELAYS
: Pressing this switch disables or enables all the relay and I/O module outputs.
AUXILIARY RELAYS
: If the LED is lit it means that the relay and I/O module outputs are disabled.
SOUNDERS DISABLE
: Pressing this button disables or enables the SOUNDERS on a SYSTEM.
SOUNDERS DISABLE
: If the LED is lit it means that the SOUNDERS on the SYSTEM are disabled.
SELECTED DETECTORS
: Using the programming functions individual detectors can be set for SELECTIVE DISABLEMENT. When this
button is activated those detectors will be disabled (isolated). Note that this button will only operate if at least one detector has been
set for SELECTIVE DISABLEMENT.
SELECTED DETECTORS
: If the LED is AMBER it means that the selected detectors are isolated.
ACTIVE DELAYS
: Delays can be configured for the sounders
and I/O modules using the programming functions. Pressing this
button enables or disables these delays.
ACTIVE DELAYS:
If the LED is AMBER it means that the delays are active.
QUEUE REVIEW
FIRE
: If there is more than one FIRE pressing this button will display the next FIRE report on the LCD display for 20 seconds.
Subsequent presses will step through all the FIRE reports.
FIRE
: If the LED is flashing RED it means that there are FIRE reports to be reviewed. If the LED is steady RED then all FIRE reports have
been reviewed.
FAULT
: If there is more than one FAULT, or if there is at least one FAULT and a FIRE, pressing this button will display the next FAULT
report on the LCD display for 20 seconds. Subsequent presses will step through all the FAULT reports.
FAULT
: If the LED is flashing AMBER it means that are FAULT reports to be reviewed. If the LED is steady AMBER then all FAULT reports
have been reviewed.
TEST
: If there are ZONES in test mode then pressing this button will show those ZONES on the LCD display. If more ZONES are in test
mode than can be shown on the LCD display at one time then subsequent presses of the button will step through all the ZONES in
test mode.
TEST
: If the LED is AMBER it means that one or more ZONES are in test mode.
DISABLED
: If there are disablements then pressing this button will show the disablements on the LCD display. If there are more
disablements than can be shown on the LCD display at one time then subsequent presses of this button will step through all the
disablements.
DISABLED
: If the LED is AMBER it means that there is at least one disablement.
ZONES
ZONE FIRE INDICATION
: When RED led is lit for a particular zone it will indicate the presence of a FIRE condition in that zone. A
separate LED is provided for each zone in the range from 1 to 16.
NOTE:
The functions of the switches, except for the LAMP TEST switch will only be operational after either the Authorized
User ( Access Level 2) or the Programming Code ( Access Level 3) is entered. Please consult Panel’s Installation and User
Manual for further details.